Accepted Materials - ASM Roof Systems
Accepted Materials - ASM Roof Systems
Contents
- 1 Standing Seam Metal Roof System - Job Site Roll-forming
- 1.1 Admiral Roofing Ltd.
- 1.2 Parker Johnston Industries Ltd.
- 1.3 Laing Roofing Ltd.
- 1.4 Interior Roofing (2011) Ltd.
- 1.5 Nelson Roofing & Sheet Metal Ltd.
- 1.6 D.M. Henderson Roofing Ltd.
- 1.7 Top Line Roofing Ltd.
- 1.8 Tomtar Roofing and Sheet Metal Ltd.
- 1.9 Western Roofing (Master Roofers) Ltd.
- 1.10 Flynn Canada Ltd.
- 1.11 Kelowna Roofing (1984) Ltd.
- 1.12 Mainline Roofing Co. Ltd.
- 1.13 Lam Metal Contracting Ltd.
- 1.14 Universal Sheet Metal Ltd.
- 1.15 Standard Roofing Corporation
- 1.16 B.F. Roofing Ltd.
- 1.17 Eby & Son Construction Ltd.
- 1.18 Homan Roofing Ltd.
- 1.19 Crown Roofing & Drainage Ltd.
- 1.20 Marine Roofing (1996) Ltd.
- 1.21 Pocklington Building Systems Ltd.
- 1.22 Cascade Roofing & Waterproofing (2007) Inc.
- 1.23 Aurora Roofing Ltd.
- 1.24 Villa Roofing & Sheet Metal Ltd.
- 1.25 Raven Roofing Ltd.
- 1.26 Transwest Roofing Ltd.
- 1.27 Alpha Roofing & Sheet Metal Inc.
1 Standing Seam Metal Roof System - Job Site Roll-forming
RCABC Guarantee Corp. RGC accepted standing seam metal roof systems, installed in conformance with RGC Guarantee Standards, qualify for a five (5) or ten (10) year guarantee under the RoofStar Guarantee Program.
Refer to member listing below for additional accepted roof system installation information.
Accepted Systems:
1.1 Admiral Roofing Ltd.
- AR5150 Snap Lock Panel - Standing Seam Metal Roof System
- AR5150 Nail Strip Panel - Standing Seam Metal Roof System
- AR9150 Standing Seam Metal Roof System
1.2 Parker Johnston Industries Ltd.
Parker Johnston Industries Ltd.
- Knudson P-2401 - Standing Seam Metal Roof System
- 30 / 80 LM Schlebach 1" - Standing Seam Metal Roof System
- Schlebach Quadro 1-1/2" Mechanical
1.3 Laing Roofing Ltd.
- Quadro Snap Seam - SS150 Panel - Standing Seam Metal Roof System
1.4 Interior Roofing (2011) Ltd.
- Roll Former Series 1000 – Snap Lock Standing Seam Metal Roof System
1.5 Nelson Roofing & Sheet Metal Ltd.
- Knudson Varipan - Snap-Lock Nail - Snap Lock Seam Metal Roof System
- Knudson Varipan - Standing Seam - Standing Seam Metal Roof System
- Quadro Snap Seam - SS 150 + 1-1/2"- Snap-Lock Metal Roof System
- Quadro 1” & 1.5” Mechanical Lock - Standing Seam Metal Roof System
- Mechanical Lock - SS 150 and SS 100 Panel - Standing Seam Metal Roof System
- Seam Lock - SS100 Panel - Standing Seam Metal Roof System
- Seam Lock - SS150 Panel - Standing Seam Metal Roof System
1.6 D.M. Henderson Roofing Ltd.
- Zimmerman SS1500 - Standing Seam Metal Roof System
1.7 Top Line Roofing Ltd.
- Schlebach Quadro Standing Seam Metal Roof System
1.8 Tomtar Roofing and Sheet Metal Ltd.
- Knudson KR-12 - Standing Seam Metal Roof System
- Knudson P-2401 - Standing Seam Metal Roof System
1.9 Western Roofing (Master Roofers) Ltd.
- ESE 150 - Standing Seam Metal Roof System
1.10 Flynn Canada Ltd.
- Knudson KR-12 - Standing Seam Metal Roof System
- Knudson KR-24 - Standing Seam Metal Roof System
- Knudson P-2406 - Standing Seam Metal Roof System
- Snap Lock II 675 Panel – Snap Lock Seam Metal Roof System
- Seam Lock SS150 – Standing Seam Metal Roof System
- Seam Lock SS100 - Standing Seam Metal Roof System
1.11 Kelowna Roofing (1984) Ltd.
- Knudson P-2401 - Standing Seam Metal Roof System
1.12 Mainline Roofing Co. Ltd.
- ESE 150 - Standing Seam Metal Roof System
1.13 Lam Metal Contracting Ltd.
- Job Site – Snap Loc 1" - Snap Lock Seam Metal Roof System
- Nu-Tech - Snap-Loc - Snap Lock Seam Metal Roof System
- Schlebach 1" Seam - Standing Seam Metal Roof System
- Lam Metal Berridge T-Panel, Compound, Curved & Tapered Tee-Panel
- ESE 100 Standing Seam Panel - Standing Seam Metal Roof System
- 1" Super Snap-Loc, Concealed Fastener System
1.14 Universal Sheet Metal Ltd.
- Knudson KR-12
1.15 Standard Roofing Corporation
- Knudson P-2401
1.16 B.F. Roofing Ltd.
- Roll Former VS-150 - Standing Seam Metal Roof System
1.17 Eby & Son Construction Ltd.
- Zimmerman SS 1500 - Standing Seam Panel
1.18 Homan Roofing Ltd.
- Seam Lock - SS150 Panel and SS100 Panel Standing Seam Metal Roof System
1.19 Crown Roofing & Drainage Ltd.
- Crown 1" & 1-1/2" Standing Seam Panel
1.20 Marine Roofing (1996) Ltd.
- Snap-Lock Nu-Tech - Standing Seam Metal Roof System
- MR-100 - Standing Seam Metal Roof System
- MR/S-100 - Standing Seam Metal Roof System
- MR/S-150 - Standing Seam Metal Roof System
- MR-675 - Standing Seam Metal Roof System
1.21 Pocklington Building Systems Ltd.
- SS100 Panel & SS150 Panel – Standing Seam Metal Roof System
- Snap Lock FF150 Panel - Snap Lock Seam Metal Roof System
1.22 Cascade Roofing & Waterproofing (2007) Inc.
- Zimmerman SS150 - Standing Seam Metal Roof System
- Snap-Loc Nu-Tech - Standing Seam Metal Roof System
1.23 Aurora Roofing Ltd.
- Knudson KR 12 - Standing Seam Metal Roof System
1.24 Villa Roofing & Sheet Metal Ltd.
- VillaLoc II 675 Panel
- Villa Seam - SS150 and SS10 panels
- Villa Snap-Loc 1" FF - Standing Seam Metal Roof System
1.25 Raven Roofing Ltd.
- Standing Seam Metal Roof System - Snap Lock 675 Panel
- SS150 Panel and SS100 Panel
- Quadro Snap Seam-FFQ 100 Panel
1.26 Transwest Roofing Ltd.
- Seam Lock - SS100 Panel - Standing Seam Metal Roof System
- Snap Lock II 675 Panel - Standing Seam Metal Roof System
- FF100 Panel - Seam Metal Roof System
1.27 Alpha Roofing & Sheet Metal Inc.
- Schlebach Quadro - Standing Seam Metal Roof System
Manufacturer: ADMIRAL ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM - AR5150 SNAP LOCK PANEL
- DESCRIPTION
The AR5150 Snap Lock panel is formed with an on-site / in-shop continuous metal roofing panel roll forming machine (Schlebach Quadro+). This machine produces a Snap-lock panel with a seam height of 38 mm (1-1/2") and profiles can vary from 200 mm (8") wide up to 500 mm (20") wide. This machine also produces a Nail-strip panel and a mechanically seamed panel.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 The AR5150 SL panel is a snap-lock concealed fastener roofing panel. The panel is attached with a hidden roof deck panel clip fastened to the acceptable substrate. The overlying panel (female rib) locks together with the underlying panel’s intergraded clip (male) and roof deck panel clips. The maximum spacing of the clips is 600 mm (24") on centre.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws) - Fasteners used to attach panels to plywood to be No. 10-12 by 25 mm (1") long pancake head wood screws. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips) - One piece assembly 57.15 mm (2-1/4") wide, 38 mm (1-1/2") high, minimum thickness 0.036" (No. 20 MSG). Clips spaced maximum 600 mm (24") on centre, fastened to the roof deck.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: ADMIRAL ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM - AR5150 NAIL STRIP PANEL
- DESCRIPTION
The AR5 150 Nail Strip panel is formed with an on-site / in-shop continuous metal roofing panel roll forming machine (Schlebach Quadro+). This machine produces a Nail-strip panel with a seam height of 38 mm (1½") and profiles can vary from 200 mm (8") wide up to 637.5 mm (25½") wide . This machine also produces a Snap-lock panel and a mechanically seamed panel.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual does NOT represent a complete set of the manufacturer’s published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 The AR5150 NS panel is a snap-lock concealed fastener roofing panel. The panel is fastened to the acceptable substrate along the integrated fastening strip along the entire length of the panel. The overlying panel (female rib) locks together with the underlying panel’s integrated clip (male), along the entire length of the panel. The maximum spacing of the fasteners is 600 mm (24") on centre.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws) - Fasteners used to attach panels to plywood to be No. 10-12 by 25 mm (1") long pancake head wood screws.
- 1.3 SITE CONDITIONS
.1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
Manufacturer: ADMIRAL ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM - AR9150
- DESCRIPTION
- The AR9150 standing seam panel is formed with an on-site/in-shop continuous metal roofing panel roll forming machine (Schlebach Quadro+). This machine produces a standing seam panel with a seam height of 38 mm (1½") and profiles can vary from 200 mm (8") wide up to 652.5 mm (26½") wide. This machine also produces a Nail-strip panel and a Snap-lock panel.
