<big><big>Division D - Construction Details</big></big>
 
<hr>
 
<hr>
[[File:7.1.5.10.jpg]]
+
<big><big><big><big><big>Asphalt Shingles | Curb Flashing (Typical) ([[Asphalt_Shingle_Systems_Standard#12.3.2.4. Curbs | Article 12.3.2.4.]])</big></big></big></big></big>
<hr>
+
{{Template:Construction Details Header}}
 
+
<div class="panel panel-success">
 +
<div class="panel-heading"><big>'''Asphalt Shingle Details'''</big></div>
 +
<div class="panel-body">
 +
<div class="col-md-6">
 +
<div style="text-align:center; vertical-align:center">
 +
[[File:7.1.5.10.jpg| link=http://rpm.rcabc.org/images/3/37/7.1.5.10.jpg | class=img-responsive]]
 +
</div>
 +
</div><!-- COL-MD-6 -->
  
 +
<div class="col-md-6">
 
=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
 +
;(1) '''Asphalt Shingles''': Installed to manufacturer&#8217;s published instructions and '''''RoofStar Guarantee Standards'''''.
 +
;(2) [[Asphalt Shingle Systems Standard#AShPART11-APRON|'''Apron Flashing''']]
 +
: Extended a minimum 100mm (4") beyond corners, interwoven with shingles and step flashings.
 +
;(3) [[Asphalt Shingle Systems Standard#AShPART11-STEP|'''Step Flashing''']]: Interwoven with each course of shingles, 75mm (3") head lap.
 +
;(4) '''Final Step flashing''': Extended around corner of the upstand and under back pan flashing. The upstand fold can alternatively be turned outward under the back pan fold.
 +
;(5) [[Asphalt Shingle Systems Standard#AShPART11-BACKPAN|'''Backpan Flashing''']]: The back-pan is to be extended 100mm (4") beyond the corner and folded. Apply caulking at the transition corner of the final step flashing and back pan.
 +
;(6) '''Capillary Section''': A capillary tab is to be extended off the end of the back pan to lead water around the corner.
  
(1) <b>Asphalt Shingles</b>: Installed to manufacturer&#8217;s published instructions and RGC Guarantee Standards.
+
*Proprietary soldered or welded diverter flashing may be used provided they conform to '''''RoofStar Guarantee Standards'''''.
 
+
</div><!-- COL-6-MD -->
(2) <b>Apron Flashing</b>: Extended a minimum 100mm (4") beyond corners, interwoven with shingles and step flashings.
+
</div><!-- PANEL BODY -->
 
+
</div><!-- PANEL -->
(3) <b>Step flashings</b>: Interwoven with each course of shingles, 75mm (3") head lap.
 
 
 
(4) <b>Final Step flashing</b>: Extended around corner of the upstand and under back pan flashing. The upstand fold can alternatively be turned outward under the back pan fold.
 
 
 
(5) <b>Back Pan</b>: The back-pan is to be extended 100mm (4") beyond the corner and folded. Apply caulking at the transition corner of the final step flashing and back pan.
 
 
 
(6) <b>Capillary Section</b>: A capillary tab is to be extended off the end of the back pan to lead water around the corner.
 
 
 
;<i>NOTE</i>
 
*Refer to <i>RGC Guarantee Standards; STR AS; STR LS; </i>for additional requirements.
 
*Proprietary soldered or welded corner flashings may be used provided they conform to RGC Guarantee Standards.
 
  
 +
'''NOTE''': See the [[Asphalt Shingle Systems Standard | '''Standard''']] for additional requirements.
  
 +
<hr>
  
[[Section:E. Application: Steep Slope Roofs|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Asphalt Shingle Application'']]
+
[[Asphalt Shingle System Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Asphalt Shingle System Details'']]
  
[[Asphalt Shingles Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Asphalt Shingles Construction Details'']]
+
[[Main Page | <i class="fa fa-home fa"></i> Home]]
  
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Construction Details'']]
+
{{Tempate:RPM Page Footer with Copyright and Current Date}}

Latest revision as of 14:39, 30 June 2022



Division D - Construction Details


Asphalt Shingles | Curb Flashing (Typical) ( Article 12.3.2.4.)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).

The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text.

Asphalt Shingle Details

7.1.5.10.jpg

1 WORK INCLUDED

(1) Asphalt Shingles
Installed to manufacturer’s published instructions and RoofStar Guarantee Standards.
(2) Apron Flashing
Extended a minimum 100mm (4") beyond corners, interwoven with shingles and step flashings.
(3) Step Flashing
Interwoven with each course of shingles, 75mm (3") head lap.
(4) Final Step flashing
Extended around corner of the upstand and under back pan flashing. The upstand fold can alternatively be turned outward under the back pan fold.
(5) Backpan Flashing
The back-pan is to be extended 100mm (4") beyond the corner and folded. Apply caulking at the transition corner of the final step flashing and back pan.
(6) Capillary Section
A capillary tab is to be extended off the end of the back pan to lead water around the corner.
  • Proprietary soldered or welded diverter flashing may be used provided they conform to RoofStar Guarantee Standards.

NOTE: See the Standard for additional requirements.