Carlisle EPDM Membrane Installation Guidelines

Jump to: navigation, search

Carlisle EPDM Membrane Installation Guidelines

Notice to the Reader:

The instructions provided below are reprinted from the manufacturer's own materials which were submitted to the RoofStar Guarantee Program for inclusion in this Manual. The reader is urged to check these against current publications issued by the manufacturer, to ensure accuracy.

Manufacturer: CARLISLE SYNTEC SYSTEMS CANADA

Contact Address: See Membership List in Section 1.

Product Group: EPDM MEMBRANE

Country of Origin: U.S.A.

Country of Manufacture: U.S.A.

Year First Installed
B.C.: 1972
Canada: 1968
U.S.A.: 1964

1 Description

Sure-Seal EPDM (ethylene, propylene, diene monomer) elastomeric membrane is the key component used in Carlisle roofing and waterproofing systems. The membrane is applied in large sheets to reduce field seams. Exceptional long-term elasticity permits the material to withstand normal building movement without cracking or tearing. It can withstand severe temperature fluctuations and prolonged ozone exposure and remain ultraviolet-stable under constant exposure to intense sunlight. The membrane is available in black or white on black, reinforced or non-reinforced depending on the type of application.

Sure-Seal EPDM is manufactured in standard widths up to 15.24 m (50') and standard lengths up to 60.96 m (200'). Standard thicknesses are 1.11 mm (0.045") and 1.52 mm (0.060"). Special sizes and thicknesses are also available. Material properties and seam strength all exceeds the CGSB 37-GP-52M standards.

1.1 GENERAL

The roofing assembly / material information published in the RCABC Roofing Practices Manual does NOT represent a complete set of the Manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority.

SYSTEM DESCRIPTIONS/RANGE OF APPLICATION

  1. Use in commercial, institutional, and industrial construction.
  2. Used in new construction and reroofing of existing roofs.
  3. Roofing applications include: Design “A”, the Fully Adhered Roofing System; Design “B”, the Ballasted Roofing System; Design “C”, the Inverted Membrane Ballasted Roofing System; the Mechanically Attached Roofing System; and the Mechanically-Fastened Roofing System.
  4. Waterproofing systems can be applied to horizontal or vertical surfaces.


DELIVERY, STORAGE AND HANDLING

  1. Deliver and store materials in original package and containers with manufacturer's name, brand name and installation instructions intact.
  2. All materials, except membrane must be stored between +15.5°C (+60°F) and 26.5°C (+80°F).


SITE CONDITIONS (CAUTIONS AND WARNINGS)

  1. Prior to the use of any product, consult the manufacturer's safety data bulletin for application cautions and warnings.
  2. Do not use bitumen-based roof cement.
  3. Do not install EPDM membrane directly onto low melting point asphalt (CSA A123.4-M1979, Type 1 or 2).
  4. Do not allow waste products (petroleum, grease, oil, solvents, vegetable or mineral oil, animal fats, etc.) or direct steam venting to come in contact with Sure-Seal Roofing System.


STANDARDS AND APPROVALS

(For specific membrane or assembly consult Carlisle SynTec Systems Canada)
  1. Canadian General Standard Board: CGSB 37-GP-52M.
  2. Underwriters Laboratories of Canada: Listed.
  3. Underwriters Laboratories: Listed.
  4. Factory Mutual: Various approvals listed.
  5. Canadian Mortgage and Housing: CMHC No. 10473.


MANUFACTURER'S SERVICES

  1. Technical Services: applicator training, technical seminars, field training, field inspections, and technical assistance are available.
  2. Specifications / Drawings: Systems Design and Review group to respond to daily design inquiries.


1.2 MATERIALS

NOTE: Regardless of the materials listed below or anywhere else in these manufacturer's guidelines, only materials accepted for use in the RoofStar Guarantee Program, or accessories associated with those materials, may be used to qualify for a RoofStar Guarantee. To see a list of the manufacturer's products accepted for use in the RoofStar Guarantee Program, click on the link above.
The components of the Sure-Seal Roofing Systems are to be products of Carlisle SynTec Systems Canada or accepted by Carlisle SynTec Systems Canada as compatible.