- On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RGC Roofing Practices Manual does NOT represent a complete set of the manufacturer’s published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 The AR9150 panel is a standing seam concealed fastener roofing panel. The panel is attached with a hidden roof deck panel clip fastened to the acceptable substrate. The panels are seamed together with a mechanical seamer. The maximum spacing of the clips is 600 mm (24") on centre.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panels to plywood to be No. 10-12 by 25 mm (1") long pancake head wood screws. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
-
- Two piece assembly consisting of steel base approx 25 mm (1") wide x 150 mm (6") long, minimum thickness of 0.036" (No. 20 MSG) and an upper tab, 41 mm (15/8") high, minimum thickness of 0.020" (No. 26 MSG). One panel clip spaced at 600 mm (24") on centre maximum.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
Manufacturer: PARKER, JOHNSTON LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – Knudson P-2401
- DESCRIPTION
The Knudson P-2401 is an on-site continuous metal roll forming machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 38 mm (1.5").
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities.
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Architectural standing seam panels employ a hidden fastening system for securing to a solid substrate. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- For panel clip to steel connections use No. 10 by 25 mm (1") long self-drilling, self-tapping hex washer–head plated steel screws used without sealing washers. Two fasteners per panel clip to be used inserted through guide holes OR No. 10-16 Phillips pancake head screws may be used. Length to be 25 mm (1"). Three fasteners per clip to be used for pancake head type, inserted through guide holes.
- Roof Deck Fastener (Panel Clip)
- Two part assembly consisting of a coated steel base, No. 20 MSG min thick and a coated steel tab No. 24 MSG thick, overall height min 40.9 mm (1-5/8"), max 62.5 mm (2-1/2"), base width 150 mm (6") tab width 300 mm (12") located at sides of panel over attachment point. Fastened 600 mm (24") on centre.
- Knudson Manufacturing Inc – “I.M.C. 2401 Sliding Strip Clip.” OR
- One part panel clip assembly, No. 22 MSG min thick. Overall height – min 40.9 mm (1-5/8"), max 62.5 mm (2-1/2") clip width 300 mm (12".)
- Knudson Manufacturing Inc. – “I.M.C. 2401 Fixed Strip Clip.”
- Fastened 600 mm (24") on centre.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: PARKER, JOHNSTON LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – 30 / 80 LM SCHLEBACH 1"
- DESCRIPTION
The Schlebach 1" Standing Seam metal roofing is a shop formed and an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") (standard width is 13", 15" or 20") with a seam height of 1". It can be rolled square, tapered and curved. It comes with no stiffening rib, with stiffening ribs and striation.
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal-sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
-
- Fasteners (Screws)
- For panel clip to steel attachment to be No. 12-16 by 22 mm (1") long self-drilling, self-tapping, hex-washer head plated steel screws used without sealing washers. Two fasteners per panel clip used, inserted into panel clip guide holes.
- Roof Deck Fasteners (Panel Clips)
- Two piece assembly consisting of a No. 18 or No. 16 MSG min thick coated steel base approximately 22 mm (1") wide x 125 mm (5") long and No. 24 MSG min thick steel upper tap section height 22 mm (1") as manufactured by metal Roofing Supply Inc. in Denver or equivalent shop formed clip by Parker Johnston Industries Ltd. As per RoofStar Guarantee standard D6.1. One panel clip spaced at 600 mm (24") on centre.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge
(0.024") or greater and minimum coating designation AZ150.
Manufacturer: PARKER, JOHNSTON LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM SCHLEBACH QUADRO STANDING SEAM SYSTEM
- DESCRIPTION
The Schlebach Quadro Panel Machine is an on-site / in-shop continuous metal roofing and soffit panel roll forming machine. This machine produces 25 mm (1") and 38 mm (1.5") seam heights in Snap lock, Nail strip and 25 mm (1") and 38 mm (1.5") and 50 mm (2") seam heights in Mechanical Lock profiles. Panels can be produced in widths from 225 mm (9") wide to 500 mm (20") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels utilize a hidden fastener clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips in either the snap lock or mechanically locked system is 600 mm OC (24"). The panels are locked together with the clips as part of the seam, by use of friction in the case of the Snap lock profiles, or by use of a mechanical seamer in the case of the mechanically locked profiles.
- .2 Range of application: on wood or metal-sloped roofs; in commercial, institutional, industrial and residential construction. This product is acceptable for re-roofing or new construction applications.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel nail strip or clips to plywood to be No. 10 by min. 25 mm (1") pancake head, No. 2 Phillips drive, A-Point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 (1-3/4") wide, heights to suit seam height as per manufacturer’s requirements. Minimum clip thickness 0.022" (No. 22 MSG). Clips spaced maximum 600 mm (24") on centre fastened to plywood or steel deck. Minimum of two fasteners used Schlebach / Quadro Fixed Clip.
- Two piece assembly to be used for longer panel lengths, clip to be Schlebach approved 22 ga. 87.5 mm (3-1/2") wide by appropriate height to suit seam height chosen. One panel clip spaced a min. of maximum of 600 mm (24") OC.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Contact manufacturer for installation practise in extreme weather areas.
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: LAING ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – QUADRO Snap Seam
- DESCRIPTION
Quadro Panel Machine is an on-site/in-shop continuous metal roofing panel roll forming machine. This machine produces Snap Seam – SS 150 with a seam height of 38 mm (1-1/2"). This machine can produce either a Nail Strip System or a Clip system. Panels can be produced for 225 mm (9") to 500 mm (20") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel nail strip or clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022". (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Quadro 150 Clip.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
-
- .1 Wind Uplift Standards
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: INTERIOR ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – SERIES 1000 INTERLOCKING PANEL
- DESCRIPTION
The Series 1000 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 37.5 mm (1-1/2").
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. Maximum clip spacing is 450 mm (18") o/c. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1 ".) long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in. (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert “Series 1000 Interlocking Clip”.
- .4 Plywood Decking
- The plywood is to be a nominal 15.9 mm (5/8") (19/32") thick, square edged.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
-
- .1 Wind Uplift Standards
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: NELSON ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – KNUDSON VARIPAN
- DESCRIPTION
The Knudson Varipan is an on-site continuous metal roll forming machine. It produces 2 panel profiles, a 1" nail strip snap lock panel and a 1.5" standing seam panel. Panel widths vary from 12" - 20". Panels may be formed with between 1-3 stiffening beads and between 1-3 striations depending on panel width.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities.
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION – STANDING SEAM
- .1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- For panel clip to steel attachment to be No. 10-16 by 22 mm (1") long self- drilling, self-tapping, pancake head plated steel screws. Two fasteners per panel clip used, inserted into panel clip guide holes. For panel clip to wood attachment to be No. 10-16 by 22 mm (1") long self-tapping, pancake head plated steel screws. Two fasteners per panel clip used, inserted into panel clip guide holes.
- Roof Deck Fastener (Panel clip)
- One piece assembly, 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high by Knudson manufacturing or approved equal. Minimum thickness 0.022" (No. 22 MSG). One panel clip spaced at 600 mm (24") on centre.
- Two piece assembly, to be used for longer panel lengths, 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high by Knudson manufacturing or approved equal. Minimum thickness 0.022" (No. 22 MSG). One panel clip spaced at 600 mm (24") on centre.
- 1.3 SYSTEM DESCRIPTION – SNAP-LOCK NAIL
- .1 Snap-lock panels employ a hidden fastening system for securement to a solid substrate. Panels are attached with screws fastened through slots cut in the male leg [flange] and then the subsequent panels female leg locks over the entire length of the panel eliminating the need for clips.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
-
- For panel to steel attachment to be No. 10-16 by 22 mm (1") long self- drilling, self-tapping, pancake head plated steel screws. One fastener every 24" on centre inserted into panel guide holes.
- For panel to wood attachment to be No. 10-16 by 22 mm (1") long self-tapping, pancake head plated steel screws. One fastener every 24" on centre inserted into panel guide holes.
- 1.4 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.5 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: NELSON ROOFING & SHEET METAL LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – QUADRO Snap Seam - SS150 Panel
- DESCRIPTION
Quadro Panel Machine is an on-site/in-shop continuous metal roofing panel roll forming machine. This machine produces Snap Seam – SS 150 with a seam height of 38 mm (1-1/2").
This machine can produce either a Nail Strip System or a Clip system. Panels can be produced for 225 mm (9") to 500 mm (20") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022". (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Quadro 150 Clip.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: NELSON ROOFING & SHEET METAL LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – QUADRO 1’ 7 1.5" MECHANICAL LOCK
- DESCRIPTION
The Quadro 1’ & 1.5" mechanical lock is an on-site continuous panel metal roofing machine. Panel profiles vary from 225 mm (9") to 500 mm (20") wide with a standing seam height of 38 mm (1-1/2"). This on-site manufacturing eliminates the need for end laps, with continuous panel forming capabilities in lengths up to 46 m (150').
- 1.1 GENERAL
The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 The range of application for this panel: on sloped wood or metal roof decks; in residential, commercial, and industrial applications; for new or re-roof.
- .3 Panel Attachment:
- Panel Clips - one piece clip 64 mm (2") wide by 38 mm (1.5") high with a 16 mm (3/4") base. The minimum thickness is 22 gauge metal; fastened to a plywood deck 600 mm (24") on centre. Manufactured by Architectural Metal Specialties Inc. Clips for longer length panels to be two piece assemblies, for thermal expansion and contraction. Two piece clip dimensions – 127mm (5”) wide by 38mm 91.5”) high with a 16mm (3/4”) base including a slot for 1 ¼” thermal movement.
- Fasteners - used to attach clips to plywood to be #8 x 1" long, pancake head, A-point, coated steel screw. Minimum two screws per clip. For steel decking or Z-girts the same size of screw with a pancake head, having a self-drill and tap point, and again two screws per clip.
- .4 Plywood decking is to be a nominal 13 mm (1/2") thick or thicker.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: NELSON ROOFING & SHEET METAL LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – SS 150 PANEL and SS 100 PANEL MECHANICAL LOCK
- DESCRIPTION
The New Tech Machinery Panel Machine is an on-site continuous metal roofing panel roll forming machine. This machine produces Seam Lock - SS 150 with a seam height of 38 mm (1-1/2") and Seam Lock - SS 100 with a seam height of 22 mm (1"). Both panel profiles vary from 300 mm (12") to 500 mm (20") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46m (150').
