| | <big><big><big><big><big>SBS | Window Opening ([[SBS_Roof_Systems_Standard#10.3.4.5._Doors.2C_Windows.2C_and_Wall_Openings | Article 10.3.4.5.]])</big></big></big></big></big> | | <big><big><big><big><big>SBS | Window Opening ([[SBS_Roof_Systems_Standard#10.3.4.5._Doors.2C_Windows.2C_and_Wall_Openings | Article 10.3.4.5.]])</big></big></big></big></big> |
| − | {| class="wikitable" | style="color: black; background-color: orange; width: 100%;text-align:center" | + | {{Template:Construction Details Header}} |
| − | | colspan="2" | <big>'''''Notice to Reader'''''</big>
| |
| − | |-
| |
| − | | style="color: black; background-color: #ffffcc; width: 100%;text-align:center" | Images used in a Construction Detail are representative and not prescriptive. Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the requirements of the Standard they represent. Unless otherwise required by the Standard, dimensions, the selection of materials and their application remains the responsibility of the ''Design Authority''.<br><br>The full text of the referenced requirements in the [[SBS Roof Systems Standard | '''Standard''']] may be read by using the <span style="color:#6495ed">'''blue hyperlinks'''</span>
| |
| − | |}
| |
| − | <div class="panel panel-success">
| |
| − | <div class="panel-heading"><big>'''SBS Details'''</big></div>
| |
| − | <div class="panel-body">
| |
| − | <div class="col-md-6">
| |
| − | <div style="text-align:center; vertical-align:center">
| |
| − | [[File:10.3.3.6.jpg|link=http://rpm.rcabc.org/images/6/6f/10.3.3.6.jpg | class=img-responsive]]
| |
| − | </div>
| |
| − | </div><!-- COL-MD-6 -->
| |
| | | | |
| − | <div class="col-md-6"> | + | <big><big>{{hilite | Note: this page is currently being reviewed and revised || 2026-September-26 }}</big></big> |
| − | === WORK INCLUDED ===
| |
| − | | |
| − | ;(1) [[SBS Roof Systems Standard#PART_9|'''Primary Roof Membrane''']]: Installed per ''RoofStar Guarantee Standards''.
| |
| − | ;(2) [[SBS Roof Systems Standard#PART_10|'''Membrane Flashing''']]: Carried up walls a minimum 200 mm (8") above roof surface. At window curbs membrane flashing must be 200mm (8") in height above the top of extruded polystyrene insulation or protection/drainage layer, extended under the window mullion (fenestration assembly) and carried to the inside edge of the curb. Membrane gussets must be installed at all corners and transitions.
| |
| − | ;(3) [[SBS Roof Systems Standard#PART_11|'''Protection/Drainage Layer''']] '''- Insulation Surfacing''': Assemblies to be determined by Design Authority. Paver systems are required to have proprietary pedestals that incorporate a minimum 3mm (1/8") gap between adjacent units. See additional requirements under [[SBS Roof Systems Standard#PART_12|'''12.1 Protected and Modified Protected Membrane Roof Assemblies''']].
| |
| − | ;(4) [[SBS Roof Systems Standard#PART_13|'''Metal Wall Flashing''']]: Required on roof assemblies using gravel ballast, filter mats and drainage mediums at insulation /curb interfaces.
| |
| − | | |
| − | <hr> | |
| − | | |
| − | === WORK BY OTHERS ===
| |
| − | ;(A) [[SBS Roof Systems Standard#PART_2|'''Acceptable Supporting Deck Structure''']]: Concrete slab shown
| |
| − | ;(B) [[SBS Roof Systems Standard#PART_11|'''Supporting Curb''']]: Height varies depending on the insulation thickness and type of roof assembly.
| |
| − | ;(C) '''Metal Water Stop Flashing''': Mechanically attached to the top of the window curb. Cut flashing to fit the opening and pan fold, weld, or solder seams at all corners and mitres.
| |
| − | ;(D) '''Metal Water Stop Flashing Seam''': Overlap metal water stop joints a minimum of 150mm (6") and seal joints with two rows of structural sealant.
| |
| − | ;(E) '''Building Envelope Membrane Flashing''': Must be compatible with and overlap the roof membrane flashing. Membrane gussets must be installed at all corners and transitions.
| |
| − | ;(F) [[SBS Roof Systems Standard#PART_13|'''Metal Cap Flashing''']]: Adhere metal cap flashing to membrane flashing with a membrane compatible structural sealant. Mechanical attachment of metal flashing through the membrane flashing is not acceptable.
| |
| − | ;(G) '''Fenestration Assembly''': CAUTION - Securement fasteners <b>MUST NOT</b> penetrate the metal or membrane flashing.
| |
| − | ;(H) '''Fenestration Assembly Securement Bar''': Fasten securement bar ONLY through upper vertical leg of the window mullion (frame).
| |
| − | </div><!-- COL-6-MD -->
| |
| − | </div><!-- PANEL BODY --> | |
| − | </div><!-- PANEL --> | |
| − | | |
| − | '''NOTE''': See the [[SBS Roof Systems Standard | '''Standard''']] for additional requirements.
| |
| | | | |