MEMBRANE

  1. 1.11 mm (0.045") black EPDM membrane used for the Loose-laid Ballasted System; Loose-laid Protected (IRMA) System; and Non-Penetrating Mechanically-Anchored System.
  2. 1.11 mm (0.045") black reinforced EPDM membrane used for the Sure-Seal Mechanically Fastened System.
  3. 1.11 mm (0.045") white on black reinforced EPDM membrane used for the Brite-Ply Mechanically-Fastened System.
  4. 1.52 mm (0.060") black EPDM membrane used for the Sure-Seal Fully-Adhered System and Waterproofing Systems.
  5. 1.52 mm (0.060") white on black EPDM membrane used for the Brite-Ply Fully Adhered System.


CARLISLE MEMBRANE ACCESSORIES

Flashing
EPDM Elastoform Flashing
Bonding Adhesive
90-8-30A Bonding Adhesive used to bond membrane to substrate
Splicing Cement
EP-95 Splicing Cement used for seam splices
Splice Cleaner & HP Splice Wipes
Used to clean membrane splicing areas
Lap Sealant
Used to seal seam edges
Water Cut-Off Mastic
Used for compression type water seal
Molded Pipe Flashing
Used to flash round penetrations
Nite Seal
Used for temporary termination
Pourable Sealer
Used in sealer pockets
Rubber Fastening Strip #3
Used for perimeter securement
HP Protective Mat
Protection mat used with crushed stone
EM-8 Hypalon
Colour coating for EPDM
In-Seam Sealant
Sealant applied in the splice
Seam Fastening Plate
50 mm (2") diameter metal fastening plate
Fasteners
HP Sure-Seal fasteners, toggles or concrete fasteners
NP Anchors
Membrane anchors for non-penetrating system
Roof Drains
PVC roof drains
Insulation
Compatible with membrane system

RELATED MATERIALS

  1. Ballast: rounded water-worn gravel, steel-troweled smooth-surface paver blocks and abrasive-surface paver blocks, or crushed stone underlaid with HP Protective Mat are acceptable ballast.
  2. Wood Nailers: pressure-treated with salt preservatives.
  3. Thermal Barrier: 19 mm (3/4") thick perlite or 15.9 mm (5/8") thick type “X” gypsum board may be used to provide a stable underlayment for the roofing system or to comply to code requirements.
  4. Vapour Retarder: for protection of the insulation, a vapour retarder should be considered.


1.3 EXECUTION

PREPARATION

  1. Proper decking for the substrate shall be provided to receive the Sure-Seal Roofing System.
  2. Substrates must be clean, smooth, dry, and free of fins, loose or foreign materials, oils, grease and roof cements.
  3. Ensure parapet substrates are suitable for adhering membrane flashings; where sheathing is required, plywood is strongly recommended, minimum exterior grade gypsum board (conforming to CSA A82.27-M1977) is required.
  4. Insulation must be compatible with roof membrane systems.
  5. Ensure plywood substrates are screwed (when EPDM applied directly over decks); alternatively, provide protection between nailed decks and membrane.


FULLY ADHERED MEMBRANE

  1. Position membrane and allow to relax for approximately 30 minutes.
  2. Fold sheet back exposing half of the underside; ensure fold is smooth without wrinkles or buckles.
  3. Apply bonding adhesive evenly without globs or puddles, using a 225 mm (9") wide plastic core short nap paint roller to both the sheet and the substrate.
  4. Allow adhesives to dry until tacky, but not stringy to the touch; roll coated membrane into the coated substrate, avoiding wrinkles.
  5. Brush down the bonded half of the sheet, fold back unbonded half, and repeat the bonding procedure.
  6. Do not apply bonding adhesive to the splice area.
  7. Install adjoining sheet in the same manner, overlap edges a minimum of 75 mm (3").


