Difference between revisions of "SBS Equipment Sleeper"

Jump to: navigation, search

Difference between revisions of "SBS Equipment Sleeper"

(RELATED WORK BY OTHERS)
Line 28: Line 28:
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
 
;(A) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSDECKS|'''Acceptable Supporting Deck Structure''']]
 
;(A) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSDECKS|'''Acceptable Supporting Deck Structure''']]
;(B) '''Air / Vapour Seal'''
+
;(B) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSAIRVAPOUR|'''Air and Vapour Control Layer Seal''']]
 
;(C) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSCURB|'''Wood Blocking/Sleeper''']]: Minimum 150 mm (6") thick, minimum 100 mm (4") above finished roof surface.
 
;(C) [[RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies#SBSCURB|'''Wood Blocking/Sleeper''']]: Minimum 150 mm (6") thick, minimum 100 mm (4") above finished roof surface.
 
</div><!-- COL-6-MD -->
 
</div><!-- COL-6-MD -->

Revision as of 19:48, 29 January 2019

RoofStar Guarantee Standards are blue-linked
SBS Details

10.3.5.2.jpg

1 WORK INCLUDED

(1) Supporting Deck Overlay
If required by design authority.
(2) Air or Vapour Control Layers
If required by design authority.
(3) Insulation
See available insulation products in the Accepted Materials section of this Manual.
(4) Insulation Overlay
As required.
(5) Primary Membrane and Membrane Protection
(6) Membrane Flashing
Lap one ply from each side over top of sleeper (C) and mechanically fasten.
(7) Alternate Cap Flashing
May be used instead of lapping membrane flashing over sleeper.
(8) Metal Base Flashing
Mechanically fasten to top of wood blocking, standing seam at corners, optional on flexible membrane systems. Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
(9) Metal Cap Flashing
NOTE: (8) and (9) may be one piece.

2 RELATED WORK BY OTHERS

(A) Acceptable Supporting Deck Structure
(B) Air and Vapour Control Layer Seal
(C) Wood Blocking/Sleeper
Minimum 150 mm (6") thick, minimum 100 mm (4") above finished roof surface.

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.




Back to RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies

Back to SBS Modified Bitumen Construction Details

Back to Construction Details