SBS Fall Protection Anchor in Roof
SBS Fall Protection Anchor in Roof
Division D - Construction Details
SBS | Fall Protection Anchor in Roof ( Article 12.3.2.1.)
Notice to Reader | |
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).
The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text. |
SBS Details
1 WORK INCLUDED
- (1) Flashing
- 0.08 mm (0.032", 20 gauge) Aluminum or 0.56 mm (16 oz) copper to CSA B272-93 flashing supplied by anchor manufacturer with flanges sealed by roofer.
- (2) Flashing Flange
- minimum 100 mm (4") flange set in coating of compatible sealant.
- (3) Primary Membrane and Membrane Flashing.
- (4) Protected Membrane Roof Assembly
- Flashing to extend a minimum 200 mm (8") above finished roof surface (pavers, ballast, or walkways). See [[SBS Roof Systems Standard#PART_12 | 12.1.3.2 Membranes for specific Application requirements.
- (5) Conventional Roof Assembly
- Flashing to extend a minimum 200 mm (8") above finished roof surface. See membrane flashing requirements under 10.3 Application.
- (6) Insulation
- See available insulation products in the Accepted Materials Division of this Manual.
2 WORK BY OTHERS
- (A) Acceptable Supporting Deck Structure
- Concrete slab shown, see anchor manufacturer's attachment details for other deck types.
- (B) Roof Anchor
- Anchor selection and attachment details are the responsibility of the Design Authority
- (C) Anchor Eye
- (D) Water Tight Cap
NOTE: See the Standard for additional requirements.
Back to "SBS" Roof System Details