The drawings contained within this section are intended to represent a variety of thermoplastic roof system applications while remaining generic with regards to manufacturers’ specific application specifications. They do not represent all possible manufacturer application roof system designs. Consult manufacturers’ specifications and RoofStar Guarantee Standards to develop a system acceptable to both the manufacturer and RGC.
+
{{Template:RPM Info}}
  
For further information about thermoplastic (TPO and PVC) membrane system designs and requirements, see '''[[TPO/PVC (Thermoplastic Membranes) Roof Systems]]'''.
+
__NONUMBEREDHEADINGS__
 +
{{DISPLAYTITLE:<span style="position: absolute; clip: rect(1px 1px 1px 1px); clip: rect(1px, 1px, 1px, 1px);">{{FULLPAGENAME}}</span>}}
 +
__NOTOC__
  
<div class="col-md-6">
+
:<big><big>Division D - Construction Details</big></big>
:[[TPO Details:D3.7.1 Assemblies (Insulated Conventional)|D3.7.1 Assemblies (Insulated Conventional)]]
+
:<hr>
:[[TPO Details:D3.7.1-1 Assemblies (Insulated Conventional)|D3.7.1-1 Assemblies (Insulated Conventional)]]
+
:<big><big><big><big><big>Construction Details for TPO Membrane Roof Systems</big></big></big></big></big>
:[[TPO Details:D3.7.3 Assemblies (Ballasted Protected Membrane)|D3.7.3 Assemblies (Ballasted Protected Membrane)]]
 
:[[TPO Details:D3.7.1-2 Assemblies (Ballasted Protected Membrane)|D3.7.1-2 Assemblies (Ballasted Protected Membrane)]]
 
:[[TPO Details:D3.7.2 Assemblies (Fully Adhered)|D3.7.2 Assemblies (Fully Adhered)]]
 
:[[TPO Details:D3.7.1-3 Assemblies (Fully Adhered)|D3.7.1-3 Assemblies (Fully Adhered)]]
 
  
:[[TPO Details:D3.7.4 Parapets & Copings (High - Wall Supported)|D3.7.4 Parapets & Copings (High - Wall Supported)(Under Construction)]]
+
<div class="col-md-2">
:[[TPO Details:D3.7.2-1 Parapets & Copings (High - Wall Supported)|D3.7.2-1 Parapets & Copings (High - Wall Supported)(Under Construction)]]
+
:[[File:TPO project (courtesy Carlisle Syntec).jpg| link=http://rpm.rcabc.org/images/5/58/TPO_project_%28courtesy_Carlisle_Syntec%29.jpg | 175 px]]
:[[TPO Details:D3.7.5 Parapets & Copings (Parapet - Wall Transition)|D3.7.5 Parapets & Copings (Parapet - Wall Transition)(Under Construction)]]
+
</div>
:[[TPO Details:D3.7.2-2 Parapets & Copings (Parapet - Wall Transition)|D3.7.2-2 Parapets & Copings (Parapet - Wall Transition)(Under Construction)]]
+
 
 +
<div class="col-md-10">
 +
:The drawings linked on this page are intended to represent a variety of TPO Membrane roof system applications while remaining generic with regards to manufacturers&#8217; specific application specifications. They do not represent all possible ''manufacturer'' application roof system designs. Consult each ''manufacturer's'' specifications and the '''''RoofStar Guarantee Standards''''' to develop a system acceptable to both the manufacturer and the '''''RoofStar Guarantee Program'''''.
  
