Difference between revisions of "Asphalt Shingles - Changes in Slope (Inside Angle)"
Difference between revisions of "Asphalt Shingles - Changes in Slope (Inside Angle)"
(→WORK INCLUDED) |
(→WORK INCLUDED) |
||
Line 17: | Line 17: | ||
;(2) [[RoofStar Guarantee Standards for Asphalt Shingle Systems#AShEAVES|'''Self-adhered (eave protection) Membrane''']]: Required for this slope change configuration, to seal the upper edge of the metal transition flashing. When installed, the SA membrane must overlap the metal by at least 50 mm (2”) and extend upslope past the edge of the lower slope underlayment by at least 50 mm (2”). | ;(2) [[RoofStar Guarantee Standards for Asphalt Shingle Systems#AShEAVES|'''Self-adhered (eave protection) Membrane''']]: Required for this slope change configuration, to seal the upper edge of the metal transition flashing. When installed, the SA membrane must overlap the metal by at least 50 mm (2”) and extend upslope past the edge of the lower slope underlayment by at least 50 mm (2”). | ||
;(3) [[RoofStar Guarantee Standards for Asphalt Shingle Systems#AShTRANSITIONS|'''Metal Transition Flashing''']]: The lower leg must measure at least 100 mm (4”); the upper leg should measure at least 125 mm (5”). | ;(3) [[RoofStar Guarantee Standards for Asphalt Shingle Systems#AShTRANSITIONS|'''Metal Transition Flashing''']]: The lower leg must measure at least 100 mm (4”); the upper leg should measure at least 125 mm (5”). | ||
− | ;(4) '''Clip''': | + | ;(4) '''Clip''': Optional. |
;(5) [[RoofStar Guarantee Standards for Asphalt Shingle Systems#AShFIELDAPPLICATION|'''Starter Shingle''']]: | ;(5) [[RoofStar Guarantee Standards for Asphalt Shingle Systems#AShFIELDAPPLICATION|'''Starter Shingle''']]: | ||
;(6) [[RoofStar Guarantee Standards for Asphalt Shingle Systems#AShFIELDAPPLICATION|'''Shingle''']]: | ;(6) [[RoofStar Guarantee Standards for Asphalt Shingle Systems#AShFIELDAPPLICATION|'''Shingle''']]: |
Revision as of 22:45, 23 October 2019
RoofStar Guarantee Standards are blue-linked |
Asphalt Shingle Details
1 WORK INCLUDED
- (1) Underlayment
- Underlayment on the upper slope must overlap the metal transition flashing and lower slope underlayment.
- (2) Self-adhered (eave protection) Membrane
- Required for this slope change configuration, to seal the upper edge of the metal transition flashing. When installed, the SA membrane must overlap the metal by at least 50 mm (2”) and extend upslope past the edge of the lower slope underlayment by at least 50 mm (2”).
- (3) Metal Transition Flashing
- The lower leg must measure at least 100 mm (4”); the upper leg should measure at least 125 mm (5”).
- (4) Clip
- Optional.
- (5) Starter Shingle
- (6) Shingle
2 RELATED WORK BY OTHERS
- (A) Acceptable Deck
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.
RoofStar Guarantee Standards for Asphalt Shingle Systems