=== WORK INCLUDED === | === WORK INCLUDED === | ||
;(1) '''Asphalt Shingles''': Installed to manufacturer’s published instructions and RGC Guarantee Standards. | ;(1) '''Asphalt Shingles''': Installed to manufacturer’s published instructions and RGC Guarantee Standards. | ||
Line 10: | Line 17: | ||
;(5) [[RoofStar Guarantee Standards for Asphalt Shingles Roof Systems#ASPROTRUSIONS|'''Backpan Flashing''']]: The back-pan is to be extended 100mm (4") beyond the corner and folded. Apply caulking at the transition corner of the final step flashing and back pan. | ;(5) [[RoofStar Guarantee Standards for Asphalt Shingles Roof Systems#ASPROTRUSIONS|'''Backpan Flashing''']]: The back-pan is to be extended 100mm (4") beyond the corner and folded. Apply caulking at the transition corner of the final step flashing and back pan. | ||
;(6) '''Capillary Section''': A capillary tab is to be extended off the end of the back pan to lead water around the corner. | ;(6) '''Capillary Section''': A capillary tab is to be extended off the end of the back pan to lead water around the corner. | ||
− | + | </div><!-- COL-6-MD --> | |
+ | </div><!-- PANEL BODY --> | ||
+ | </div><!-- PANEL --> | ||
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements. | '''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements. |
Revision as of 20:56, 19 August 2016
Asphalt Shingle Details
WORK INCLUDED
- (1) Asphalt Shingles
- Installed to manufacturer’s published instructions and RGC Guarantee Standards.
- (2) Apron Flashing
- Extended a minimum 100mm (4") beyond corners, interwoven with shingles and step flashings.
- (3) Step Flashing
- Interwoven with each course of shingles, 75mm (3") head lap.
- (4) Final Step flashing
- Extended around corner of the upstand and under back pan flashing. The upstand fold can alternatively be turned outward under the back pan fold.
- (5) Backpan Flashing
- The back-pan is to be extended 100mm (4") beyond the corner and folded. Apply caulking at the transition corner of the final step flashing and back pan.
- (6) Capillary Section
- A capillary tab is to be extended off the end of the back pan to lead water around the corner.
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.
- Proprietary soldered or welded diverter flashing may be used provided they conform to RoofStar Guarantee Standards.
Back to Asphalt Shingle Application