- 1.1 GENERAL
The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 The range of application for this panel: on sloped wood or metal roof decks; in residential, commercial, and industrial applications; for new or re-roof.
- .3 Panel Attachment:
- Panel Clips - one piece clip 64 mm (2") wide by 38 mm (1.5") high with a 16 mm (3/4") base. The minimum thickness is 22 gauge metal; fastened to a plywood deck 600 mm (24") on centre. Manufactured by Architectural Metal Specialities Inc.
- Fasteners - used to attach clips to plywood to be #8 x 1" long, pancake head, A-point, coated steel screw. Minimum two screws per clip. For steel decking or Z-girts the same size of screw with a pancake head, having a self-drill and tap point, and again two screws per clip.
- .4 Plywood decking is to be a nominal 13 mm (1/2") thick or thicker.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:2.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: NELSON ROOFING & SHEET METAL LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – SEAM LOCK – SS150 PANEL AND SS100 PANEL
- DESCRIPTION
- The New Tech Machinery Panel Machine is an on-site continuous metal roofing panel roll forming machine. This machine produces Seam Lock – SS 150 with a seam height of 38 mm (1-1/2") and Seam Lock – SS 100 with a seam height of 22 mm (1"). Both panel profiles vary from 300 mm (12") to 500 mm (20") wide.
- On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in. (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert “Series 1000 Interlocking Clip”.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: D.M. HENDERSON ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – ZIMMERMAN SS1500 STANDING SEAM PANEL
- DESCRIPTION
- The Zimmerman SS1500 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a standing seam height of 38 mm (1 1/2").
- This on-site manufacturing eliminates the need for end laps, with continuous panel forming capabilities in lengths up to 46 m (150'). Panel clips for longer length panels to be two piece assemblies, for thermal expansion and contraction design allowances, using 20 gauge metal conforming to 150-ST-22G and 500-SB-22-g base by AMSI or Approved equivalent.
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 The range of application for this panel: on sloped wood or metal roof decks; in residential, commercial, and industrial applications; for new or reroof.
- .3 Panel Attachment:
- Panel Clips – one piece clip 64 mm (2 ½") wide by 38 mm (1 ½") high with a 16 mm (5/8") base. The minimum thickness is 22 gauge metal; fastened to a plywood deck 600 mm (24") on centre. Custom-Bilt 2SS RC1.5" standing seam roof clip.
- Fasteners - used to attach clips to plywood to be #8 x 1" long, pancake head, A-point, coated steel screw. Minimum two screws per clip. For steel decking or Z-girts the same size of screw with a pancake head, having a self-drill and tap point, and again two screws per clip.
- .4 Plywood decking is to be a nominal 13 mm (1/2") thick or thicker.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
-
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: TOP LINE ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – SCHLEBACH QUADRO STANDING SEAM SYSTEM
- DESCRIPTION
The Schlebach Quadro Panel Machine is an on-site/in-shop continuous metal roofing and soffit panel roll forming machine. This machine produces 25 mm (1") and 38 mm (1.5") seam heights in Snap Lock, Nail strip and 25 mm (1") and 38 mm (1.5") and 50 mm (2") seam heights in Mechanical Lock profiles. Panels can be produced in widths from 225 mm (9") to 500 mm (20") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to 46 m (150'). Panel curving is available in 1" - 1½" standing seam using a Schlebach panel-curving machine.
- 1.1 GENERAL
The roof assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer’s published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels utilize a hidden fastener clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips in either the snap lock or mechanically locked system is 600 mm OC (24"). The panels are locked together with the clips as part of the seam, by use of friction in the case of the Snap lock profiles, or by use of a mechanical seamer in the case of the mechanically locked profiles. :.2 Range of application on wood or metal sloped roofs in commercial, institutional, industrial and residential construction. This product is acceptable for re-roofing or new construction applications.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel nail strip or clips to plywood to be No. 10 by minimum 25 mm (1") pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 (1¾") wide, heights to suit seam height as per manufacturer’s requirements. Minimum clip thickness 0.022" (No. 22 MSG). Clips spaced maximum 600 mm (24") on centre fastened to plywood or steel deck. Minimum of two fasteners used Schlebach / Quadro Fixed Clip.
- Two piece assembly to be used for longer panel lengths, clip to be Schlebach approved 22 gauge, 88.1 mm (3½") wide by appropriate height to suit seam height chosen. One panel clip spaced a min. of maximum of 600 mm (24") OC.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Contact manufacturer for installation practise in extreme weather areas.
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: TOMTAR ROOFING AND SHEET METAL LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – KNUDSON KR-12
- DESCRIPTION
- The Knudson KR-12 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 38 mm (1.5").
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment
-
- Fasteners (Screws)
- For panel clip to steel attachment to be No. 12-16 by 22 mm (1") long self- drilling, self-tapping, hex-washer head plated steel screws used without sealing washers. Two fasteners per panel clip used, inserted into panel clip guide holes.
- Roof Deck Fastener (Panel clip)
- Two part assembly consisting of a No. 16 MSG min thick coated steel base approximately 47.6 mm (1-7/8") wide and 40.9 mm (1-5/8") long and a No. 22 MSG min thick coated steel upper tab section. Fastened 600 mm (24") on centre. Height 61 mm (2-7/16") min, 75 mm (3") max, width 108 mm (4-5/16") Knudson Manufacturing Inc. – “KR-24 Low-Floating Clip”, “KR-24 High-Floating Clip”OR
- One part assembly, No. 22 MSG min coated steel. Height, 59 mm (2-3/8") min, 75 mm (3") max, width 75 mm (3") Knudson Manufacturing Inc. – “KR-24 Low-Fixed Clip”, “KR-24 High-Fixed Clip” Fastened 600 mm (24") on centre.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: TOMTAR ROOFING AND SHEET METAL LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – KNUDSON P2401
- DESCRIPTION
The Knudson P-2401 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 50 mm (2").
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- For panel clip to steel attachment to be No. 12-16 by 22 mm (1") long self- drilling, self-tapping, hex-washer head plated steel screws used without sealing washers. Two fasteners per panel clip used, inserted into panel clip guide holes.
- Roof Deck Fastener (Panel clip)
- Two part assembly consisting of a No. 16 MSG min thick coated steel base approximately 47.6 mm (1-7/8") wide and 40.9 mm (1-5/8") long and a No. 22 MSG min thick coated steel upper tab section. Fastened 600 mm (24") on centre. Height 61 mm (2-7/16") min, 75 mm (3") max, width 108 mm (4-5/16") Knudson Manufacturing Inc. – “KR-24 Low-Floating Clip”, “KR-24 High-Floating Clip”
- OR
- One part assembly, No. 22 MSG min coated steel. Height, 59 mm (2-3/8") min, 75 mm (3") max, width 75 mm (3") Knudson Manufacturing Inc. – “KR-24 Low-Fixed Clip”, “KR-24 High-Fixed Clip”. Fastened 600 mm (24") on centre.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: WESTERN ROOFING MASTER ROOFERS LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – ESE 150 STANDING SEAM PANEL
- DESCRIPTION
- The ESE 150 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a standing seam height of 38 mm (1 1/2").
- This on-site manufacturing eliminates the need for end laps, with continuous panel forming capabilities in lengths up to 30.77 m (100').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 The range of application for this panel: on sloped wood or metal roof decks; in residential, commercial, and industrial applications; for new or reroof.
- .3 Panel Attachment:
- Panel Clips
- One piece clip 64 mm (2 ") wide by 38 mm (1 ½") high with a 16 mm (3/4") base. The minimum thickness is 22 gauge metal; fastened to a plywood deck 600 mm (24") on centre. Manufactured by Architectural Metal Specialities Inc.
- Fasteners
- Used to attach clips to plywood to be #8 x 1" long, pancake head, A-point, coated steel screw. Minimum two screws per clip. For steel decking or Z-girts the same size of screw with a pancake head, having a self-drill and tap point, and again two screws per clip.
- .4 Plywood decking is to be a nominal 13 mm (1/2") thick or thicker.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: FLYNN CANADA LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – KNUDSON KR-12
- DESCRIPTION
The Knudson KR-12 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 38 mm (1 1/2"). Panels are produced with two stiffening flutes.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment: Wood
- Panel clip to be Knudson 22 ga one piece assembly 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 762 mm (30") on centre. Two fasteners per panel clip used, inserted into panel clip guide holes. Fasteners to be #10 x 22 mm (1") long pancake head type A plated.
- Two piece assembly to be used for longer panel lengths, clip to be Knudson 22 ga 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre.
- Panel Attachment: Steel
- Panel clip to be Knudson 22 ga one piece assembly 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre. Two fasteners per panel clip used, inserted into panel clip guide holes. Fasteners to be #8-16 x 22 mm (1") long self-drilling, self tapping wafer head, plated screws.
- Two piece assembly to be used for longer panel lengths, clip to be Knudson 22 ga 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: FLYNN CANADA LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – KNUDSON KR-24
- DESCRIPTION
The Knudson KR-24 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 38 mm (1 1/2"). Panels are produced with two stiffening flutes.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification.
- The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment: Wood
Panel clip to be Knudson 22 ga one piece assembly 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre. Two fasteners per panel clip used, inserted into panel clip guide holes. Fasteners to be #10 x 22 mm (1") long pancake head type A plated.
- Two piece assembly to be used for longer panel lengths, clip to be Knudson 22 ga 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre.
- Panel Attachment: Steel
- Panel clip to be Knudson 22 ga one piece assembly 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre. Two fasteners per panel clip used, inserted into panel clip guide holes. Fasteners to be #8-16 x 22 mm (1") long self-drilling, self tapping wafer head, plated screws.
- Two piece assembly to be used for longer panel lengths, clip to be Knudson 22 ga 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
Manufacturer: FLYNN CANADA LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – KNUDSON P-2406
- DESCRIPTION
The Knudson P-2406 is an on-site continuous metal roll forming machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 38 mm (1.5"). Panels are produced with two stiffening flutes.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities.
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Architectural standing seam panels employ a hidden fastening system for securing to a solid substrate. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment: Wood
- Panel clip to be Knudson 22 ga one piece assembly 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre. Two fasteners per panel clip used, inserted into panel clip guide holes. Fasteners to be #10 x 22 mm (1") long pancake head type A plated.
