=== WORK INCLUDED === | === WORK INCLUDED === | ||
− | + | ;(1) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMUNDERLAYMENT|'''Underlayment''']]: The type of underlay required is determined by roof slope. | |
− | (1) | + | ;(2) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMSLIP|'''Slip Sheet''']]: Recommended over asphaltic underlays and / or as required by metal roof panel manufacturer. |
− | + | ;(3) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMVALLEYPAN |'''Valley Metal Panel''']]: Turn up (bread panned) at termination and drag load fastened with compatible non-corrosive fasteners. | |
− | (2) | + | ;(4) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMCLIP|'''Metal Panel Clip''']]: Installed to metal roof panel manufacturer's printed instructions. |
− | + | ;(5) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMZ |''''Z' Closure''']]: Set in accepted caulking and secured with compatible, non-corrosive, flat head fasteners. | |
− | (3) | + | ;(6) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMSHEETMETAL |'''Sheet Metal Flashing''']]: Hooked to 'Z' closure and fastened to wall with non-corrosive, flat head fasteners 300 mm (12") o/c or preformed foam closures set in acceptable caulking with high domed gasketed cladding type screws at each standing rib. |
− | + | ;(7) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMCOUNTER |'''Metal Counter Flashing''']]: Must extend behind siding and building paper. Stucco stops are not considered to be a counter flashing. | |
− | (4) | + | ;(8) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMJOINTOVER |'''Joint Overlap''']] |
− | + | : Joints overlapped 100 mm (4") minimum, sealed with two rows of accepted caulking. Exposed edges of joints must be turned under 12.7 mm (1/2"). | |
− | (5) | ||
− | |||
− | (6) | ||
− | |||
− | (7) | ||
− | |||
− | (8) | ||
=== RELATED WORK BY OTHERS === | === RELATED WORK BY OTHERS === | ||
+ | ;(A) [['''RoofStar Guarantee Standards for ASM Roof Systems#ASMDECK|'''Acceptable Deck''']] | ||
+ | ;(B) Wood Nailer''' | ||
+ | ;(C) '''Wall''' | ||
+ | ;(D) '''Siding''' | ||
+ | ;(E) '''Building Paper''' | ||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
− | |||
+ | '''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements. | ||
<hr> | <hr> | ||
Line 43: | Line 30: | ||
− | [[Section:E. Application: Steep Slope Roofs|<i class="fa fa-chevron-circle-left fa | + | [[Section:E. Application: Steep Slope Roofs|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''ASM Application'']] |
− | [[Architectural Sheet Metal Construction Details|<i class="fa fa-chevron-circle-left fa | + | [[Architectural Sheet Metal Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''ASM Construction Details'']] |
− | [[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa | + | [[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']] |
Revision as of 17:01, 10 August 2016
1 WORK INCLUDED
- (1) Underlayment
- The type of underlay required is determined by roof slope.
- (2) Slip Sheet
- Recommended over asphaltic underlays and / or as required by metal roof panel manufacturer.
- (3) Valley Metal Panel
- Turn up (bread panned) at termination and drag load fastened with compatible non-corrosive fasteners.
- (4) Metal Panel Clip
- Installed to metal roof panel manufacturer's printed instructions.
- (5) 'Z' Closure
- Set in accepted caulking and secured with compatible, non-corrosive, flat head fasteners.
- (6) Sheet Metal Flashing
- Hooked to 'Z' closure and fastened to wall with non-corrosive, flat head fasteners 300 mm (12") o/c or preformed foam closures set in acceptable caulking with high domed gasketed cladding type screws at each standing rib.
- (7) Metal Counter Flashing
- Must extend behind siding and building paper. Stucco stops are not considered to be a counter flashing.
- (8) Joint Overlap
- Joints overlapped 100 mm (4") minimum, sealed with two rows of accepted caulking. Exposed edges of joints must be turned under 12.7 mm (1/2").
2 RELATED WORK BY OTHERS
- (A) Acceptable Deck
- (B) Wood Nailer
- (C) Wall
- (D) Siding
- (E) Building Paper
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.