Difference between revisions of "SBS Protected Roof Assembly (typical)"

Jump to: navigation, search

Difference between revisions of "SBS Protected Roof Assembly (typical)"

(WORK INCLUDED)
(RELATED WORK BY OTHERS)
Line 29: Line 29:
 
:Sloped to roof where parapet is over 100 mm (4") in width.
 
:Sloped to roof where parapet is over 100 mm (4") in width.
  
NOTE: Refer to <i>RGC Guarantee Standards</i> for additional requirements.
+
 
 +
'''NOTE''': Refer to <i>RGC Guarantee Standards</i> for additional requirements.
 +
 
 +
 
 
<hr>
 
<hr>
 +
  
  
Line 38: Line 42:
 
[[SBS Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''SBS Construction Details'']]
 
[[SBS Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''SBS Construction Details'']]
  
[[:Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''G. Construction Details'']]
+
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Construction Details'']]

Revision as of 20:10, 19 July 2016


D1.7.2.jpg


1 WORK INCLUDED

(1) Base Sheet
Adhered to deck using asphalt, cold adhesive, self-adhered, torch applied membrane or loose laid according to manufacturer’s specification and to RGC Guarantee Standards.
(2) Base Sheet Flashing
Adhered according to manufacturer’s specifications using cold adhesive, self-adhered or torch applied to cover boards, or mechanically attached membrane. Torching directly to wood surfaces is not permitted. Must be carried over to outside of parapet or minimum 200 mm (8") above finished roof surface. (See RGC Guarantee Standards Section 2.1.1, A5.6, and Section 2.1.3, C8.5).
(3) Cap Sheet
Applied according to manufacturer’s printed instructions and RGC Guarantee Standards.
(4) Cap Sheet Flashing
Applied according to manufacturer’s printed instructions and RGC Guarantee Standards to top of parapet or minimum 200 mm (8") above top of finished roof surface.
(5) Insulation
See list of accepted materials in Section 2.2.
(6) Filter Fabric
Metal base flashing required. (See RGC Guarantee Standard A6.9.1.2)
(7) Ballast
Gravel or concrete paving tiles. (See RGC Guarantee Standards Section 2.1.1, A5.2)
(8) Metal Flashing
As required by RGC Guarantee Standards. (See RGC Guarantee Standard A6.9 and A6.10)

2 RELATED WORK BY OTHERS

(A) Acceptable Deck
Smooth, dry and clean concrete, coated with proprietary primer.
(B) Plywood Backing
Required on rough concrete or where stripping adhesion is asphalt. Must be primed.
(C) Wood Blocking
Sloped to roof where parapet is over 100 mm (4") in width.


NOTE: Refer to RGC Guarantee Standards for additional requirements.





Back to SBS Application

Back to SBS Construction Details

Back to Construction Details