SBS Expansion Joint (Wall)
SBS Expansion Joint (Wall)
Revision as of 17:06, 27 August 2021 by James Klassen (talk | contribs)
RoofStar Guarantee Standards are blue-linked |
SBS Details
1 WORK INCLUDED
- (1) Air or Vapour Control Layers
- The requirement for a vapour retarder is determined by the design authority. Optional terminations.
- (2) Insulation
- (3) Insulation Overlay
- Where required.
- (4) Primary Membrane and Membrane Protection
- (5) Membrane Flashing
- Mechanically fasten to top of wood blocking.
- (6) Membrane Counter-flashing
- Flashing sealed to wall with compatible mastic.
- (7) Metal Base Flashing
- Mechanically fasten to top of wood blocking (C). Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
- (8) Metal Counter-flashing
- Into reglet approximately 30 mm (1¼") and caulked.
- (9) Caulking
- (10) Membrane Underlay
- Minimum self-adhered modified bitumen membrane.
- (11) Metal Cap Flashing
- Must overlap exterior wall finish. Fasten with continuous concealed clip-type fasteners or cladding screws evenly spaced between seams.
2 RELATED WORK BY OTHERS
- (A) Acceptable Supporting Deck Structure
- (B) Air and Vapour Control Layer Seal
- Sealed to wall.
- (C) Wood Blocking
- Height to provide minimum 200 mm (8") above completed roof system, slope top edge.
- (D) Flexible Insulation
- (E) Reglet
- (F) Sloped Wood Blocking
NOTE: See the Standard for additional requirements.
Back to RoofStar Guarantee Standards for SBS Modified Bitumen Roof Assemblies
Back to SBS Modified Bitumen Construction Details
© RCABC 2024
RoofStarTM is a registered Trademark of the RCABC.
No reproduction of this material, in whole or in part, is lawful without the expressed permission of the RCABC Guarantee Corp.