Draft CD 3

Jump to: navigation, search

Draft CD 3

Revision as of 16:25, 2 October 2020 by James Klassen (talk | contribs) (WORK INCLUDED)
Notice to Reader
Images used in a Construction Detail are representative and not intended in their representation of an assembly to be prescriptive. Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the Standards, Guiding Principles and Recommendations of the RoofStar Guarantee Standards for a Waterproofing or Water-shedding System. Actual design with respect to dimensions, the selection of materials and their application remains the responsibility of the Design Authority.

The full text of applicable RoofStar Guarantee Standards may be read by using the blue hyperlinks
SBS Details

ASM 10.1.1 Eave and Rake Flashing (Mechanical Seam).jpg


Click below for a printable version of this page.
Print Sheet

1 WORK INCLUDED

(1) Separation membrane, applied above deck and beneath metal eave flashing
(2) Hook securement strip.
(3) Eave metal flashing.
(4) Eave Protection
One ply of self-adhered modified bituminous underlayment material. Lap 50 mm (2") minimum on sides and 100 mm (4") minimum on ends.
(5) Underlayment
Applicable to roof slopes 1:3 or greater. For slopes less than 1:3, the entire roof slope must be covered with a self-adhered underlayment.


Architectural Metal Roof Panel

(2) Ventilation Layer
Recommended over asphaltic underlays and / or as required by metal roof panel manufacturer.
(3) Underlayment
The type of underlay required is determined by roof slope.
(4) Metal Panel Clip
Installed to metal roof panel manufacturer’s printed instructions.
(4) Architectural Metal Roof Panel
(5) Eave Protection
One ply of self-adhered modified bituminous underlayment material. Lap 50 mm (2") minimum on sides and 100 mm (4") minimum on ends.
(6) Metal flashing underlayment/separation membrane
required for metal flashings installed on wood substrates.
(7) Edge Metal Flashing (Continuous)
(8) Continuous metal cleat

2 RELATED WORK BY OTHERS

(A) Acceptable Deck
(B) Fascia Board

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.


RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems

Back to ASM Construction Details