Difference between revisions of "LMF Metal Cap Flashing (inside corner)"

Jump to: navigation, search

Difference between revisions of "LMF Metal Cap Flashing (inside corner)"

(WORK INCLUDED)
(WORK INCLUDED)
Line 21: Line 21:
 
(4) <b>Metal Cap Flashing &#8211; Interior Face:</b> Fastened with continuous clips or cladding screws evenly spaced between seams. Over 100 mm (4") width requires standing seam. See [[RoofStar Guarantee Standards for SBS Roof Systems#SBSMETALBASE|'''SBS Roof Systems - 12.6 Cap Flashings, Base Flashings and Reglets''']] for requirements.
 
(4) <b>Metal Cap Flashing &#8211; Interior Face:</b> Fastened with continuous clips or cladding screws evenly spaced between seams. Over 100 mm (4") width requires standing seam. See [[RoofStar Guarantee Standards for SBS Roof Systems#SBSMETALBASE|'''SBS Roof Systems - 12.6 Cap Flashings, Base Flashings and Reglets''']] for requirements.
  
(5) <b>Seam:</b> Lap seam in a corner is acceptable if vertical distance is not more than 100 mm (4"). Again see [[RoofStar Guarantee Standards for SBS Roof Systems#SBSMETALSEAM|'''SBS Roof Systems - 12.5 Seams''']].
+
(5) <b>Seam:</b> Lap seam at an inside corner is acceptable if vertical distance is not more than 100 mm (4"). Again see [[RoofStar Guarantee Standards for SBS Roof Systems#SBSMETALSEAM|'''SBS Roof Systems - 12.5 Seams''']].
  
 
(6) <b>Metal Cap Flashing &#8211; Top Face:</b> Over 100 mm (4") width must provide positive slope to roof area.
 
(6) <b>Metal Cap Flashing &#8211; Top Face:</b> Over 100 mm (4") width must provide positive slope to roof area.

Revision as of 15:42, 20 November 2019

RoofStar Guarantee Standards are blue-linked
Metal Flashing Details

10.2.1.1.jpg

1 WORK INCLUDED

(1) Metal Cant Flashing: Standing seam required at corners of cant. See SBS Roof Systems - 12.5 Seams.

(2) Metal Base Flashing: Vertical runs over 100 mm (4") require standing seam or S-lock corners. See SBS Roof Systems - 12.6 Cap Flashings, Base Flashings and Reglets. Cross-breaks and cladding-type fasteners are optional.

(3) Double S-Lock Corner: Fastened through concealed flanges to top of parapet. Again, see SBS Roof Systems - 12.5 Seams.

(4) Metal Cap Flashing – Interior Face: Fastened with continuous clips or cladding screws evenly spaced between seams. Over 100 mm (4") width requires standing seam. See SBS Roof Systems - 12.6 Cap Flashings, Base Flashings and Reglets for requirements.

(5) Seam: Lap seam at an inside corner is acceptable if vertical distance is not more than 100 mm (4"). Again see SBS Roof Systems - 12.5 Seams.

(6) Metal Cap Flashing – Top Face: Over 100 mm (4") width must provide positive slope to roof area.

(7) Standing Seam

(8) Metal Cap Flashing – Outside Face: Corner standing seams may be folded flat on outside face only. Fasten with continuous concealed clip-type fasteners or cladding screws evenly spaced between seams.

2 RELATED WORK BY OTHERS

(A) Acceptable Parapet

(B) Sloped Blocking: Required over minimum 100 mm (4") parapet width. See SBS Roof Systems - 12. Perimeter Flashing: Metal

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.



Back to Metal Flashing Details

Back to Construction Details