;(5) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMICE|'''Membrane flashing''']]: Accepted self-adhered modified bituminous eave protection membrane. | ;(5) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMICE|'''Membrane flashing''']]: Accepted self-adhered modified bituminous eave protection membrane. | ||
;(6) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMUNDERLAYMENT|'''Underlayment''']]: The type of underlay required is determined by roof slope. | ;(6) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMUNDERLAYMENT|'''Underlayment''']]: The type of underlay required is determined by roof slope. | ||
− | ;(7) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMSLIP|'''Ventilation layer''']]: | + | ;(7) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMSLIP|'''Ventilation layer''']]: A ventilation space is required on slopes less than 1:3; entangled mesh (shown) may be used as void fill. The ventilation space facilitates drying as condensation forms on the underside of the metal panels. |
;(8) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMVALLEYPAN | '''Sealant or pre-formed closures''']]: Required at the bottom ends of panels. | ;(8) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMVALLEYPAN | '''Sealant or pre-formed closures''']]: Required at the bottom ends of panels. | ||
;(9) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMPANEL |'''Architectural metal roof panel''']] | ;(9) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMPANEL |'''Architectural metal roof panel''']] |
Revision as of 15:59, 7 October 2020
Notice to Reader | |
Images used in a Construction Detail are representative and not intended in their representation of an assembly to be prescriptive. Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the Standards, Guiding Principles and Recommendations of the RoofStar Guarantee Standards for a Waterproofing or Water-shedding System. Actual design with respect to dimensions, the selection of materials and their application remains the responsibility of the Design Authority. The full text of applicable RoofStar Guarantee Standards may be read by using the blue hyperlinks |
SBS Details
1 WORK INCLUDED
- (1) Valley protection membrane
- Accepted self-adhered modified bituminous eave protection membrane.
- (2) Valley Metal Panel
- Preformed with centre rib.
- (3) Metal panel clip
- Installed to metal roof panel manufacturer's printed instructions.
- (4) Valley panel overlap
- Overlaps minimum 200 mm (8") sealed with two rows of acceptable sealant or butyl tape, and secured with drag load fasteners.
- (5) Membrane flashing
- Accepted self-adhered modified bituminous eave protection membrane.
- (6) Underlayment
- The type of underlay required is determined by roof slope.
- (7) Ventilation layer
- A ventilation space is required on slopes less than 1:3; entangled mesh (shown) may be used as void fill. The ventilation space facilitates drying as condensation forms on the underside of the metal panels.
- (8) Sealant or pre-formed closures
- Required at the bottom ends of panels.
- (9) Architectural metal roof panel
2 RELATED WORK BY OTHERS
- (A) Acceptable Deck
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.
RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems