Template:All Systems - INSULATION OVERLAY BOARD
Template:All Systems - INSULATION OVERLAY BOARD
1 General
RGC accepted insulation overlay boards shall be installed over all plastic foam insulations (EPS, XEPS, Polyisocyanurate) on all adhered low slope roofing systems. When heat sensitive insulations (EPS,XEPS) are used with heat welded membrane seams an accepted overlay board must be installed. Fibreboard shall not be used with flame welded seams.
2 Layering
Insulation and overlay board joints are to be offset/staggered 300 mm (12") from adjacent layers and rows. The uppermost layer of [insulation or] overlay board directly below membranes shall have joints that are offset/staggered from adjacent layers and rows.
3 Mechanical Fastening
Possible Wording: Refer to C5.c in this Manual for RoofStar Guarantee requirements for the application of mechanical fasteners, as they pertain to both insulation and overlay board applications.
4 Using Adhesives
When asphaltic membranes are adhered (using hot asphalt, cold adhesives, or when applied with a torch), at least one layer of overlay board is required over all types of insulation. In addition, the following standards, principles and information apply:
Heat Sensitive Insulation: On all heat sensitive insulation (polystyrene, extruded, and expanded), an overlay consisting of two layers of acceptable cover board is to be used when using hot asphalt as an adhesive, or where the cover board is less than 1/2" in thickness on torch applied assemblies.
- A. Two layer system: Back mop and flop first layer of overlay board (for hot asphalt adhered systems), or use manufacturers accepted proprietary adhesives per published directions, offsetting the joints from those of the insulation. Then tape joints and install second layer offsetting the joints from those of the insulation. Then tape joints and install second layer offsetting the joints from those of the layer below. Alternatively, the membrane manufacturer's proprietary insulation adhesives may be used to adhere accepted cover boards and insulation.
- B. Single layer system: Flame protection over the cover board is required. Install the insulation and cover board with the proprietary accepted adhesive. Seal over all cover board joints and wall transitions with the membrane manufacturer's proprietary self-adhered membrane tape.
Asphalt core overlay boards, [minimum thickness 4.5 mm (3/16") nominal] or insulation and insulation overlay boards specifically designed for torch applications, that are accepted by RGC, mechanically attached with nails with a minimum 25 mm (1") nominal head size placed a minimum of one nail per 0.093 m² (1 sq. ft.) or plates and screws placed a minimum of 0.186 m² (2 sq. ft.). Seal all board joints and wall transitions with membrane manufacturer’s approved self-adhered membrane or tapes.
5 Joint Taping
Acceptable materials for taping joints, of hot asphalt, and cold adhesive applied roof assemblies on overlay board, insulation, gypsum board, and primed plywood are minimum 150 mm (6") wide No.15 felt, 150 mm (6") wide Fibreglass roof tape, or 150 mm (6") wide sheathing (membrane breather-type to CAN / CGSB 51.32-M77). The only acceptable methods of hot asphalt installation are by back coating with asphalt, or laying with a back-coating machine expressly intended for the purpose.