- Two piece assembly to be used for longer panel lengths, clip to be Knudson 22 ga 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre.
- Panel Attachment: Steel
- Panel clip to be Knudson 22 ga one piece assembly 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre. Two fasteners per panel clip used, inserted into panel clip guide holes. Fasteners to be #8-16 x 22 mm (1") long self-drilling, self tapping wafer head, plated screws.
- Two piece assembly to be used for longer panel lengths, clip to be Knudson 22 ga 87.5 mm (3 1/2") wide 47.6 mm (1-5/8") high. One panel clip spaced at 600 mm (24") on centre.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
Manufacturer: FLYNN CANADA LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – SNAP LOCK II 675 PANEL
- DESCRIPTION
The Snap Lock II 675 Panel is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 44 mm (1-3/4").
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150’).
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 The SS675 44 mm (1-3/4") Snap-Lock profile is a snap lock concealed fastener roofing panel. The panel can be formed in any width between 300 mm (12") and 450 mm (18"). Stiffening ribs, striations and / or clip relief can be added depending in the application. The male leg locks along the entire length of the panel and does not rely upon clips to provide additional locking. The SS675 utilizes 153 mm (6-1/8") of metal in forming the panel legs providing greater structural integrity, which can carry greater loads.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to steel to be No. 10-16 by 25 mm (1") long cadmium plated pancake head No. 2 Phillips drive, No. 3 self-drilling point steel screws. Two screws per clip inserted through 6.25 mm (1/4") diameter guide holes.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly, No. 22 MSG min thick, 87.5 mm (3-1/2") wide, 47.6 mm (1-7/8 in.) high. One panel clip spaced at 600 mm (24") on centre for Class 90.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: FLYNN CANADA LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – SEAM LOCK – SS150 PANEL AND SS100 PANEL
- DESCRIPTION
- The New Tech Machinery Panel Machine is an on-site continuous metal roofing panel roll forming machine. This machine produces Seam Lock – SS 150 with a seam height of 38 mm (1-1/2") and Seam Lock – SS 100 with a seam height of 22 mm (1"). Both panel profiles vary from 300 mm (12") to 500 mm (20") wide.
- On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in. (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert “Series 1000 Interlocking Clip”.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: FLYNN CANADA LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – QUADRO Snap Seam – SS100 Panel
- DESCRIPTION
- QUADRO Panel Machine is an on-site/in-shop continuous metal roofing panel roll forming machine. This machine produces Snap Seam – SS 100 with a seam height of 25 mm (1"). This machine can produce either a Nail Strip System or a Clip System. Panels can be produced from 225 mm (9") wide up to 400mm (16") wide.
- On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022". (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Quadro 100 Clip.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: FLYNN CANADA LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – QUADRO Snap Seam – SS150 Panel
- DESCRIPTION
Quadro Panel Machine is an on-site/in-shop continuous metal roofing panel roll forming machine. This machine produces Snap Seam – SS 150 with a seam height of 38 mm (1-1/2"). This machine can produce either a Nail Strip System or a Clip system. Panels can be produced for 225 mm (9") to 400 mm (16") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022". (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Quadro 150 Clip.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: KELOWNA ROOFING (1984) LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – KNUDSON P-2401
- DESCRIPTION
The Knudson P-2401 is an on-site continuous metal roll forming machine. Panel profiles vary from 200 mm (8") to 610 mm (24") wide with a seam height of 38 mm (1 1/2").
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities.
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Architectural standing seam panels employ a hidden fastening system for securing to a solid substrate. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- For panel clip to steel connections use No. 10 by 25 mm (1") long self-drilling, self-tapping hex washer – head plated steel screws used without sealing washers. Two fasteners per panel clip to be used inserted through guide holes OR No. 10-16 Phillips pancake head screws may be used. Length to be 25 mm (1"). Three fasteners per clip to be used for pancake head type, inserted through guide holes.
- Roof Deck Fastener (Panel Clip)
- Two part assembly consisting of a coated steel base, No. 20 MSG min thick and a coated steel tab No. 24 MSG thick, overall height min 40.9 mm (1-5/8"), max 62.5 mm (2 1/2"), base width 150 mm (6") tab width 300 mm (12") located at sides of panel over attachment point. Knudson Manufacturing Inc. – “I.M.C. 2401 Sliding Strip Clip.” Fastened 600 mm (24") on centre. OR
- One part panel clip assembly, No. 22 MSG min thick. Overall height – min 40.9 mm (1-5/8"), max 62.5 mm (2 1/2") clip width 300 mm (12"). Knudson Manufacturing Inc. – “I.M.C. 2401 Fixed Strip Clip.” Fastened 600 mm (24") on centre.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: MAINLINE ROOFING CO. LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – ESE 150 STANDING SEAM PANEL
- DESCRIPTION
The ESE 150 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a standing seam height of 38 mm (1 1/2"). This on-site manufacturing eliminates the need for end laps, with continuous panel forming capabilities in lengths up to 30.77 m (100').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 The range of application for this panel: on sloped wood or metal roof decks; in residential, commercial, and industrial applications; for new or reroof.
- .3 Panel Attachment:
- Panel Clips –
- One piece clip 64 mm (2 ") wide by 38 mm (1 ½") high with a 16 mm (3/4") base. The minimum thickness is 22 gauge metal; fastened to a plywood deck 600 mm (24") on centre. Manufactured by Architectural Metal Specialities Inc.
- Fasteners
- Used to attach clips to plywood to be #8 x 1" long, pancake head, A-point, coated steel screw. Minimum two screws per clip. For steel decking or Z-girts the same size of screw with a pancake head, having a self-drill and tap point, and again two screws per clip.
- .4 Plywood decking is to be a nominal 13 mm (1/2") thick or thicker.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
Manufacturer: LAM METAL CONTRACTING LTD.
Contact Address: See Membership List in Section 1.
Product Group: SNAP LOCK SEAM METAL ROOF SYSTEM – SNAP-LOC 1"
- DESCRIPTION
The 1" Snap-Loc is a metal roof panel formed from 24 gauge. The panel can be applied on to solid sheeting with or without insulation. Width from 300 mm (12") to 400 mm (16") wide with a 22 mm (1") height at the male rib. Panels are continuous with no end laps.
Fasteners (screws) used to attach panels to plywood deck to be No. 8 by 22 mm (1") panhead. Fasteners to be placed a maximum of 600 mm (24") on center.
- PART 1 - GENERAL
1.1 The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
- .1 Metal panels employ a hidden fastening system for securement to a solid substrate. 1" Snap-Loc design allows the panel seams to interlock without having to use a mechanical seaming device.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; also used for roof replacement (retrofit) application.
1.3 DELIVERY, STORAGE AND HANDLING
- .1 Protect against damage and discoloration.
- .2 Handle panels with non-marring slings.
- .3 Do not bend panels.
- .4 Store panels above ground, with one end elevated for drainage.
- .5 Protect panels against standing water and condensation between adjacent surfaces.
- .6 If panels become wet, immediately separate sheets, wipe dry with clean cloth, allow to air dry.
- PART 2 - PRODUCTS
2.1 FABRICATION
- .1 Unless otherwise shown on drawings or specified herein, fabricate panels in continuous one piece lengths and fabricate flashings and accessories in longest practical lengths.
- .2 Roofing panels shall be factory formed or site formed.
2.2 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No. B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for Most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
- PART 3 - EXECUTION
3.1 EXAMINATION – EXISTING CONDITIONS
- .1 Verify that structural deck to receive panels is complete, in true plane, secure and otherwise properly prepared.
- .2 Prior to starting work, notify General Contractor about defects requiring correction.
- .3 Do not start work until conditions are satisfactory.
3.2 PREPARATION – FIELD MEASUREMENTS
- .1 Verify prior to fabrication.
- .2 If field measurements differ from drawing dimensions, notify Architect / Professional Engineer prior to fabrication.
- 3.3 PROTECTION
- .1 Treat, or isolate with protective material, any contacting surfaces of dissimilar materials to prevent electrolytic corrosion.
Manufacturer: LAM METAL CONTRACTING LTD.
Contact Address: See Membership List in Section 1.
Product Group: SNAP LOCK SEAM METAL ROOF SYSTEM – SNAP-LOC NU-TECH
- DESCRIPTION
The Snap-Loc Nu-Tech is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 457 mm (18") wide with a 44 mm (1 3/4") rib.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 The Snap-Loc Nu-Tech 44 mm (1 3/4") is a snap lock concealed fastener roofing panel. The panel can be formed in any width between 300 mm (12") to 457 mm (18"). Stiffening ribs, striations and / or clip relief can be added depending on the application. The male leg locks along the entire length of the panel and does not rely upon clips to provide additional locking. The Snap-Loc Nu-Tech utilizes 153 mm (6 1/8") of metal in forming the panel legs providing greater structural integrity, which can carry greater loads.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to steel to be No. 10-16 by 25 mm (1") long cadmium plated pancake head No. 2 Phillips drive, No. 3 self-drilling points steel screws. Two screws per clip inserted through 6.25 mm (1/4") diameter guide holes.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly, No. 22 MSG min thick, 88 mm (3 1/2") high. One panel clip spaced at 600 mm (24") on centre for Class 90.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: LAM METAL CONTRACTING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – SCHLEBACH 1"
- DESCRIPTION
- The Schlebach 1" Standing Seam metal roofing is a shop formed and an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") (standard width is 13", 15" or 20") with a seam height of 1". It can be rolled square, tapered and curved. It comes with no stiffening rib, with stiffening ribs and striation.
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- For panel clip to steel attachment to be No. 12-16 by 22 mm (1") long self-drilling, self-tapping, hex-washer head plated steel screws used without sealing washers. Two fasteners per panel clip used, inserted into panel clip guide holes.
- Roof Deck Fasteners (Panel Clips)
- Two piece assembly consisting of a No. 18 or No. 16 MSG min thick coated steel base approximately 22 mm (1") wide x 125 mm (5") long and No. 24 MSG min thick steel upper tap section height 22 mm (1") as manufactured by metal Roofing Supply Inc. in Denver. One panel clip spaced at 600 mm (24") on centre.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: LAM METAL CONTRACTING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – LAM METAL BERRIDGE T-PANEL, COMPOUND CURVED & TAPERED TEE-PANEL
- DESCRIPTION
- Lam Metal Berridge T-Panel can be roll formed as straight, tapered or curved to any radius greater than 10’ in continuous length from a coil. Panel width is 12 ¾" (324 mm) with a 5/8" (16 mm) leg, and a nominal 1" (25 mm) seam height after clipping on the Snap-On Seam.
