Difference between revisions of "WP Details:F1.7.10 (Walls - Double Surface Reglet Flashing)"
Difference between revisions of "WP Details:F1.7.10 (Walls - Double Surface Reglet Flashing)"
(→RELATED WORK BY OTHERS) |
|||
Line 3: | Line 3: | ||
− | + | === WORK INCLUDED === | |
(1)<b>Primary Waterproofing Membrane: </b>Fully adhered to acceptable substrates (concrete slab depicted), installed as per <i>RGC Guarantee Standards E </i>and Membrane Manufacturer's installation specifications. | (1)<b>Primary Waterproofing Membrane: </b>Fully adhered to acceptable substrates (concrete slab depicted), installed as per <i>RGC Guarantee Standards E </i>and Membrane Manufacturer's installation specifications. | ||
Line 18: | Line 18: | ||
− | + | === RELATED WORK BY OTHERS === | |
(A)<b>Concrete, Stone or Steel Wall Finish:</b> Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required). | (A)<b>Concrete, Stone or Steel Wall Finish:</b> Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required). |
Revision as of 22:44, 23 December 2015
1 WORK INCLUDED
(1)Primary Waterproofing Membrane: Fully adhered to acceptable substrates (concrete slab depicted), installed as per RGC Guarantee Standards E and Membrane Manufacturer's installation specifications.
(2) Membrane Flashing: Carried up wall minimum 200 mm (8") above deck surface and minimum 100 mm (4") above top of finished permeable wearing course or overburden.
(3) Primary Surface Reglet: Install as detailed with steel channel and concrete pins. Adhered membrane termination held in place by clamping pressure and pins.
(4) Fasteners: Suitable expanding type concrete pins.
(5) Clamping Bar: Steel channel with elongated holes to permit expansion/contraction, pinned into concrete at maximum 400 mm (16") o/c. Bar dimensions to be a minimum 38 mm (1 ½") wide x 12 mm (1/2") thick C-channel, formed from a minimum 22 gauge galvanized or pre-finished steel.
(6) Caulking: Polyurethane sealant, fill to top of the flashing and crown to promote drainage.(7) Surface Reglet Counter Flashing: To cover lower reglet assembly, pinned directly without a clamping bar at maximum 300 mm (12") o/c. (Interlocking hooked type assembly optional)
2 RELATED WORK BY OTHERS
(A)Concrete, Stone or Steel Wall Finish: Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required).
NOTE: * AVOID SURFACE REGLET: (wherever possible) Use preformed or saw cut REGLETS:
- Refer to RGC Guarantee Standards E for additional requirements
Back to Waterproofing Application