Template:Part 8 (Waterproofing Roofs - SBS)
Template:Part 8 (Waterproofing Roofs - SBS)
Revision as of 15:31, 15 July 2020 by James Klassen (talk | contribs)
1 General
- Insulation overlay boards are installed in most conventionally insulated roof assemblies to
- protect heat-sensitive insulation materials from damage by heat and flame.
- protect insulation materials from accidental impact.
- provide dimensional stability to the roof system.
- distribute dead loads from heavy overburdens or equipment installed on top of the finished roof assembly.
- ensure the membrane performs as it should.
- provide a suitable substrate for membrane application.
- Insulation overlay boards may be mechanically attached or adhered, depending upon the insulation type and the design requirements of the roof assembly as a whole. See more information on Insulation Joints and Overlays in Essential Elements.
1.1 Design
1.1.1 RoofStar 15-Year Guarantee
- An insulation overlay is required for all insulated systems, regardless of the insulation type, and overlays must
- be at least 6.4 mm (1/4”) thick.
- possess a compressive strength of at least 690 kPa (100 psi).
1.1.2 All Projects
- Notwithstanding the requirements in Part 7 concerning heat-sensitive insulation, an insulation overlay of one or more layers is required over all flat and sloped board-type insulation, and on insulation installed on vertical surfaces, when
- the compressive strength of the insulation is less than 110 KPa (20 psi).
- the membrane is self-adhered or will be applied with a torch flame, adhesives or hot bitumen.
- a conventionally insulated roof assembly supports an overburden; these roof systems must be designed with at least one layer of adhered composite insulation overlay
- no less than 12.7 mm (½") thick.
- with a minimum compressive strength of 620 kPa (90 psi).
- The requirement to use an insulation overlay does not apply to the field application of
- self-adhered membranes
- expressly accepted by the RGC for application directly on specific insulation types without the use of an overlay.
- expressly approved (in published literature) by the manufacturer for application directly on an insulation panel.
- torch-applied membranes installed directly on mineral fibre insulation treated with a thermofusible bitumen top surface. This exception is subject to the standards for mineral wool insulation published in Part 7 INSULATION.
- self-adhered membranes
- When an overlay board is required over mineral wool insulation, the overlay board must be a moisture resistant gypsum core board measuring at least 12.7 mm (1/2") thick. See also 7.2 concerning Mineral Wool Insulation.
- Heat-sensitive crickets used in membrane systems applied with a torch flame or hot bitumen must be overlaid using either of the following approaches:
- one layer of panels,
- at least 12.5 mm (1/2”) thick.
- offset from insulation joints by at least 300 mm (12”).
- continuously sealed with a flame-impervious tape along all joints with adjacent panels.
- two layers of panels,
- each at least 4.8 mm (3/16”) thick.
- offset from each other, from the adjacent layer, and from insulation joints by at least 300 mm (12”).
See also 14.1.2.1 General. - one layer of panels,
2 Materials
See Insulation Overlays accepted for use in RoofStar Guaranteed roof systems.
Table 8.1 Insulation Overlay Minimum Thicknesses Material Minimum Thickness - mm (in.) Asphaltic core board 4.8 (3/16") Moisture-resistant gypsum core board 6.4 (1/4") High-density Insulation Board 12.7 (1/2") Composite and Laminated Overlay Board 6.4 (1/4") Fibreboard As listed in this Manual Membrane-laminated overlays As listed in this Manual Mineral wool As listed in this Manual
- Regardless of the type of insulation overlay, the overall thickness of insulation overlay boards shall not exceed 50 mm (2”). Minimum allowable thicknesses are shown in Table 8.1 above.
- Asphalt-coated fibreboard roof insulation adhered with hot asphalt or an asphalt-based adhesive must be asphalt-coated on the top and bottom surface (minimum coated two-sides).
- Fire guard tape must be 150 mm (6”) wide
- self-adhering modified bituminous tape acceptable to the membrane manufacturer.
- Type IV fibreglass felt or No. 15 organic felt, applied with hot bitumen or cold adhesive.
3 Application
3.1 General
3.1.1 RoofStar 15-Year Guarantee
- See the requirements for a RoofStar 15-Year Guarantee in 8.1.1.1.
3.1.2 All Projects
- See the Design requirements in 8.1.1 Design.
- Fibreboard shall not be used as an insulation overlay beneath torch-applied membranes.
- Insulation overlays
- should be square and should make firm, full contact with adjacent panels unless specified otherwise by the manufacturer.
- must be offset at least 300 mm (12") from the joints of the insulation layer; a minus offset tolerance of 50 mm (2") maximum is permissible.
- When multiple layers of an insulation overlay are specified, the joints between boards must be offset/staggered at least 300 mm (12") from adjacent layers and rows. See Figure 8.1. See also Part 7 INSULATION.
Figure 8.1
- Mechanical securement:
- When mechanically attaching insulation overlay boards, the insulation and overlay boards may be fastened together as one assembly. Unless otherwise indicated by the system requirements in a Tested Assembly, follow the fastener patterns set out in Part 3 SECURING the ROOF ASSEMBLY.
- When a composite overlay with an integrated base membrane is mechanically fastened over insulation, fasteners and plates used in the field of each panel must be covered with torch-applied polyester or composite-reinforced membrane patches that extend past the edge of each plate at least 50 mm (2”).
- Adhered securement:
- Adhered composite or moisture resistant gypsum core board overlays measuring at least 12.7 mm (1/2") thick must be used when
- conventionally insulated roof assemblies support an overburden (overlays must provide compressive strength of at least 620 kPa (90 psi).
- mandated by the standards for mineral wool insulation (see 7.1.1.2(11)). See also Part 14 The ROOF as a PLATFORM for design and construction standards.
- Roof system components adhered with two-component low-rise polyurethane foam must be
- installed immediately in wet adhesive (before a surface skin develops) applied
- in parallel runs or in a Z-pattern, no more than 150 mm (6”) from any edge of the board and spaced no more than 300 mm (12”) apart.
- to a clean, dry and contaminant-free surface.
- in ribbon widths specified by the adhesive manufacturer or, in the absence of manufacturer requirements, 19 mm (3/4”) wide.
- properly placed and weighted in wet adhesive until cured.
- installed immediately in wet adhesive (before a surface skin develops) applied
- Hot bitumen used to adhere a roof assembly
- must be applied at minimum rates and temperatures based on the type of product, as published by the material manufacturer and in the RoofStar Guarantee Standards for Built-up Roof (BUR) Systems.
- may be applied on slopes up to 1/2:12 (for steeper slopes, select a different method of securement).
- Adhered composite or moisture resistant gypsum core board overlays measuring at least 12.7 mm (1/2") thick must be used when