1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
- .1 Berridge T-Panel employ a hidden fastening system for securement to a solid substrate. Panel seams are covered by extruded vinyl weatherseal to prevent siphoning or flooding over seam and the panels are seamed together by Snap-On Seam.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Use 11 gauge 1¼" galvanized roofing for installation over wood, and use #10 x 1¼" pancake head teks screws for installation over metal. One fastener per clip @ minimum 20" OC.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly consisting of a No. 26 GA minimum thick coated steel base approximately 1" wide x 2" long as manufactured by Berridge Manufacturing in Denver, USA.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 3:12 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- The Berridge T-Panel complies with UL 90, No. 580 Wind Uplifting Resistance of Roof Assemblies, and UL Fire Resistance Roof Assemblies, No. P-224, 225, 227, 230, 237, 508, 512, 701 and 803.
- 1.5 Material
- ASTM Standard specifications A446-85 Grade C, G-90 coasting ASTM A 653 –94 and 924-94, 24 gauge hot-dipped galvanized pre-finished steel. ASTM standard specification 792-86 24 gauge pre-finished Galvalume®.
- 1.6 Paint Finish
- Fluorocarbon coating finish, Kynar 500® or Hylar 5000™ with a top side film thickness of 0.70 to 0.90 mil over 0.25 to 0.31 mil primer coat to a total dry film thickness of 0.95 to 1.25 mil. Primer coat on bottom side of panel shall be a dry film thickness of 0.25 mil.
Manufacturer: LAM METAL CONTRACTING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – ESE 100 STANDING SEAM PANEL
- DESCRIPTION
The ESE 100 Standing Seam Metal roof is shop formed and on site continuous panel metal roofing machine. Panel profiles vary from 330 mm (13") to 533 mm (21") wide with a seam height of 25 mm (1"). Standard width is 13", 15" or 21". It can be formed with optional stiffening ribs or striation to reduce oil canning. The panel can also be formed into curved and tapered panels. Batterns can be attached to the 1" seam height for a more distinct architectural look.
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening system for securement to a solid substrate. The panels are seamed together with a mechanical seamer.
- .2 The range of application for this panel: on wood or metal sloped roofs; in residential, commercial, institutional and industrial applications; for reproofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- For panel clip to steel attachment to be No. 13-16 by 22 mm (1") long self-drilling, self-tapping, hex-washer head plated steel screws used without sealing washers. Two fasteners per panel clip used, inserted into panel clip guide holes.
- Roof Deck Fasteners (Panel Clip)
- There are two types. One piece 1.5" wide by 1" high with a 1" base in 24 ga as manufactured by Lam Metal. Two parts assembly consisting of a a24 ga msg minimum thick coated steel base approximately 1" wide x 5" long and 24 ga msg minimum thick steel upper tap section height 1" as manufactured by Logan Stamping Ltd.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
Manufacturer: LAM METAL CONTRACTING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM - 1" SUPER SNAP-LOC CONCEALED FASTENER SYSTEM
- DESCRIPTION
The 1" Super Snap-Loc is metal roof and wall panel formed of 24 gauge. The panel can be applied onto solid sheeting with or without insulation. Width from is 12" to 20", with a 1" height at the male rib. Panels are continuous with no end laps. Sides are raised to accommodate screw heads. Fasteners (screws) used to attach panels to plywood deck to be No. 8 by 1" pan head.
- PART 1 - GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- 1. Metal panels employ a hidden fastening system for securement to a solid substrate. 1" Super Snap-Loc design allows the panel seams to interlock without having to use a mechanical seaming device.
- 2. Range of application: on wood or metal sloped roofs and to vertical wall framing in commercial, institutional, industrial and residential construction: also used for roof recovering or roof replacement (retrofit) application.
- 1.3 DELIVERY. STORAGE AND HANDLING
- 1. Protect against damage and discoloration.
- 2. Handle panels with non-marring slings.
- 3. Do not bend panels.
- 4. Store panels above ground, with one end elevated for drainage.
- 5. Protect panels against standing water and condensation between adjacent surfaces.
- 6. If panels become wet, immediately separate sheets, wipe dry with clean cloth, allow to air dry.
- PART 2- PRODUCTS
- 2.1 FABRICATION
- 1. Unless otherwise shown on drawings or specified herein, fabricate panels in continuous one piece lengths and fabricate flashings and accessories in longest practical lengths.
- 2. Roofing panels shall be factory formed or site formed.
- 2.2 PERFORMANCE REQUIREMENTS
- 1. Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No. B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptance level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer Appendix II for calculations for typical roof wind uplift pressure requirements for building located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers. RGC accepted metal panel systems shall be formed of steel conforming to one of the following specifications, as applicable:
- ASTM Standard Specifications A653 / A653M Sheet Steel. Zinc-coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by hot dip process, minimum Grade 33, with a design thickness of 24 gauge (.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process. Minimum Grade 33, with a design thickness of 24 gauge (.024") or greater and minimum coating designation AZ150.
- PART 3- EXECUTION
- 3.1 EXAMINATION - EXISTING CONDITIONS
- 1. Verify that structural deck to receive panels complete, in true plane, secure and otherwise properly prepared.
- 2. Prior to starting work, notify General Contractor about defects requiring correction.
- 3. Do not start work until conditions are satisfactory.
- 3.2 PREPARATION - FIELD MEASUREMENTS
- 1. Verify prior to fabrication.
- 2. If field measurements differ from drawing dimensions, notify Architect / Professional Engineer prior to fabrication.
- 3.3 PROTECTION
- 1. Treat, or isolate with protective material, any contacting surfaces of dissimilar materials to prevent electrolytic corrosion.
Active Member: UNIVERSAL SHEET METAL LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM - Knudson KR-12
DESCRIPTION
The Knudson KR-12 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 38 mm (1 1/2").
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2. SYSTEM DESCRIPTION
- .1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- For panel clip to steel attachment to be No. 12-16 by 22 mm (1") long self- drilling, self-tapping, hex-washer head plated steel screws used without sealing washers. Two fasteners per panel clip used, inserted into panel clip guide holes.
- Roof Deck Fastener (Panel clip
- Two part assembly consisting of a No. 16 MSG min thick coated steel base approximately 47.6 mm (1-7/8") wide and 40.9 mm (1-5/8") long and a No. 22 MSG min thick coated steel upper tab section. Fastened 600 mm (24") on centre. Height 61 mm (2-7/16") min, 75 mm (3") max, width 108 mm (4-5/16") Knudson Manufacturing Inc. – “KR-24 Low-Floating Clip”, “KR-24 High-Floating Clip”OR
- One part assembly, No. 22 MSG min coated steel. Height, 59 mm (2-3/8") min, 75 mm (3") max, width 75 mm (3") Knudson Manufacturing Inc. – “KR-24 Low-Fixed Clip”, “KR-24 High-Fixed Clip”. Fastened 600 mm (24") on centre.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminium-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: STANDARD ROOFING CORPORATION
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – KNUDSON P2401
- DESCRIPTION
The Knudson P-2401 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 50 mm (2").
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- For panel clip to steel attachment to be No. 12-16 by 22 mm (1") long self- drilling, self-tapping, hex-washer head plated steel screws used without sealing washers. Two fasteners per panel clip used, inserted into panel clip guide holes.
- Roof Deck Fastener (Panel clip)
- Two part assembly consisting of a No. 16 MSG min thick coated steel base approximately 47.6 mm (1-7/8") wide and 40.9 mm (1-5/8") long and a No. 22 MSG min thick coated steel upper tab section. Fastened 600 mm (24") on centre. Height 61 mm (2-7/16") min, 75 mm (3") max, width 108 mm (4-5/16") Knudson Manufacturing Inc. – “KR-24 Low-Floating Clip”, “KR-24 High-Floating Clip” OR
- One part assembly, No. 22 MSG min coated steel. Height, 59 mm (2-3/8") min, 75 mm (3") max, width 75 mm (3") Knudson Manufacturing Inc. – “KR-24 Low-Fixed Clip”, “KR-24 High-Fixed Clip”. Fastened 600 mm (24") on centre.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminium-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: B.F. ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – ROLL FORMER VS-150
- DESCRIPTION
The VS-150 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 37.5 mm (1-1/2").
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. Maximum clip spacing is 450 mm (18") o/c. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal-sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1 in.) long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One-piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in. (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck.
- .4 Plywood Decking: The plywood is to be a nominal 15.9 mm (5/8") (19/32") thick, square edged.
1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: EBY & SON CONSTRUCTION LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM ZIMMERMAN SS 1500 STANDING SEAM PANEL
- DESCRIPTION
The Zimmerman SS 1500 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a standing seam height of 38 mm (1½").
This on–site manufacturing eliminates the need for end laps, with continuous panel forming capabilities in lengths up to 15 – 24 m (50’).
1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application for this panel: on wood or metal-sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Panel clips
- One piece clip 64 mm (2½") wide by 38mm (1½") high with a 16 mm (5/8") base. The minimum thickness is 22 gauge metal; fastened to a plywood deck 600 mm (24") on centre. Custom-Built 2SS RC1.5" standing seam roof clip.
- Fasteners
- Used to attach clips to plywood to be #8 x 1" long pancake head, A-point, coated steel screw. Minimum 2 screws per clip. For steel decking or Z-girts, #8 x 1" long pancake head, having a self-drill and tap point, minimum 2 screws per clip.
