Difference between revisions of "TS Details:E4.7.13 (Tile/Slate - Guilt-in Gutters)"
Difference between revisions of "TS Details:E4.7.13 (Tile/Slate - Guilt-in Gutters)"
Line 1: | Line 1: | ||
− | < | + | <div class="panel panel-success"> |
− | [[File:8.3.1.jpg]] | + | <div class="panel-heading"><big>'''Slate Roofing Details'''</big></div> |
− | + | <div class="panel-body"> | |
+ | <div class="col-md-6"> | ||
+ | <div style="text-align:center; vertical-align:center"> | ||
+ | [[File:8.3.1.jpg|class=img-responsive]] | ||
+ | </div> | ||
+ | </div><!-- COL-MD-6 --> | ||
+ | <div class="col-md-6"> | ||
=== WORK INCLUDED === | === WORK INCLUDED === | ||
Line 21: | Line 27: | ||
NOTE: <b>*</b> Refer to <i>RGC Guarantee Standards</i> for additional requirements. | NOTE: <b>*</b> Refer to <i>RGC Guarantee Standards</i> for additional requirements. | ||
+ | </div><!-- COL-6-MD --> | ||
+ | </div><!-- PANEL BODY --> | ||
+ | </div><!-- PANEL --> | ||
<hr> | <hr> | ||
− | |||
− | [[Tile and Slate Construction Details|<i class="fa fa-chevron-circle-left fa | + | [[Section:E. Application: Steep Slope Roofs|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Slate Application'']] |
+ | |||
+ | [[Tile and Slate Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Tile and Slate Construction Details'']] | ||
− | [[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa | + | [[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']] |
Revision as of 21:26, 19 August 2016
1 WORK INCLUDED
(1) MEMBRANES: Membranes must be installed to RGC Guarantee Standards and the manufacturer's printed instructions
(2) ADHESION: Membranes must be fully adhered, where exposed, and mechanically fastened at terminations 300 mm (12") o/c
(3) HEIGHT: The minimum vertical sealed height above the maximum water level is 150 mm (6"). The membrane run up the slope will vary with roof pitch. Increase height in heavy snow regions.
(4) EAVE PROTECTION: Built-in gutter membranes can be extended to act as an eave protection membrane. Underlay or eave protection membrane must overlap built-in gutter membrane by a minimum of 200 mm (8") and be installed in shingle fashion (not shown for clarity).
2 RELATED WORK BY OTHERS
(A) DIMENSIONS: Dimensions of parapets, cants and water loading of gutters are variable and should be determined by design authority
(B) ACCEPTABLE DECK
NOTE: * Refer to RGC Guarantee Standards for additional requirements.