==== WORK INCLUDED ====
+
<big><big>Division D - Construction Details</big></big>
 
+
<hr>
(1) <b>Primary Waterproofing Membrane: </b>Fully adhered to acceptable substrates (concrete slab depicted), installed as per <i>RGC Guarantee Standards E </i>and Membrane Manufacturer's installation specifications.
+
<big><big><big><big><big>WP Details:F1.7.9 (Walls - Reglet & Counter-Flashings)</big></big></big></big></big>
 +
{| class="wikitable" | style="color: black; background-color: orange; width: 100%;text-align:center"
 +
| colspan="2"  | <big>'''''Notice to Reader'''''</big>
 +
|-
 +
| style="color: black; background-color: #ffffcc; width: 100%;text-align:center" | Images used in a Construction Detail are representative and not prescriptive.  Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the requirements of the Standard they represent. Unless otherwise required by the Standard, dimensions, the selection of materials and their application remains the responsibility of the ''Design Authority''.<br><br>The full text of the referenced requirements in the [[Grade-level Waterproofing Standard | '''Standard''']] may be read by using the <span style="color:#6495ed">'''blue hyperlinks'''</span>
 +
|}
 +
<div class="panel panel-success">
 +
<div class="panel-heading"><big>'''Waterproofing Details for Plazas, Promenades and Terraces'''</big></div>
 +
<div class="panel-body">
 +
<div class="col-md-6">
 +
<div style="text-align:center; vertical-align:center">
 +
[[File:9.6.9.jpg| link=http://rpm.rcabc.org/images/a/a6/9.6.9.jpg | class=img-responsive]]
 +
</div>
 +
</div><!-- COL-MD-6 -->
  
(2)<b> Membrane Flashing (stripping): </b>Carried up walls a minimum 200 mm (8") above membrane surface (Deck) and a minimum of 100mm (4") above top surface of permeable waterproofing wearing surfaces and overburdens.  
+
<div class="col-md-6">
 +
=== WORK INCLUDED ===
 +
;(1) [[Grade-level Waterproofing Standard#WPMEMBRANE | '''Primary Waterproofing Membrane''']]: Fully adhered to acceptable substrates (concrete slab depicted), installed as per the Standard and Membrane Manufacturer's installation specifications.
 +
;(2) [[Grade-level Waterproofing Standard#WPSTRIPPING | '''Membrane Flashing (stripping)''']]: Carried up walls a minimum 200 mm (8") above membrane surface (Deck) and a minimum of 100mm (4") above top surface of permeable waterproofing wearing surfaces and overburdens.
 +
;(3) Membrane Primer or Adhesive: Proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications.
 +
;(4) [[Grade-level Waterproofing Standard#WPMETAL | '''Metal Base Flashing''']]: Required on all waterproofing assemblies flashing lengths joined by use of [[MF Details:G1.7.1 Metal Flashings (Cap Flashings - Joint Ends) | '''S-locks''']] or  standing seam joints.
 +
;(5) [[Grade-level Waterproofing Standard#WPMETAL | '''Metal Counter Flashing''']]: Set in reglet fastened with expanding type concrete pins, join flashing lengths by use of S-locks or standing seam joints.
 +
;(6) Fasteners: Suitable expanding type concrete pins.
 +
;(7) Caulking: Polyurethane sealant, fill void and tool smooth.
  
(3)<b> Membrane Primer or Adhesive: </b>proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications.
+
=== RELATED WORK BY OTHERS ===
 +
;(A) Concrete Wall: Must be dry, smooth and primed for membrane flashing to be adhered directly.  (Plywood or fibre-mat reinforced cement board may be required).
 +
;(B) [[Grade-level Waterproofing Standard#WPREGLET | '''Reglet''']]: Minimum 19mm (3/4") in depth, saw cut or manufactured preformed reglet.
 +
</div><!-- COL-6-MD -->
 +
</div><!-- PANEL BODY -->
 +
</div><!-- PANEL -->
  
(4)<b>Metal Base Flashing:</b> Required on all waterproofing assemblies flashing lengths joined by use of S-locks or  standing seam joints.
+
'''NOTE''': See the [[Grade-level Waterproofing Standard | '''Standard''']] for additional requirements.
 
 
(5)<b>Metal Counter Flashing:</b> Set in reglet fastened with expanding type concrete pins, join flashing lengths by use of S-locks or standing seam joints.
 
 
 
(6)<b> Fasteners: </b>Suitable expanding type concrete pins.
 
 
 
(7)<b> Caulking: </b>Polyurethane sealant, fill void and tool smooth.
 
 
 
 
 
==== RELATED WORK BY OTHERS ====
 
 
 
(A)<b>Concrete Wall:</b> Must be dry, smooth and primed for membrane flashing to be adhered directly.  (Plywood or fibre-mat reinforced cement board may be required).
 
 
 
(B)<b>Reglet: </b>minimum 75mm (3/4") in depth, saw cut or manufactured preformed reglet.
 
 
 
NOTE: Refer to<i> RGC Guarantee Standards E </i>for additional requirements.
 
  
 
<hr>
 
<hr>
  
 +
[[Grade-level Waterproofing System Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Grade-level Waterproofing Construction Details'']]
  
 +
[[Main Page | <i class="fa fa-home fa"></i> Home]]
  
[[Section:F. Application: Waterproofing Plazas, Promenades and Terraces|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Waterproofing Application'']]
+
{{Tempate:RPM Page Footer with Copyright and Current Date}}
 
 
[[Waterproofing Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Waterproofing Construction Details'']]
 
 
 
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Construction Details'']]
 

Latest revision as of 21:18, 7 September 2021



Division D - Construction Details


WP Details:F1.7.9 (Walls - Reglet & Counter-Flashings)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive. Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the requirements of the Standard they represent. Unless otherwise required by the Standard, dimensions, the selection of materials and their application remains the responsibility of the Design Authority.

The full text of the referenced requirements in the Standard may be read by using the blue hyperlinks
Waterproofing Details for Plazas, Promenades and Terraces

9.6.9.jpg

1 WORK INCLUDED

(1) Primary Waterproofing Membrane
Fully adhered to acceptable substrates (concrete slab depicted), installed as per the Standard and Membrane Manufacturer's installation specifications.
(2) Membrane Flashing (stripping)
Carried up walls a minimum 200 mm (8") above membrane surface (Deck) and a minimum of 100mm (4") above top surface of permeable waterproofing wearing surfaces and overburdens.
(3) Membrane Primer or Adhesive
Proprietary primer or adhesive, application and quantities as directed by membrane manufacturers published application specifications.
(4) Metal Base Flashing
Required on all waterproofing assemblies flashing lengths joined by use of S-locks or standing seam joints.
(5) Metal Counter Flashing
Set in reglet fastened with expanding type concrete pins, join flashing lengths by use of S-locks or standing seam joints.
(6) Fasteners
Suitable expanding type concrete pins.
(7) Caulking
Polyurethane sealant, fill void and tool smooth.

2 RELATED WORK BY OTHERS

(A) Concrete Wall
Must be dry, smooth and primed for membrane flashing to be adhered directly. (Plywood or fibre-mat reinforced cement board may be required).
(B) Reglet
Minimum 19mm (3/4") in depth, saw cut or manufactured preformed reglet.

NOTE: See the Standard for additional requirements.


Back to Grade-level Waterproofing Construction Details

Home

© RCABC 2024
No reproduction of this material, in whole or in part, is lawful without the expressed permission of the RCABC Guarantee Corp.