WP Details:F1.7.9 (Walls - Reglet & Counter-Flashings)

Jump to: navigation, search

WP Details:F1.7.9 (Walls - Reglet & Counter-Flashings)

Revision as of 20:09, 25 October 2016 by James Klassen (talk | contribs)
RoofStar Guarantee Standards are blue-linked
Waterproofing Details for Plazas, Promenades and Terraces

9.6.9.jpg

1 WORK INCLUDED

(1) Primary Waterproofing Membrane: Fully adhered to acceptable substrates (concrete slab depicted), installed as per RoofStar Guarantee Standards for Waterproofing Plazas, Promenades & Terraces and Membrane Manufacturer's installation specifications.

(2) Membrane Flashing (stripping): Carried up walls a minimum 200 mm (8") above membrane surface (Deck) and a minimum of 100mm (4") above top surface of permeable waterproofing wearing surfaces and overburdens.

(3) Membrane Primer or Adhesive: proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications.

(4) Metal Base Flashing: Required on all waterproofing assemblies flashing lengths joined by use of S-locks or standing seam joints.

(5) Metal Counter Flashing: Set in reglet fastened with expanding type concrete pins, join flashing lengths by use of S-locks or standing seam joints.

(6) Fasteners: Suitable expanding type concrete pins.

(7) Caulking: Polyurethane sealant, fill void and tool smooth.

2 RELATED WORK BY OTHERS

(A) Concrete Wall: Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required).

(B) Reglet: Minimum 75mm (3/4") in depth, saw cut or manufactured preformed reglet.

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.



RoofStar Guarantee Standards for Waterproofing Plazas, Promenades & Terraces

Back to Waterproofing Construction Details

Back to Construction Details