=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
 
;(1) '''Asphalt Shingles''': Installed to manufacturer&#8217;s published instructions and RGC Guarantee Standards.
 
;(1) '''Asphalt Shingles''': Installed to manufacturer&#8217;s published instructions and RGC Guarantee Standards.
Line 10: Line 17:
 
;(5) [[RoofStar Guarantee Standards for Asphalt Shingles Roof Systems#ASPROTRUSIONS|'''Backpan Flashing''']]: The back-pan is to be extended 100mm (4") beyond the corner and folded. Apply caulking at the transition corner of the final step flashing and back pan.
 
;(5) [[RoofStar Guarantee Standards for Asphalt Shingles Roof Systems#ASPROTRUSIONS|'''Backpan Flashing''']]: The back-pan is to be extended 100mm (4") beyond the corner and folded. Apply caulking at the transition corner of the final step flashing and back pan.
 
;(6) '''Capillary Section''': A capillary tab is to be extended off the end of the back pan to lead water around the corner.
 
;(6) '''Capillary Section''': A capillary tab is to be extended off the end of the back pan to lead water around the corner.
 
+
</div><!-- COL-6-MD -->
 +
</div><!-- PANEL BODY -->
 +
</div><!-- PANEL -->
  
 
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements.
 
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements.

Revision as of 20:56, 19 August 2016

Asphalt Shingle Details

7.1.5.10.jpg

WORK INCLUDED

(1) Asphalt Shingles
Installed to manufacturer’s published instructions and RGC Guarantee Standards.
(2) Apron Flashing
Extended a minimum 100mm (4") beyond corners, interwoven with shingles and step flashings.
(3) Step Flashing
Interwoven with each course of shingles, 75mm (3") head lap.
(4) Final Step flashing
Extended around corner of the upstand and under back pan flashing. The upstand fold can alternatively be turned outward under the back pan fold.
(5) Backpan Flashing
The back-pan is to be extended 100mm (4") beyond the corner and folded. Apply caulking at the transition corner of the final step flashing and back pan.
(6) Capillary Section
A capillary tab is to be extended off the end of the back pan to lead water around the corner.

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.