- .4 Plywood decking is to be nominal 13mm (½") thick or thicker.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: HOMAN CONTRACTORS LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – SEAM LOCK – SS150 PANEL AND SS100 PANEL
- DESCRIPTION
The New Tech Machinery Panel Machine is an on-site continuous metal roofing panel roll forming machine. This machine produces Seam Lock – SS 150 with a seam height of 38 mm (1-1/2") and Seam Lock – SS 100 with a seam height of 22 mm (1"). Both panel profiles vary from 300 mm (12") to 500 mm (20") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in. (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert “Series 1000 Interlocking Clip”.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: CROWN ROOFING & DRAINAGE LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – CROWN 1" & 1½" STANDING SEAM PANEL
- DESCRIPTION
The New Tech Machinery Panel Machine is an on-site continuous metal roofing panel roll forming machine. This machine produces Seam Lock – SS 150 with a seam height of 38 mm (1-1/2") and Seam Lock – SS 100 with a seam height of 25 mm (1"). Both panel profiles vary from 300 mm (12") to 500 mm (20") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in. (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert “Series 1000 Interlocking Clip”.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: CROWN ROOFING & DRAINAGE LTD.
Contact Address: See Membership List in Section 1.
Product Group: SEAM METAL ROOF SYSTEM – CROWN 1" FF SNAP-LOC
- DESCRIPTION
- The 1" Snap-Lock is a metal roof panel formed from 24 gauge. The panel can be applied on to solid sheeting with or without insulation. Width from 300 mm (12") to 500 mm (20") wide with a 25 mm (1") height at the male rib. Panels are continuous with no end laps.
- Fasteners (screws) used to attach panels to plywood deck to be No. 8 by 22 mm (1") panhead. Fasteners to be placed a maximum of 600 mm (24") on center.
- PART 1 - GENERAL
1.1 The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
- .1 Metal panels employ a hidden fastening system for securement to a solid substrate. 1" Snap-Lock panels are produced with a nail strip to eliminate the use of clips and allows the panel seams to interlock without having to use a mechanical seaming device
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; also used for roof replacement (retrofit) application.
1.3 DELIVERY, STORAGE AND HANDLING
- .1 Protect against damage and discoloration.
- .2 Handle panels with non-marring slings.
- .3 Do not bend panels.
- .4 Store panels above ground, with one end elevated for drainage.
- .5 Protect panels against standing water and condensation between adjacent surfaces.
- .6 If panels become wet, immediately separate sheets, wipe dry with clean cloth, allow to air dry.
- PART 2 - PRODUCTS
2.1 FABRICATION
- .1 Unless otherwise shown on drawings or specified herein, fabricate panels in continuous one piece lengths and fabricate flashings and accessories in longest practical lengths.
- .2 Roofing panels shall be factory formed or site formed.
2.2 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No. B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for Most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
- PART 3 - EXECUTION
3.1 EXAMINATION – EXISTING CONDITIONS
- .1 Verify that structural deck to receive panels is complete, in true plane, secure and otherwise properly prepared.
- .2 Prior to starting work, notify General Contractor about defects requiring correction.
- .3 Do not start work until conditions are satisfactory.
3.2 PREPARATION – FIELD MEASUREMENTS
- .1 Verify prior to fabrication.
- .2 If field measurements differ from drawing dimensions, notify Architect / Professional Engineer prior to fabrication.
3.3 PROTECTION
- .1 Treat, or isolate with protective material, any contacting surfaces of dissimilar materials to prevent electrolytic corrosion.
Manufacturer: CROWN ROOFING AND DRAINAGE LTD.
Contact Address: See Membership List in Section 1.
Product Group: SNAP LOCK SEAM METAL ROOF SYSTEM - CROWN 1-1/2" SNAP-LOCK PANEL
- DESCRIPTION
The Crown 1½" Snap Lock is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a 38 mm (1½") rib.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
1.1 GENERAL
The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
- .1 The Crown 1½" Snap Lock 38 mm (1½") is a snap lock concealed fastener roofing panel. The panel can be formed in any width between 300 mm (12") to 500 mm (20"). Stiffening ribs, striations and / or clip relief can be added depending on the application. The male leg locks along the entire length of the panel and does not rely upon clips to provide additional locking. The Crown 1½" Snap Lock utilizes 130 mm (5 1/8") of metal in forming the panel legs providing greater structural integrity, which can carry greater loads.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to steel to be No. 10-16 by 25 mm (1") long cadmium plated pancake head No. 2 Phillips drive, No. 3 self-drilling points steel screws. Two screws per clip inserted through 6.25 mm (1/4") diameter guide holes.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly, No. 22 MSG min thick, 88 mm (3 1/2") high. One panel clip spaced at 600 mm (24") on centre for Class 90.
1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: METRO ROOFING & SHEET METAL LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – SS150 PANEL AND SS100 PANEL
- DESCRIPTION
The New Tech Machinery Panel Machine is an on-site continuous metal roofing panel roll forming machine. This machine produces Seam Lock – SS 150 with a seam height of 38 mm (1-1/2") and Seam Lock – SS 100 with a seam height of 25 mm (1"). Both panel profiles vary from 300 mm (12") to 500 mm (20") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in. (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert “Series 1000 Interlocking Clip”.
1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: METRO ROOFING & SHEET METAL LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – SS675 PANEL
- DESCRIPTION
The Snap Lock II 675 Panel is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 44 mm (1-3/4").
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150’).
1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
- .1 The SS675 44 mm (1-3/4") Snap-Lock profile is a snap lock concealed fastener roofing panel. The panel can be formed in any width between 300 mm (12") and 450 mm (18"). Stiffening ribs, striations and / or clip relief can be added depending in the application. The male leg locks along the entire length of the panel and does not rely upon clips to provide additional locking. The SS675 utilizes 153 mm (6-1/8") of metal in forming the panel legs providing greater structural integrity, which can carry greater loads.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to steel to be No. 10-16 by 25 mm (1") long cadmium plated pancake head No. 2 Phillips drive, No. 3 self-drilling point steel screws. Two screws per clip inserted through 6.25 mm (1/4") diameter guide holes.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly, No. 22 MSG min thick, 87.5 mm (3-1/2") wide, 47.6 mm (1-7/8 in.) high. One panel clip spaced at 600 mm (24") on centre for Class 90.
1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: MARINE ROOFING (1996) LTD.
Contact Address: See Membership List in Section 1.
Product Group: SNAP LOCK SEAM METAL ROOF SYSTEM - SNAP-LOC NU-TECH
- DESCRIPTION
The Snap-Loc Nu-Tech is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 457 mm (18") wide with a 44 mm (1¾") rib.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer’s published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
- .1 The Snap-Loc Nu-Tech 44 mm (1¾") is a snap lock concealed fastener roofing panel. The panel can be formed in any width between 300 mm (12") to 457 mm (18"). Stiffening ribs, striations and / or clip relief can be added depending on the application. The male leg locks along the entire length of the panel and does not rely upon clips to provide additional locking. The Snap-Loc Nu-Tech utilizes 153 mm (61/8") of metal in forming the panel legs providing greater structural integrity, which can carry greater loads.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to steel to be No. 10 - 16 pancake head, No. 2 Phillips drive, No. 3 self-drilling point steel screws. Two screws per clip inserted through 6.25 mm (¼") diameter guide holes.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly, No. 22 MSG min. thick, 88 mm (3½") high. One panel clip spaced at 600 mm (24") on centre for Class 90.
1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: MARINE ROOFING (1996) LTD.
Contact Address: See Membership List in Section 1.
Product Group: SEAM METAL ROOF SYSTEM – MR-100
- DESCRIPTION
The 1" MR-100 is a metal roof panel formed from 24 gauge. The panel can be applied onto solid sheeting with or without insulation. Width from 300 mm (12") to 500 mm (20") wide with a 25 mm (1") height at the male rib.
On-site rool forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- PART 1 - GENERAL
1.1 The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
- .1 Metal panels employ a hidden fastening system for securement to a solid substrate. 1" MR-100 panels are produced with a nail strip to eliminate the use of clips and allow the panel seams to interlock without having to use a mechanical seaming device.
- .2 Range of application: on wood or metal sloped roofs, with or without exterior insulation; in commercial, institutional, industrial and residential construction; also used for roof replacement (retrofit) application.
- .3 Panel Attachment:
- Fasteners(Screws) - Fasteners used to attach panels to steel or wood substrate to be No. 10 - 16 pancake head, No. 2 Phillips drive, self-drilling, coated screw.
1.3 DELIVERY, STORAGE AND HANDLING
- .1 Protect against damage and discoloration.
- .2 Handle panels with non-marring slings.
- .3 Do not bend panels.
- .4 Store panels above ground, with one end elevated for drainage.
- .5 Protect panels against standing water and condensation between adjacent surfaces.
- .6 If panels become wet, immediately separate sheets, wipe dry with clean cloth, allow to air dry.
- PART 2 - PRODUCTS
2.1 FABRICATION
- .1 Unless otherwise shown on drawings or specified herein, fabricate panels in continuous one piece lengths and fabricate flashings and accessories in longest practical lengths.
- .2 Roofing panels shall be factory formed or site formed.
2.2 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No. B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
- PART 3 - EXECUTION
3.1 EXAMINATION – EXISTING CONDITIONS
- .1 Verify that structural deck to receive panels is complete, in true plane, secure and otherwise properly prepared.
- .2 Prior to starting work, notify General Contractor about defects requiring correction.
- .3 Do not start work until conditions are satisfactory.
3.2 PREPARATION – FIELD MEASUREMENTS
- .1 Verify prior to fabrication.
- .2 If field measurements differ from drawing dimensions, notify Architect / Professional Engineer prior to fabrication.
- 3.3 PROTECTION
- .1 Treat, or isolate with protective material, any contacting surfaces of dissimilar materials to prevent electrolytic corrosion.
Manufacturer: MARINE ROOFING (1996) LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – MR/S-100
- DESCRIPTION
The New Tech Machinery Panel Machine is an on-site continuous panel metal roofing machine. This machine produces MR/S-100 panels with a seam height of 22 mm (1"). Panel profiles vary from 300 mm (12") to 500mm (20") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs with or without exterior insulation; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to steel to be No. 10-16 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022". (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert "series 1000 Interlocking Clip".
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
-
- .1 Wind Uplift Standards
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: MARINE ROOFING (1996) LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – MR/S-150
- DESCRIPTION
The New Tech Machinery Panel Machine is an on-site continuous panel metal roofing machine. This machine produces MR/S-150 panels with a seam height of 38 mm (1-1/2"). Panel profiles vary from 300 mm (12") to 500mm (20") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs with or without exterior insulation; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to steel to be No. 10-16 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022". (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert "series 1000 Interlocking Clip".
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
-
- .1 Wind Uplift Standards
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: MARINE ROOFING (1996) LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – MR-675
- DESCRIPTION
The New Tech Machinery Panel Machine is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 457 mm (18") wide with a 44 mm (1-3/4") rib.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 The MR-675 44 mm (1-3/4") is a snap lock concealed fastener roofing panel. The panel can be formed in any width between 300 mm (12") to 457 mm (18"). Stiffening ribs, striations and/or clip relief can be added depending on the application. The male leg locks along the entire length of the panel and does not rely upon clips to provide additional locking. The MR-675 utilizes 153 mm (6-1/8")of metal in forming the panel legs providing greater structural integrity, which can carry greater loads.
- .2 Range of application: on wood or metal sloped roofs with or without exterior insulation; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to steel to be No. 10 - 16 by 25 mm (1") long cadmium plated pancake head, No. 2 Phillips drive, No. 3 self-drilling point steel screws. Two screws per clip inserted through 6.25 mm (1/4") diameter guide holes.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly, No. 22 MSG min. thick, 88 mm (3-1/2") high. One panel clip spaced at 600 mm (24") on centre for Class 90.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
-
- .1 Wind Uplift Standards
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: POCKLINGTON BUILDING SYSTEMS LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – SEAM LOCK – SS100 PANEL AND SS150 PANEL
- DESCRIPTION
- The New Tech Machinery Panel Machine is an on-site continuous metal roofing panel roll forming machine. This machine produces Seam Lock – SS 100 with a seam height of 38 mm (1") and Seam Lock – SS 150 with a seam height of 22 mm (1-1/2"). Both panel profiles vary from 300 mm (12") to 500 mm (20") wide.
- On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
1.1 GENERAL
- .1 The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in. (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert “Series 1000 Interlocking Clip”.
1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: POCKLINGTON BUILDING SYSTEMS LTD.
Contact Address: See Membership List in Section 1.
Product Group: SNAP LOCK SEAM METAL ROOF SYSTEM – Snap Lock FF150 PANEL DESCRIPTION
- DESCRIPTION
- The New Tech Machinery Panel Machine is an on-site continuous metal roofing panel roll forming machine. This machine produces Snap Lock – FF 150 with a seam height of 22 mm (1-1/2"). Both panel profiles vary from 300 mm (12") to 500 mm (20") wide. This machine also produces a Standing Seam panel.
- On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
1.1 GENERAL
- .1 The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in. (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert “Series 1000 Interlocking Clip”.
1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: CASCADE ROOFING & WATERPROOFING (2007) INC.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM ZIMMERMAN SS 1500 STANDING SEAM PANEL
- DESCRIPTION
- The Zimmerman SS 1500 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a standing seam height of 38 mm (1½").
- This on–site manufacturing eliminates the need for end laps, with continuous panel forming capabilities in lengths up to 15 – 24 m (50’).
1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application for this panel: on wood or metal-sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Panel clips
- One piece clip 64 mm (2½") wide by 38mm (1½") high with a 16 mm (5/8") base. The minimum thickness is 22 gauge metal; fastened to a plywood deck 600 mm (24") on centre. Custom-Built 2SS RC1.5" standing seam roof clip.
- Fasteners
- Used to attach clips to plywood to be #8 x 1" long pancake head, A-point, coated steel screw. Minimum 2 screws per clip. For steel decking or Z-girts, #8 x 1" long pancake head, having a self-drill and tap point, minimum 2 screws per clip.
- .4 Plywood decking is to be nominal 13mm (½") thick or thicker.
1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: CASCADE ROOFING & WATERPROOFING (2007) INC.
Contact Address: See Membership List in Section 1.
Product Group: SNAP LOCK SEAM METAL ROOF SYSTEM - SNAP-LOC NU-TECH
- DESCRIPTION
The Snap-Loc Nu-Tech is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 457 mm (18") wide with a 44 mm (1¾") rib.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer’s published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
- .1 The Snap-Loc Nu-Tech 44 mm (1¾") is a snap lock concealed fastener roofing panel. The panel can be formed in any width between 300 mm (12") to 457 mm (18"). Stiffening ribs, striations and / or clip relief can be added depending on the application. The male leg locks along the entire length of the panel and does not rely upon clips to provide additional locking. The Snap-Loc Nu-Tech utilizes 153 mm (61/8") of metal in forming the panel legs providing greater structural integrity, which can carry greater loads.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws) - fasteners used to attach panel clips to steel to be No. 10 - 16 by 25 mm (1") long cadmium plated pancake head, No. 2 Phillips drive, No. 3 self-drilling point steel screws. Two screws per clip inserted through 6.25 mm (¼") diameter guide holes.
- Roof Deck Fasteners (Panel Clips) - one piece assembly, No. 22 MSG min. thick, 88 mm (3½") high. One panel clip spaced at 600 mm (24") on centre for Class 90.
1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:15 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Active Member: AURORA ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM - Knudson KR-12
- DESCRIPTION
- The Knudson KR-12 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 38 mm (1 1/2").
- On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
1.1 GENERAL
- The roofing assembly / material information published in the RGC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2. SYSTEM DESCRIPTION
- .1 Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- For panel clip to steel attachment to be No. 12-16 by 22 mm (1") long self- drilling, self-tapping, hex-washer head plated steel screws used without sealing washers. Two fasteners per panel clip used, inserted into panel clip guide holes.
- Roof Deck Fastener (Panel clip)
- Two part assembly consisting of a No. 16 MSG min thick coated steel base approximately 47.6 mm (1-7/8") wide and 40.9 mm (1-5/8") long and a No. 22 MSG min thick coated steel upper tab section. Fastened 600 mm (24") on centre. Height 61 mm (2-7/16") min, 75 mm (3") max, width 108 mm (4-5/16") Knudson Manufacturing Inc. – “KR-24 Low-Floating Clip”, “KR-24 High-Floating Clip”OR
- One part assembly, No. 22 MSG min coated steel. Height, 59 mm (2-3/8") min, 75 mm (3") max, width 75 mm (3") Knudson Manufacturing Inc. – “KR-24 Low-Fixed Clip”, “KR-24 High-Fixed Clip”. Fastened 600 mm (24") on centre.
1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 7.5.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminium-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: VILLA ROOFING & SHEET METAL LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – VillaLoc II 675 PANEL
- DESCRIPTION
The Villa Loc II 675 Panel is formed on-site on a New Tech Machinery continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 44 mm (1-3/4").
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150’).
1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
1.2 SYSTEM DESCRIPTION
- .1 The SS675 44 mm (1-3/4") Snap-Lock profile is a snap lock concealed fastener roofing panel. The panel can be formed in any width between 300 mm (12") and 450 mm (18"). Stiffening ribs, striations and / or clip relief can be added depending in the application. The male leg locks along the entire length of the panel and does not rely upon clips to provide additional locking. The SS675 utilizes 153 mm (6-1/8") of metal in forming the panel legs providing greater structural integrity, which can carry greater loads.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to steel to be No. 10-16 by 25 mm (1") long cadmium plated pancake head No. 2 Phillips drive, No. 3 self-drilling point steel screws. Two screws per clip inserted through 6.25 mm (1/4") diameter guide holes.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly, No. 22 MSG min thick, 87.5 mm (3-1/2") wide, 47.6 mm (1-7/8 in.) high. One panel clip spaced at 600 mm (24") on centre for Class 90.
1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 7.5.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: VILLA ROOFING & SHEET METAL LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – VILLA SEAM – SS150 PANEL AND VILLA SEAM – SS100 PANEL
- DESCRIPTION
The Villa Seam– SS150 and Villa Seam – SS100 metal panels are produced on-site on a New Tech Machinery continuous metal roofing panel roll forming machine. This machine produces Seam Lock – SS 150 with a seam height of 38 mm (1-1/2") and Seam Lock – SS 100 with a seam height of 22 mm (1"). Both panel profiles vary from 300 mm (12") to 500 mm (20") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in. (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert “Series 1000 Interlocking Clip”.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 7.5.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: VILLA ROOFING & SHEET METAL LTD.
Contact Address: See Membership List in Section 1.
Product Group: SEAM METAL ROOF SYSTEM – 1" FF VILLA SNAP-LOC
- DESCRIPTION
The 1" FF Villa Snap-Loc is a metal roof panel formed from 24 gauge. The panel can be applied on to solid sheeting with or without insulation. Width from 300 mm (12") to 500 mm (20") wide with a 25 mm (1") height at the male rib. Panels are continuous with no end laps.
Fasteners (screws) used to attach panels to plywood deck to be No. 8 by 22 mm (1") panhead. Fasteners to be placed a maximum of 600 mm (24") on center.
- PART 1 - GENERAL
1.1 The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Metal panels employ a hidden fastening system for securement to a solid substrate. 1" Snap-Lock panels are produced with a nail strip to eliminate the use of clips and allows the panel seams to interlock without having to use a mechanical seaming device
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; also used for roof replacement (retrofit) application.
- 1.3 DELIVERY, STORAGE AND HANDLING
- .1 Protect against damage and discoloration.
- .2 Handle panels with non-marring slings.
- .3 Do not bend panels.
- .4 Store panels above ground, with one end elevated for drainage.
- .5 Protect panels against standing water and condensation between adjacent surfaces.
- .6 If panels become wet, immediately separate sheets, wipe dry with clean cloth, allow to air dry.
- PART 2 - PRODUCTS
- 2.1 FABRICATION
- .1 Unless otherwise shown on drawings or specified herein, fabricate panels in continuous one piece lengths and fabricate flashings and accessories in longest practical lengths.
- .2 Roofing panels shall be factory formed or site formed.
- 2.2 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No. B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for Most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 7.5.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
- PART 3 - EXECUTION
- 3.1 EXAMINATION – EXISTING CONDITIONS
- .1 Verify that structural deck to receive panels is complete, in true plane, secure and otherwise properly prepared.
- .2 Prior to starting work, notify General Contractor about defects requiring correction.
- .3 Do not start work until conditions are satisfactory.
- 3.2 PREPARATION – FIELD MEASUREMENTS
- .1 Verify prior to fabrication.
