Difference between revisions of "Draft CD 7"

Jump to: navigation, search

Difference between revisions of "Draft CD 7"

(WORK INCLUDED)
Line 25: Line 25:
 
;(2) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMVALLEYPAN |'''Valley flashing''']]
 
;(2) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMVALLEYPAN |'''Valley flashing''']]
 
;(3) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMFASTENING |'''Fastening''']]: Metal valley panels to be secured with compatible, non-corrosive, flat head fasteners 200 mm (8") o/c. Metal roof panel to metal valley panel overlap must be a minimum of 125 mm (5"). See '''10.3.5.2.2''' ('''5''').
 
;(3) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMFASTENING |'''Fastening''']]: Metal valley panels to be secured with compatible, non-corrosive, flat head fasteners 200 mm (8") o/c. Metal roof panel to metal valley panel overlap must be a minimum of 125 mm (5"). See '''10.3.5.2.2''' ('''5''').
;(4) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMVALOVERLAP |'''Valley panel overlap''']]: Set in two continuous rows of accepted caulking or sealant tape.
+
;(4) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMVALOVERLAP |'''Valley panel overlap''']]: Overlaps minimum 200 mm (8") sealed with two rows of acceptable sealant or butyl tape, and secured with drag load fasteners.
 
;(5) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMICE|'''Membrane flashing''']]: Accepted self-adhered modified bituminous eave protection membrane.
 
;(5) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMICE|'''Membrane flashing''']]: Accepted self-adhered modified bituminous eave protection membrane.
 
;(6) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMUNDERLAYMENT|'''Underlayment''']]: The type of underlay required is determined by roof slope.
 
;(6) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMUNDERLAYMENT|'''Underlayment''']]: The type of underlay required is determined by roof slope.
 
;(7) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMSLIP|'''Ventilation layer''']]: Recommended over asphaltic underlays and / or as required in this Standard (see [http://rpm.rcabc.org/index.php?title=RoofStar_Guarantee_Standards_for_Architectural_Sheet_Metal_(ASM)_Systems#Design_5 '''8.1.2 Design''']).
 
;(7) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMSLIP|'''Ventilation layer''']]: Recommended over asphaltic underlays and / or as required in this Standard (see [http://rpm.rcabc.org/index.php?title=RoofStar_Guarantee_Standards_for_Architectural_Sheet_Metal_(ASM)_Systems#Design_5 '''8.1.2 Design''']).
;(8) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMPANEL |'''Architectural Metal Roof Panel''']]  
+
;(8) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMPANEL |'''Architectural Metal Roof Panel''']]
  
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===

Revision as of 14:21, 5 October 2020

Notice to Reader
Images used in a Construction Detail are representative and not intended in their representation of an assembly to be prescriptive. Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the Standards, Guiding Principles and Recommendations of the RoofStar Guarantee Standards for a Waterproofing or Water-shedding System. Actual design with respect to dimensions, the selection of materials and their application remains the responsibility of the Design Authority.

The full text of applicable RoofStar Guarantee Standards may be read by using the blue hyperlinks
ASM Details

ASM 10.3.1 Hooked Valley Flashing.jpg

Click below for a printable version of this page (N/A)
Print Sheet

1 WORK INCLUDED

(1) Valley Protection Membrane
Accepted self-adhered modified bituminous eave protection membrane.
(2) Valley flashing
(3) Fastening
Metal valley panels to be secured with compatible, non-corrosive, flat head fasteners 200 mm (8") o/c. Metal roof panel to metal valley panel overlap must be a minimum of 125 mm (5"). See 10.3.5.2.2 (5).
(4) Valley panel overlap
Overlaps minimum 200 mm (8") sealed with two rows of acceptable sealant or butyl tape, and secured with drag load fasteners.
(5) Membrane flashing
Accepted self-adhered modified bituminous eave protection membrane.
(6) Underlayment
The type of underlay required is determined by roof slope.
(7) Ventilation layer
Recommended over asphaltic underlays and / or as required in this Standard (see 8.1.2 Design).
(8) Architectural Metal Roof Panel

2 RELATED WORK BY OTHERS

(A) Acceptable Deck

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.


RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems