Difference between revisions of "LMF Metal Cap Flashing (inside corner)"
Difference between revisions of "LMF Metal Cap Flashing (inside corner)"
(→WORK INCLUDED) |
|||
Line 21: | Line 21: | ||
(4) <b>Metal Cap Flashing – Interior Face:</b> Fastened with continuous clips or cladding screws evenly spaced between seams. Over 100 mm (4") width requires standing seam. See [[RoofStar Guarantee Standards for SBS Roof Systems#SBSMETALBASE|'''SBS Roof Systems - 12.6 Cap Flashings, Base Flashings and Reglets''']] for requirements. | (4) <b>Metal Cap Flashing – Interior Face:</b> Fastened with continuous clips or cladding screws evenly spaced between seams. Over 100 mm (4") width requires standing seam. See [[RoofStar Guarantee Standards for SBS Roof Systems#SBSMETALBASE|'''SBS Roof Systems - 12.6 Cap Flashings, Base Flashings and Reglets''']] for requirements. | ||
− | (5) <b>Seam:</b> Lap seam is acceptable if vertical distance is not more than 100 mm (4"). Again see [[RoofStar Guarantee Standards for SBS Roof Systems#SBSMETALSEAM|'''SBS Roof Systems - 12.5 Seams''']]. | + | (5) <b>Seam:</b> Lap seam in a corner is acceptable if vertical distance is not more than 100 mm (4"). Again see [[RoofStar Guarantee Standards for SBS Roof Systems#SBSMETALSEAM|'''SBS Roof Systems - 12.5 Seams''']]. |
(6) <b>Metal Cap Flashing – Top Face:</b> Over 100 mm (4") width must provide positive slope to roof area. | (6) <b>Metal Cap Flashing – Top Face:</b> Over 100 mm (4") width must provide positive slope to roof area. | ||
Line 28: | Line 28: | ||
(8) <b>Metal Cap Flashing – Outside Face:</b> Corner standing seams may be folded flat on outside face only. Fasten with continuous concealed clip-type fasteners <b>or</b> cladding screws evenly spaced between seams. | (8) <b>Metal Cap Flashing – Outside Face:</b> Corner standing seams may be folded flat on outside face only. Fasten with continuous concealed clip-type fasteners <b>or</b> cladding screws evenly spaced between seams. | ||
− | |||
=== RELATED WORK BY OTHERS === | === RELATED WORK BY OTHERS === |
Revision as of 15:42, 20 November 2019
RoofStar Guarantee Standards are blue-linked |
1 WORK INCLUDED
(1) Metal Cant Flashing: Standing seam required at corners of cant. See SBS Roof Systems - 12.5 Seams.
(2) Metal Base Flashing: Vertical runs over 100 mm (4") require standing seam or S-lock corners. See SBS Roof Systems - 12.6 Cap Flashings, Base Flashings and Reglets. Cross-breaks and cladding-type fasteners are optional.
(3) Double S-Lock Corner: Fastened through concealed flanges to top of parapet. Again, see SBS Roof Systems - 12.5 Seams.
(4) Metal Cap Flashing – Interior Face: Fastened with continuous clips or cladding screws evenly spaced between seams. Over 100 mm (4") width requires standing seam. See SBS Roof Systems - 12.6 Cap Flashings, Base Flashings and Reglets for requirements.
(5) Seam: Lap seam in a corner is acceptable if vertical distance is not more than 100 mm (4"). Again see SBS Roof Systems - 12.5 Seams.
(6) Metal Cap Flashing – Top Face: Over 100 mm (4") width must provide positive slope to roof area.
(7) Standing Seam
(8) Metal Cap Flashing – Outside Face: Corner standing seams may be folded flat on outside face only. Fasten with continuous concealed clip-type fasteners or cladding screws evenly spaced between seams.
2 RELATED WORK BY OTHERS
(A) Acceptable Parapet
(B) Sloped Blocking: Required over minimum 100 mm (4") parapet width. See SBS Roof Systems - 12. Perimeter Flashing: Metal
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.