Difference between revisions of "WP Details:F1.7.9 (Walls - Reglet & Counter-Flashings)"
Difference between revisions of "WP Details:F1.7.9 (Walls - Reglet & Counter-Flashings)"
(→RELATED WORK BY OTHERS) |
(→WORK INCLUDED) |
||
Line 19: | Line 19: | ||
(3) <b> Membrane Primer or Adhesive: </b>proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications. | (3) <b> Membrane Primer or Adhesive: </b>proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications. | ||
− | (4) [http://{{SERVERNAME}}/index.php?title=RoofStar_Guarantee_Standards_for_Waterproofing#WPMETAL '''Metal Base Flashing''']: Required on all waterproofing assemblies flashing lengths joined by use of S-locks or standing seam joints. | + | (4) [http://{{SERVERNAME}}/index.php?title=RoofStar_Guarantee_Standards_for_Waterproofing#WPMETAL '''Metal Base Flashing''']: Required on all waterproofing assemblies flashing lengths joined by use of [[MF Details:G1.7.1 Metal Flashings (Cap Flashings - Joint Ends) | '''S-locks''']] or standing seam joints. |
(5) [http://{{SERVERNAME}}/index.php?title=RoofStar_Guarantee_Standards_for_Waterproofing#WPMETAL '''Metal Counter Flashing''']: Set in reglet fastened with expanding type concrete pins, join flashing lengths by use of S-locks or standing seam joints. | (5) [http://{{SERVERNAME}}/index.php?title=RoofStar_Guarantee_Standards_for_Waterproofing#WPMETAL '''Metal Counter Flashing''']: Set in reglet fastened with expanding type concrete pins, join flashing lengths by use of S-locks or standing seam joints. |
Revision as of 18:31, 12 October 2016
RoofStar Guarantee Standards are blue-linked |
1 WORK INCLUDED
(1) Primary Waterproofing Membrane: Fully adhered to acceptable substrates (concrete slab depicted), installed as per RoofStar Guarantee Standards for Waterproofing Plazas, Promenades & Terraces and Membrane Manufacturer's installation specifications.
(2) Membrane Flashing (stripping): Carried up walls a minimum 200 mm (8") above membrane surface (Deck) and a minimum of 100mm (4") above top surface of permeable waterproofing wearing surfaces and overburdens.
(3) Membrane Primer or Adhesive: proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications.
(4) Metal Base Flashing: Required on all waterproofing assemblies flashing lengths joined by use of S-locks or standing seam joints.
(5) Metal Counter Flashing: Set in reglet fastened with expanding type concrete pins, join flashing lengths by use of S-locks or standing seam joints.
(6) Fasteners: Suitable expanding type concrete pins.
(7) Caulking: Polyurethane sealant, fill void and tool smooth.
2 RELATED WORK BY OTHERS
(A) Concrete Wall: Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required).
(B) Reglet: Minimum 75mm (3/4") in depth, saw cut or manufactured preformed reglet.
NOTE: Refer to RoofStar Guarantee Standards for additional requirements.
Back to Waterproofing Application