<div class="principles">A roof system underlay is installed under the roof system and over the roof deck assembly. Underlays are most commonly placed over steel decks to provide a level surface for the membrane, or as a thermal barrier between the roof deck and combustible insulations.</div>
 
<div class="principles">A roof system underlay is installed under the roof system and over the roof deck assembly. Underlays are most commonly placed over steel decks to provide a level surface for the membrane, or as a thermal barrier between the roof deck and combustible insulations.</div>
 +
  
 
RGC requires either minimum 12.7 mm (1/2") gypsum with fibreglass facers and a silicone treated gypsum core (See Section 2.1, A2.5) or minimum 12.7 mm (1/2") plywood as an underlay for membranes installed directly over steel decks. Where an underlay is used as a thermal barrier, it must conform to the applicable code and insurance requirements for the roof assembly.
 
RGC requires either minimum 12.7 mm (1/2") gypsum with fibreglass facers and a silicone treated gypsum core (See Section 2.1, A2.5) or minimum 12.7 mm (1/2") plywood as an underlay for membranes installed directly over steel decks. Where an underlay is used as a thermal barrier, it must conform to the applicable code and insurance requirements for the roof assembly.

Revision as of 21:27, 11 January 2016

1 General

NOTE: Refer to subsection 3 (SUBSTRATES - DECK OVERLAY BOARD and WALL SHEATHING) of the RoofStar Guarantee Standards for either Low Slope Roof Systems or for Architectural Sheet Metal Roof Systems.

A roof system underlay is installed under the roof system and over the roof deck assembly. Underlays are most commonly placed over steel decks to provide a level surface for the membrane, or as a thermal barrier between the roof deck and combustible insulations.


RGC requires either minimum 12.7 mm (1/2") gypsum with fibreglass facers and a silicone treated gypsum core (See Section 2.1, A2.5) or minimum 12.7 mm (1/2") plywood as an underlay for membranes installed directly over steel decks. Where an underlay is used as a thermal barrier, it must conform to the applicable code and insurance requirements for the roof assembly.

2 Underlays for Metal Roofing

Acceptable membrane underlays for metal roofing are listed in Section 8.2 and in Section 2.2 (accepted Materials list) of this manual.


Back to Essential Elements

Vapour Retarders