SBS Fall Protection Anchor in Roof

Jump to: navigation, search

SBS Fall Protection Anchor in Roof

Revision as of 16:16, 19 July 2016 by James Klassen (talk | contribs) (Created page with "File:10.3.7.1.jpg === WORK INCLUDED === (1) <b>Flashing</b>: 0.08 mm (0.032", 20 gauge) Aluminum or 0.56 mm (16 oz) copper to CSA B272-93 flashing supplied by anchor manu...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)

10.3.7.1.jpg

1 WORK INCLUDED

(1) Flashing: 0.08 mm (0.032", 20 gauge) Aluminum or 0.56 mm (16 oz) copper to CSA B272-93 flashing supplied by anchor manufacturer with flanges sealed by roofer.

(2) Flashing Flange: minimum 100 mm (4") flange set in coating of compatible sealant.

(3) Membrane Flashing / Stripping & Primary Membrane

(4) Protected Membrane Roof Assembly: Flashing to extend a minimum 200 mm (8") above finished roof surface (pavers, ballast, or walkways)

(5) Conventional Roof Assembly: Flashing to extend a minimum 200 mm (8") above finished roof surface.

(6) Insulation

2 WORK BY OTHERS

(A) Acceptable Deck: Concrete slab shown, see anchor manufacturer’s attachment details for other deck types.

(B) Roof Anchor to CSA Z91-M90

(C) Anchor Eye to CSA Z91-M90

(D) Water Tight Cap


NOTE: Refer to RGC Guarantee Standards for additional requirements.