Asphalt Shingles - Intersection with Waterproofing Roof (Lower)

Jump to: navigation, search

Asphalt Shingles - Intersection with Waterproofing Roof (Lower)

RoofStar Guarantee Standards are blue-linked
Asphalt Shingle Details
Click on any image to expand it
link=http://rpm.rcabc.org/images/e/ef/ASh 10.7.2-1 CD.jpg
link=http://rpm.rcabc.org/images/e/ed/ASh 10.7.2-2 CD.jpg

1 WORK INCLUDED

(1) Underlayment
Required, and installed to overlap the Valley Protection Membrane and the Valley Metal Flashing. Install ‘shingle-style’, following the requirements for side and end laps; use acceptable fasteners, or adhere (if a self-adhering membrane) in keeping with the manufacturer’s published requirements.
(2) Shingles (field)
(3) Field Shingles
Fasteners used to secure shingles must be at least 300 mm (12") above the finished surface of the roof waterproofing system.
(4) Field Membrane
Secure membrane to water-shedding roof deck at least 300 mm (12") above the finished surface of the roof waterproofing (refer to the related Membrane Standards, Part 9 FIELD MEMBRANE and Part 10 PERIMETERS and WALLS).

2 RELATED WORK BY OTHERS

(A) Acceptable Deck

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.



Standard for Asphalt Shingle Systems

Back to Asphalt Shingles Construction Details

Back to Construction Details