LOOSE-LAID MEMBRANE

  1. Unroll and position membrane, allow it to relax approximately 30 minutes prior to splicing or membrane securement.
  2. Position adjoining sheets in same manner overlapping edges a minimum of 75 mm (3 inches).


MECHANICALLY FASTENED SYSTEM

  1. Unroll and position membrane and allow it to relax approximately 1/2 hour.
  2. Secure the membrane with in-seam plates 300 mm (1' 0") on center 75 mm (3") away from the edge of the membrane.
  3. Position adjoining sheets to allow a minimum overlap of 150 mm (6").


SEAMS

  1. Fold top sheet of splice area back; clean top and bottom seam areas using splice cleaner and splice wipes or clean natural fibre rag to remove talc on membrane surface.
  2. Apply EP-95 splicing cement to both mating surfaces with medium nap roller in manner and rate specified on container.
  3. Apply a 5 mm (3/16") diameter bead of in-seam sealant 12 mm (1/2") from the edge of the bottom mating surface while splicing cement is drying.
  4. Allow cement to dry, roll top sheet onto mating surface with hand pressure.
  5. Roll splice with 50 mm (2") wide steel roller perpendicular to length of the seam.
  6. Wait at least two hours; apply lap sealant to seam edges and feather with tool provided.


MEMBRANE SECUREMENT

  1. Securement shall be provided at the perimeter of each roof level, and at any angle change where slope or combined slopes exceed 1:6 (2" in 12").
  2. Securement shall be with Rubber Fastening Strip #3 (RFS #3) and acceptable fastener.


FLASHING

  1. Complete all flashing detail and termination according to Carlisle SynTec Systems Canada details; use EPDM Elastoform where required.

2 Membrane Assemblies

2.1 Sure-Seal and Brite-Ply Adhered Roofing System (Carlisle Design “A”)

Slope Limitation: No slope restrictions.

ROOF ASSEMBLY
Components Options Comments or Cautions
Roof Deck Wood / Plywood All defects in the deck must be corrected. Membrane may be directly adhered to smooth clean concrete, wood, or plywood decks.
Concrete
Steel
Fibrous Cement / Gypsum
Thermal Barrier Perlite Perlite or gypsum board may be used to provide stable underlayment for roofing systems or to comply with code requirements.
Gypsum
Vapour Retarder Designer's Option May be required for the protection of the insulation.
Insulation Expanded polystyrene Mechanically fasten to deck. Membrane can only be fully bonded to insulation overlayment listed below.
Extruded polystyrene
Polyisocyanurate
Pre-approved alternatives
Insulation Overlay Carlisle HP Recovery Board Approved asphalt-impregnated fibreboard Mechanically fasten overlayment to deck, with minimum of one fastener every 0.185 meters squared (2 sq ft).
Plywood
Adhesive Carlisle 90-8-30A Fully bonds surface areas.
Membrane 1.52 mm (0.060") Maximum 3.05 m (10') wide, maximum 61 m (200') long
Sure-Seal EPDM or
Brite-Ply EPDM


2.2 Sure-Seal Loose-Laid Roofing System (Carlisle Design “B”)

Slope Limitation: Must not exceed 1:6 (2" in 12")

ROOF ASSEMBLY
Components Options Comments or Cautions
Roof Deck Wood / Plywood Decks must withstand loads. Steel decks require overlayment.
Concrete
Steel
Fibrous Cement / Gypsum
Thermal Barrier Perlite Perlite or gypsum board may be used to provide stable underlayment for roofing systems or to comply with code requirements.
Gypsum
Vapour Retarder Designer's Option May be required for the protection of the insulation.
Insulation Expanded polystyrene
Extruded polystyrene
Polyisocyanurate
Glass fibreboard
Pre-approved alternatives
Membrane 1.11 mm (0.045") Sure-Seal EPDM Loose-laid.
1.52 mm (0.060") Sure-Seal EPDM Loose-laid.
Ballast Gravel 38 mm (1-1/2") nominal diameter applied at 50 kg / meters squared (10 lb / sq.ft). Crushed stone requires HP protective mat.
Crushed Stone
Concrete Pavers