- .2 If field measurements differ from drawing dimensions, notify Architect / Professional Engineer prior to fabrication.
- 3.3 PROTECTION
- .1 Treat, or isolate with protective material, any contacting surfaces of dissimilar materials to prevent electrolytic corrosion.
Manufacturer: RAVEN ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – SNAP LOCK 675 PANEL
- DESCRIPTION
The Snap Lock 675 Panel is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 44 mm (1-3/4").
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150’).
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 The SS675 44 mm (1-3/4") Snap-Lock profile is a snap lock concealed fastener roofing panel. The panel can be formed in any width between 300 mm (12") and 450 mm (18"). Stiffening ribs, striations and / or clip relief can be added depending on the application. The male leg locks along the entire length of the panel and does not rely upon clips to provide additional locking. The SS675 utilizes 153 mm (6-1/8") of metal in forming the panel legs providing greater structural integrity, which can carry greater loads.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to steel to be No. 10-16 by 25 mm (1") long cadmium plated pancake head No. 2 Phillips drive, No. 3 self-drilling point steel screws. Two screws per clip inserted through 6.25 mm (1/4") diameter guide holes.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly, No. 22 MSG min thick, 87.5 mm (3-1/2") wide, 47.6 mm (1-7/8 in.) high. One panel clip spaced at 600 mm (24") on centre for Class 90.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: RAVEN ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM - SS150 PANEL and SS100 PANEL
- DESCRIPTION
The New Tech Machinery Panel Machine is an on-site continuous metal roofing panel roll forming machine. This machine produces Seam Lock - SS 150 with a seam height of 38 mm (1-1/2") and Seam Lock - SS 100 with a seam height of 22 mm (1"). Both panel profiles vary from 300 mm (12") to 500 mm (20") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46m (150').
- 1.1 GENERAL
The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws) - Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips) - One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in.(No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert "Series 1000 Interlocking Clip".
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: RAVEN ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – QUADRO Snap Seam - FFQ100 Panel
- DESCRIPTION
Quadro Panel Machine is an on-site/in-shop continuous metal roofing panel roll forming machine. This machine produces Snap Seam -FFQ 100 with a seam height of 25 mm (1").
This machine can produce either a Nail Strip System or a Clip system. Panels can be produced from 225 mm (9") wide up to 400 mm (16") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').
- 1.1 GENERAL
The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for reroofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022". (No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Quadro 100 Clip.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in TAB 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: TRANSWEST ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM - SEAM LOCK - SS100 PANEL
- DESCRIPTION
The New Tech Machinery Panel Machine is an on-site continuous metal roofing panel roll forming machine. This machine produces Seam Lock - SS 100 with a seam height of 22 mm (1"). Panel profiles vary from 300 mm (12") to 500 mm (20") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46m (150').
- 1.1 GENERAL
The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels use a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips is 600 mm (24") on centre. The panels are locked together, with the clips as part of the seam, by use of a mechanical seamer.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws) - Fasteners used to attach panel clips to plywood to be No. 10-12 by 25 mm (1") long pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips) - One piece assembly 43.75 mm (1-3/4") wide, 31 mm (1-1/4") high. Minimum thickness 0.022 in.(No. 22 MSG). Clips spaced 600 mm (24") on centre fastened to plywood deck. Englert "Series 1000 Interlocking Clip".
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:4 (3" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in Section 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: TRANSWEST ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM –SNAP LOCK II 675 PANEL
- DESCRIPTION
The Snap Lock II 675 Panel is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 44 mm (1-3/4").
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150’).
- 1.1 GENERAL
- The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 The SS675 44 mm (1-3/4") Snap-Lock profile is a snap lock concealed fastener roofing panel. The panel can be formed in any width between 300 mm (12") and 450 mm (18"). Stiffening ribs, striations and / or clip relief can be added depending on the application. The male leg locks along the entire length of the panel and does not rely upon clips to provide additional locking. The SS675 utilizes 153 mm (6-1/8") of metal in forming the panel legs providing greater structural integrity, which can carry greater loads.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel clips to steel to be No. 10-16 by 25 mm (1") long cadmium plated pancake head No. 2 Phillips drive, No. 3 self-drilling point steel screws. Two screws per clip inserted through 6.25 mm (1/4") diameter guide holes.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly, No. 22 MSG min thick, 87.5 mm (3-1/2") wide, 47.6 mm (1-7/8 in.) high. One panel clip spaced at 600 mm (24") on centre for Class 90.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in Section 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
Manufacturer: TRANSWEST ROOFING LTD.
Contact Address: See Membership List in Section 1.
Product Group: SEAM METAL ROOF SYSTEM - FF100 PANEL
- DESCRIPTION
The FF100 Panel is a metal roof panel formed from 24 gauge. The panel can be applied on to solid sheeting with or without insulation. Width from 300 mm (12") to 500 mm (20") wide with a 25 mm (1") height at the male rib. Panels are continuous with no end laps.
Fasteners (screws) used to attach panels to plywood deck to be No. 8 by 22 mm (1") panhead. Fasteners to be placed a maximum of 600 mm (24") on center.
- PART 1 - GENERAL
- 1.1 The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Metal panels employ a hidden fastening system for securement to a solid substrate. 1" Snap-Lock panels are produced with a nail strip to eliminate the use of clips and allows the panel seams to interlock without having to use a mechanical seaming device.
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; also used for roof replacement (retrofit) application.
- 1.3 DELIVERY, STORAGE AND HANDLING
- .1 Protect against damage and discoloration.
- .2 Handle panels with non-marring slings.
- .3 Do not bend panels.
- .4 Store panels above ground, with one end elevated for drainage.
- .5 Protect panels against standing water and condensation between adjacent surfaces.
- .6 If panels become wet, immediately separate sheets, wipe dry with clean cloth, allow to air dry.
- PART 2 - PRODUCTS
- 2.1 FABRICATION
- .1 Unless otherwise shown on drawings or specified herein, fabricate panels in continuous one piece lengths and fabricate flashings and accessories in longest practical lengths.
- .2 Roofing panels shall be factory formed. Field formed panels are not acceptable.
- 2.2 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in Section 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.
- PART 3 - EXECUTION
- 3.1 EXAMINATION - EXISTING CONDITIONS
- .1 Verify that structural deck to receive panels is complete, in true plane, secure and otherwise properly prepared.
- .2 Prior to starting work, notify General Contractor about defects requiring correction.
- .3 Do not start work until conditions are satisfactory.
- 3.2 PREPARATION - FIELD MEASUREMENTS
- .1 Verify prior to fabrication.
- .2 If field measurements differ from drawing dimensions, notify Architect / Professional Engineer prior to fabrication.
- 3.3 PROTECTION
- .1 Treat, or isolate with protective material, any contacting surfaces of dissimilar materials to prevent electrolytic corrosion.
Manufacturer: ALPHA ROOFING & SHEET METAL INC.
Contact Address: See Membership List in Section 1.
Product Group: STANDING SEAM METAL ROOF SYSTEM – SCHLEBACH QUADRO Standing Seam System
- DESCRIPTION
The Schlebach Quadro Panel Machine is an on-site/in-shop continuous metal roofing and soffit panel roll forming machine. This machine produces 25 mm (1")and 38 mm (1.5") seam heights in Snap lock, Nail strip and 25 mm (1") and 38 mm (1.5") and 50 mm (2") seam heights in Mechanical Lock profiles. Panels can be produced in widths from 225 mm (9") wide to 500 mm (20") wide.
On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to 46 m (150').
- 1.1 GENERAL
The roofing assembly / material information published in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.
- 1.2 SYSTEM DESCRIPTION
- .1 Standing seam panels utilize a hidden fastening clip system for mechanical fastening to a solid substrate. The maximum spacing of the clips in the snap lock or mechanically locked system is 600 mm OC (24"). The panels are locked together with the clips as part of the seam, by use of friction in the case of the Snap lock profiles, or by use of a mechanical seamer in the case of the mechanically locked profiles..
- .2 Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction. This product is acceptable for re-roofing or new construction applications.
- .3 Panel Attachment:
- Fasteners (Screws)
- Fasteners used to attach panel nail strip or clips to plywood to be No. 10 by min 25 mm (1") pancake head, No. 2 Phillips drive, A-point, coated steel screw. Minimum two fasteners per clip to be used.
- Roof Deck Fasteners (Panel Clips)
- One piece assembly 43.75 mm (1-3/4") wide, heights to suit seam height as per manufacturer's requirements. Minimum clip thickness 0.022" (No. 22 MSG). Clips spaced maximum 600 mm (24") on centre fastened to plywood or steel deck. Minimum of two fasteners used Schlebach / Quadro Fixed Clip.
- Two piece assembly to be used for longer panel lengths, clip to be Schlebach approved 22 ga, 87.5 mm (3-1/2") wide by appropriate height to suit seam height chosen. One panel clip spaced a min. of maximum of 600 mm (24") OC.
- 1.3 SITE CONDITIONS
- .1 Minimum roof slope is 1:6 (2" in 12"). Contact manufacturer for installation practice in extreme weather areas.
- 1.4 PERFORMANCE REQUIREMENTS
- .1 Wind Uplift Standards:
- National Research Council (NRC-CNRC) Report No.B1040 Wind Uplift Resistance of Metal Roofing. The NRC-CNRC Report No. B1040 test results confirm that an acceptable level of wind uplift resistance can be achieved with RGC Accepted Metal Panel Systems on typical roof designs over solid decking for most British Columbia geographical locations. Refer to Appendix II for calculations for typical roof wind uplift pressure requirements for buildings located in the Province of British Columbia.
- A simplified design procedure developed by NRC-CNRC for selecting wind pressure calculations for metal roof assemblies by region (location) and building height in the Province of British Columbia is provided in Section 8.1.5 to assist designers.
- RGC accepted metal panel systems shall be formed of steel conforming to one of the following material specifications, as applicable:
- ASTM Standard Specification A653 / A653M, Sheet Steel, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed) by the hot dip process, minimum Grade 33, with a design thickness of 24 gauge. (0.024") or greater and a minimum zinc coating designation Z275 (G-90).
- ASTM Standard Specification A792 / A792M, Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process, minimum Grade 33, with a design thickness of 24 gauge (0.024") or greater and minimum coating designation AZ150.