Asphalt Shingles - Application (Common and Steep Slopes)
Asphalt Shingles - Application (Common and Steep Slopes)
Revision as of 15:50, 31 August 2021 by James Klassen (talk | contribs)
Notice to Reader | |
Images used in a Construction Detail are representative and not prescriptive. Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the requirements of the Standard they represent. Unless otherwise required by the Standard, dimensions, the selection of materials and their application remains the responsibility of the Design Authority. The full text of the referenced requirements in the Standard may be read by using the blue hyperlinks |
Asphalt Shingle Details
1 WORK INCLUDED
- (1) Eave Protection
- One ply of self-adhered modified bituminous underlayment material or other acceptable eaves protection. Lap 75 mm (3") minimum on sides and 150 mm (6") minimum on ends.
- (2) Underlayment
- Minimum one ply of No. 15 non-perforated asphalt saturated felt or accepted eaves protection. Overlap 50 mm (2") minimum on side laps and 150 mm (6") minimum on end laps.
- (3) Edge Metal Flashing
- Required for all eave and rake edges.
- (4) Starter Course
- Standard strip, laminated or architectural shingle starter course consists of proprietary starter shingles or (in the case of strip shingles) the same type shingles used in the field. Install according to requirements in Subsection 9.3.1 General, together with the Manufacturer's printed application instructions.
- (5) Standard Strip, Laminated or Architectural Shingles
- Applied as recommended by manufacturer.
- (6) Nailing
- See the requirements in Section 3.3 Application.
2 RELATED WORK BY OTHERS
- (A) Acceptable Deck
NOTE: See the Standard for additional requirements.
Back to Asphalt Shingle System Details