Line 1: | Line 1: | ||
− | + | <li>An Integrity Scan | |
− | {| | + | <ol> |
− | |- | + | <li>must be performed by an RGC-recognized service provider {{hilite | listed in this ''Manual'' || 2021-October-30 }}. |
− | + | <li>is required on all ''Waterproofing Systems'', to ensure the waterproofing is leak and damage-free, when ''Overburdens'', amenities or equipment are or will be installed on the completed ''Waterproofing System'' by | |
− | + | <ol> | |
− | + | <li>anyone other than the ''Contractor''. | |
− | + | <li>the ''Contractor'' but only when | |
+ | <ol> | ||
+ | <li>{{hilite | the total ''Project'' area (footprint), inclusive of planters or other waterproofed features, exceeds 18.58 m2 (200 sf), and || 2021-October-30 }} | ||
+ | <li>the ''Overburdens'', amenities or equipment exceed 150 mm (6”) in depth. | ||
+ | </li></ol> | ||
+ | <li>is not required when the ''Contractor'' installs overburden, amenities or equipment | ||
+ | <ol> | ||
+ | <li>equal to or less than 150 mm (6”) in depth. | ||
+ | <li>{{hilite | the total ''Project'' area (footprint), inclusive of planters or other waterproofed features, is less than 18.58 m2 (200 sf), but the ''Contractor'' must nevertheless protect all membrane-covered surfaces (including walls and parapets) with RoofStar-accepted protection materials immediately after the membrane is installed || 2021-October-30 }}. | ||
+ | </li></ol> | ||
+ | </li></ol> | ||
+ | <br> | ||
+ | See '''Figure 1.1''' for further reference. |
Revision as of 19:02, 20 October 2020
- must be performed by an RGC-recognized service provider listed in this Manual.
- is required on all Waterproofing Systems, to ensure the waterproofing is leak and damage-free, when Overburdens, amenities or equipment are or will be installed on the completed Waterproofing System by
- anyone other than the Contractor.
- the Contractor but only when
- the total Project area (footprint), inclusive of planters or other waterproofed features, exceeds 18.58 m2 (200 sf), and
- the Overburdens, amenities or equipment exceed 150 mm (6”) in depth.
- is not required when the Contractor installs overburden, amenities or equipment
- equal to or less than 150 mm (6”) in depth.
- the total Project area (footprint), inclusive of planters or other waterproofed features, is less than 18.58 m2 (200 sf), but the Contractor must nevertheless protect all membrane-covered surfaces (including walls and parapets) with RoofStar-accepted protection materials immediately after the membrane is installed.
See Figure 1.1 for further reference.