2.3 Sure-Seal Loose-Laid Protected Membrane Roofing System (Carlisle Design “C”)

Slope Limitation: Must not exceed 1:6 (2" in 12")

ROOF ASSEMBLY
Components Options Comments or Cautions
Roof Deck Wood / Plywood Decks must withstand loads. Steel decks require overlayment.
Concrete
Steel
Fibrous Cement / Gypsum
Thermal Barrier Perlite Perlite or gypsum board may be used to provide stable underlayment for roofing systems or to comply with code requirements.
Gypsum
Vapour Retarder Designer's Option May be required for the protection of the insulation.
Insulation Expanded polystyrene See RGC Guarantee Standards for minimum thickness.
Extruded polystyrene
Polyisocyanurate
Glass fibreboard
Pre-approved alternatives
Membrane 1.11 mm (0.045") Sure-Seal EPDM Loose-laid.
1.52 mm (0.060") Sure-Seal EPDM Loose-laid.
Insulation Above Membrane Extruded polystyrene (CGSB 51-GP-20M Type 4)
Protective Fabric HP Protective Mat Loose-laid.
Alternates approved by insulation manufacturer
Ballast Gravel 38 mm (1-1/2") nominal diameter applied at 50 kg / m² (10 lb / sq. ft) over field of roof; applied at 100 kg / m² (20 lb / sq. ft) for 1220 mm (4') wide area at perimeter, drains and penetrations.
Crushed Stone
Concrete Pavers


2.4 Brite-Ply and Sure-Seal Mechanically Fastened Roofing System

Slope Limitation: No slope restrictions.

ROOF ASSEMBLY
Components Options Comments or Cautions
Roof Deck Wood / Plywood Decks must provide required withdrawal resistance.
Concrete
Steel
Fibrous Cement / Gypsum
Thermal Barrier Perlite Perlite or gypsum board may be used to provide stable underlayment for roofing systems or to comply with code requirements.
Gypsum
Vapour Retarder Designer's Option May be required for the protection of the insulation.
Insulation Expanded polystyrene Some insulations require fibreboard overlayment as a surface to which roofing system may be fastened. Mechanically fasten insulation with minimum of one fastener and plate every 0.74 m&sup2 (8 sq ft).
Extruded polystyrene
Polyisocyanurate
Pre-approved alternatives
Membrane 1.11 mm (0.045") reinforced Sure-Seal EPDM Mechanically fastened.
1.11 mm (0.045") reinforced Brite-Ply EPDM Mechanically fastened.


2.5 FleeceBACK 100 mil (045) EPDM Membrane

Slope Limitation: Refer to the manufacturer's technical data on this product.

Note: Consult the manufacturer's Technical Data Sheet and application methods for further information.


2.6 FleeceBACK 115 mil (060) EPDM Membrane

Slope Limitation: Refer to the manufacturer's technical data on this product.

Note: Consult the manufacturer's Technical Data Sheet and application methods for further information.


2.7 FleeceBACK 145 mil (090) EPDM Membrane

Slope Limitation: Refer to the manufacturer's technical data on this product.

Note: Consult the manufacturer's Technical Data Sheet and application methods for further information.


2.8 AFX (hot mopped) 100 mil (045) EPDM Membrane

Slope Limitation: Refer to the manufacturer's technical data on this product.

Note: Consult the manufacturer's Technical Data Sheet and application methods for further information.


2.9 AFX (hot mopped) 115 mil (060) EPDM Membrane

Slope Limitation: Refer to the manufacturer's technical data on this product.

Note: Consult the manufacturer's Technical Data Sheet and application methods for further information.


2.10 Sure-Tough 075 Reinforced EPDM Membrane

Slope Limitation: Refer to the manufacturer's technical data on this product.

Note: Consult the manufacturer's Technical Data Sheet and application methods for further information.


2.11 Sure-Seal 145 mil (090) Non-reinforced EPDM Membrane

Slope Limitation: Refer to the manufacturer's technical data on this product.

Note: Consult the manufacturer's Technical Data Sheet and application methods for further information.