=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
 +
;(1) '''Asphalt Shingles''': Installed to manufacturer&#8217;s published instructions and RGC Guarantee Standards.
 +
;(2) [[RoofStar Guarantee Standards for Asphalt Shingles Roof Systems#ASPROTRUSIONS|'''Apron Flashing''']]
 +
: Extended a minimum 100mm (4") beyond corners, interwoven with shingles and step flashings.
 +
;(3) [[RoofStar Guarantee Standards for Asphalt Shingles Roof Systems#ASPROTRUSIONS|'''Step Flashing''']]: Interwoven with each course of shingles, 75mm (3") head lap.
 +
;(4) '''Final Step flashing''': Extended around corner of the upstand and under back pan flashing. The upstand fold can alternatively be turned outward under the back pan fold.
 +
;(5) [[RoofStar Guarantee Standards for Asphalt Shingles Roof Systems#ASPROTRUSIONS|'''Backpan Flashing''']]: The back-pan is to be extended 100mm (4") beyond the corner and folded. Apply caulking at the transition corner of the final step flashing and back pan.
 +
;(6) '''Capillary Section''': A capillary tab is to be extended off the end of the back pan to lead water around the corner.
  
(1) <b>Asphalt Shingles</b>: Installed to manufacturer&#8217;s published instructions and RGC Guarantee Standards.
+
*Proprietary soldered or welded diverter flashing may be used provided they conform to RGC Guarantee Standards.
  
(2) <b>Apron Flashing</b>: Extended a minimum 100mm (4") beyond corners, interwoven with shingles and step flashings.
+
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements.
  
(3) <b>Step flashings</b>: Interwoven with each course of shingles, 75mm (3") head lap.
 
  
(4) <b>Final Step flashing</b>: Extended around corner of the upstand and under back pan flashing. The upstand fold can alternatively be turned outward under the back pan fold.
+
<hr>
 
 
(5) <b>Back Pan</b>: The back-pan is to be extended 100mm (4") beyond the corner and folded. Apply caulking at the transition corner of the final step flashing and back pan.
 
 
 
(6) <b>Capillary Section</b>: A capillary tab is to be extended off the end of the back pan to lead water around the corner.
 
 
 
;<i>NOTE</i>
 
*Refer to <i>RGC Guarantee Standards; STR AS; STR LS; </i>for additional requirements.
 
*Proprietary soldered or welded corner flashings may be used provided they conform to RGC Guarantee Standards.
 
  
  
  
[[Section:E. Application: Steep Slope Roofs|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Asphalt Shingle Application'']]
+
[[Section:E. Application: Steep Slope Roofs|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Asphalt Shingle Application'']]
  
[[Asphalt Shingles Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Asphalt Shingles Construction Details'']]
+
[[Asphalt Shingles Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Asphalt Shingles Construction Details'']]
  
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Construction Details'']]
+
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']]

Revision as of 16:54, 9 August 2016

7.1.5.10.jpg


WORK INCLUDED

(1) Asphalt Shingles
Installed to manufacturer’s published instructions and RGC Guarantee Standards.
(2) Apron Flashing
Extended a minimum 100mm (4") beyond corners, interwoven with shingles and step flashings.
(3) Step Flashing
Interwoven with each course of shingles, 75mm (3") head lap.
(4) Final Step flashing
Extended around corner of the upstand and under back pan flashing. The upstand fold can alternatively be turned outward under the back pan fold.
(5) Backpan Flashing
The back-pan is to be extended 100mm (4") beyond the corner and folded. Apply caulking at the transition corner of the final step flashing and back pan.
(6) Capillary Section
A capillary tab is to be extended off the end of the back pan to lead water around the corner.
  • Proprietary soldered or welded diverter flashing may be used provided they conform to RGC Guarantee Standards.

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.