Difference between revisions of "SBS Expansion Joint (Wall)"

Jump to: navigation, search

Difference between revisions of "SBS Expansion Joint (Wall)"

(RELATED WORK BY OTHERS)
(WORK INCLUDED)
Line 13: Line 13:
 
;(10) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSSTRIPTERM|'''Membrane Underlay''']]: Minimum self-adhered modified bitumen membrane.
 
;(10) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSSTRIPTERM|'''Membrane Underlay''']]: Minimum self-adhered modified bitumen membrane.
 
;(11) [[RoofStar Guarantee Standards for SBS Roof Systems#METALCAP-SBS|'''Metal Cap Flashing''']]: Must overlap exterior wall finish.  Fasten with continuous concealed clip-type fasteners or cladding screws evenly spaced between seams.
 
;(11) [[RoofStar Guarantee Standards for SBS Roof Systems#METALCAP-SBS|'''Metal Cap Flashing''']]: Must overlap exterior wall finish.  Fasten with continuous concealed clip-type fasteners or cladding screws evenly spaced between seams.
 +
 +
<hr>
  
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===

Revision as of 19:02, 4 August 2016

10.3.3.2.jpg

1 WORK INCLUDED

(1) Vapour Retarder
The requirement for a vapour retarder is determined by the design authority. Optional terminations.
(2) Insulation
(3) Insulation Overlay
Where required.
(4) Primary Membrane and Membrane Protection
(5) Membrane Flashing
Mechanically fasten to top of wood blocking.
(6) Membrane Counter-flashing
Flashing sealed to wall with compatible mastic.
(7) Metal Base Flashing
Mechanically fasten to top of wood blocking (C). Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
(8) Metal Counter-flashing
Into reglet approximately 30 mm (1¼") and caulked.
(9) Caulking
(10) Membrane Underlay
Minimum self-adhered modified bitumen membrane.
(11) Metal Cap Flashing
Must overlap exterior wall finish. Fasten with continuous concealed clip-type fasteners or cladding screws evenly spaced between seams.

2 RELATED WORK BY OTHERS

(A) Acceptable Deck
(B) Air/Vapour Seal Sealed to wall.
(C) Wood Blocking 
Height to provide minimum 200 mm (8") above completed roof system, slope top edge.
(D) Flexible Insulation
(E) Reglet
(F) Sloped Wood Blocking


NOTE: Refer to RGC Guarantee Standards for additional requirements.





Back to SBS Application

Back to SBS Construction Details

Back to Construction Details