=== WORK INCLUDED === | === WORK INCLUDED === | ||
;(1) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSVAPOUR|'''Vapour Retarder''']]: The requirement for a vapour retarder is determined by the design authority. Optional terminations. | ;(1) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSVAPOUR|'''Vapour Retarder''']]: The requirement for a vapour retarder is determined by the design authority. Optional terminations. | ||
Line 23: | Line 31: | ||
;(E) [[RoofStar Guarantee Standards for SBS Roof Systems#METALCAP-SBS|'''Reglet''']]: | ;(E) [[RoofStar Guarantee Standards for SBS Roof Systems#METALCAP-SBS|'''Reglet''']]: | ||
;(F) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSSLOPEDWOODBLOCKING|'''Sloped Wood Blocking''']]: | ;(F) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSSLOPEDWOODBLOCKING|'''Sloped Wood Blocking''']]: | ||
− | + | </div><!-- COL-6-MD --> | |
+ | </div><!-- PANEL BODY --> | ||
+ | </div><!-- PANEL --> | ||
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements. | '''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements. |
Revision as of 17:53, 19 August 2016
SBS Details
1 WORK INCLUDED
- (1) Vapour Retarder
- The requirement for a vapour retarder is determined by the design authority. Optional terminations.
- (2) Insulation
- (3) Insulation Overlay
- Where required.
- (4) Primary Membrane and Membrane Protection
- (5) Membrane Flashing
- Mechanically fasten to top of wood blocking.
- (6) Membrane Counter-flashing
- Flashing sealed to wall with compatible mastic.
- (7) Metal Base Flashing
- Mechanically fasten to top of wood blocking (C). Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
- (8) Metal Counter-flashing
- Into reglet approximately 30 mm (1¼") and caulked.
- (9) Caulking
- (10) Membrane Underlay
- Minimum self-adhered modified bitumen membrane.
- (11) Metal Cap Flashing
- Must overlap exterior wall finish. Fasten with continuous concealed clip-type fasteners or cladding screws evenly spaced between seams.
2 RELATED WORK BY OTHERS
- (A) Acceptable Deck
- (B) Air/Vapour Seal
- Sealed to wall.
- (C) Wood Blocking
- Height to provide minimum 200 mm (8") above completed roof system, slope top edge.
- (D) Flexible Insulation
- (E) Reglet
- (F) Sloped Wood Blocking
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.