(A) <b>Acceptable Deck</b>
+
;(A) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSDECKS|'''Acceptable Deck''']]
 
+
;(B) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSVAPOUR|'''Air/Vapour Seal''']] Sealed to wall.
(B) <b>Air / Vapour Seal:</b> Sealed to wall.
+
;(C) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSWOODBLOCKING|'''Wood Blocking''']] : Height to provide minimum 200 mm (8") above completed roof system, slope top edge.
 
+
;(D) <b>Flexible Insulation</b>
(C) <b>Wood Blocking or Plywood:</b> Height to provide minimum 200 mm (8") above completed roof system, slope top edge. As per <i>RGC Guarantee Standard A1.5</i>
+
;(E) [[RoofStar Guarantee Standards for SBS Roof Systems#METALCAP-SBS|'''Reglet''']]:
 
+
;(F) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSSLOPEDWOODBLOCKING|'''Sloped Wood Blocking''']]:
(D) <b>Flexible Insulation</b>
 
 
 
(E) <b>Reglet</b>
 
 
 
(F) <b>Sloped Wood Blocking</b>
 
  
  

Revision as of 21:23, 2 August 2016

10.3.3.2.jpg

1 WORK INCLUDED

(1) Vapour Retarder
The requirement for a vapour retarder is determined by the design authority. Optional terminations.
(2) Insulation
(3) Insulation Overlay
Where required.
(4) Primary Membrane and Membrane Protection
(5) Membrane Flashing
Mechanically fasten to top of wood blocking.
(6) Membrane Counter-flashing
Flashing sealed to wall with compatible mastic.
(7) Metal Base Flashing
Mechanically fasten to top of wood blocking (C). Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
(8) Metal Counter-flashing
Into reglet approximately 30 mm (1¼") and caulked.
(9) Caulking
(10) Membrane Underlay
Minimum self-adhered modified bitumen membrane.
(11) Metal Cap Flashing
Must overlap exterior wall finish. Fasten with continuous concealed clip-type fasteners or cladding screws evenly spaced between seams.

2 RELATED WORK BY OTHERS

(A) Acceptable Deck
(B) Air/Vapour Seal Sealed to wall.
(C) Wood Blocking 
Height to provide minimum 200 mm (8") above completed roof system, slope top edge.
(D) Flexible Insulation
(E) Reglet
(F) Sloped Wood Blocking


NOTE: Refer to RGC Guarantee Standards for additional requirements.