:[[TPO Details:D3.7.6 Edges & Fascia (Cant Edge)|D3.7.6 Edges & Fascia (Cant Edge)(Under Construction)]]
+
:For further information about TPO Membrane System designs and requirements, see the '''[https://rpm.rcabc.org/index.php?title=TPO_Roof_Systems_Standard Standard for TPO Membrane Roof Systems]'''.
:[[TPO Details:D3.7.3-1 Edges & Fascia (Cant Edge)|D3.7.3-1 Edges & Fascia (Cant Edge)(Under Construction)]]
+
</div>
:[[TPO Details:D3.7.7 Edges & Fascia (Gravel Stop)|D3.7.7 Edges & Fascia (Gravel Stop)(Under Construction)]]
 
:[[TPO Details:D3.7.3-2 Edges & Fascia (Gravel Stop)|D3.7.3-2 Edges & Fascia (Gravel Stop)(Under Construction)]]
 
:[[TPO Details:D3.7.8 Edges & Fascia (Roof Edge)|D3.7.8 Edges & Fascia (Roof Edge)]]
 
:[[TPO Details:D3.7.3-3 Edges & Fascia (Roof Edge)|D3.7.3-3 Edges & Fascia (Roof Edge)]]
 
  
:[[TPO Details:D3.7.9 Counter-flashings & Reglets (Deck - Wall Supported)|D3.7.9 Counter-flashings & Reglets (Deck - Wall Supported)(Under Construction)]]
+
<div class="col-md-12">
:[[TPO Details:D3.7.4-1 Counter-flashings & Reglets (Deck - Wall Supported)|D3.7.4-1 Counter-flashings & Reglets (Deck - Wall Supported)(Under Construction)]]
 
:[[TPO Details:D3.7.10 Counter-flashings & Reglets (Deck - Unsupported by Wall)|D3.7.10 Counter-flashings & Reglets (Deck - Unsupported by Wall)(Under Construction)]]
 
:[[TPO Details:D3.7.4-2 Counter-flashings & Reglets (Deck - Unsupported by Wall)|D3.7.4-2 Counter-flashings & Reglets (Deck - Unsupported by Wall)(Under Construction)]]
 
:[[TPO Details:D3.7.11 Counter-flashings & Reglets (Stucco Wall: Re-roofing)|D3.7.11 Counter-flashings & Reglets (Stucco Wall: Re-roofing)(Under Construction)]]
 
:[[TPO Details:D3.7.4-3 Counter-flashings & Reglets (Stucco Wall: Re-roofing)|D3.7.4-3 Counter-flashings & Reglets (Stucco Wall: Re-roofing)(Under Construction)]]
 
:[[TPO Details:D3.7.12 Counter-flashings & Reglets (Stucco Wall: New)|D3.7.12 Counter-flashings & Reglets (Stucco Wall: New)(Under Construction)]]
 
:[[TPO Details:D3.7.4-4 Counter-flashings & Reglets (Stucco Wall: New)|D3.7.4-4 Counter-flashings & Reglets (Stucco Wall: New)(Under Construction)]]
 
:[[TPO Details:D3.7.13 Counter-flashings & Reglets (Double Surface Reglet)|D3.7.13 Counter-flashings & Reglets (Double Surface Reglet)(Under Construction)]]
 
:[[TPO Details:D3.7.4-5 Counter-flashings & Reglets (Double Surface Reglet)|D3.7.4-5 Counter-flashings & Reglets (Double Surface Reglet)(Under Construction)]]
 
:[[TPO Details:D3.7.14 Counter-flashings & Reglets (Low Door Sill)|D3.7.14 Counter-flashings & Reglets (Low Door Sill)(Under Construction)]]
 
:[[TPO Details:D3.7.4-6 Counter-flashings & Reglets (Low Door Sill)|D3.7.4-6 Counter-flashings & Reglets (Low Door Sill)(Under Construction)]]
 
:[[TPO Details:D3.7.15 Counter-flashings & Reglets (Window Curb)|D3.7.15 Counter-flashings & Reglets (Window Curb)(Under Construction)]]
 
:[[TPO Details:D3.7.4-7 Counter-flashings & Reglets (Window Curb)|D3.7.4-7 Counter-flashings & Reglets (Window Curb)(Under Construction)]]
 
 
</div>
 
</div>
<div class="col-md-6">
+
<div class="col-md-4">
:[[TPO Details:D3.7.16 Roof-Wall Transitions (Expansion Joint)|D3.7.16 Roof-Wall Transitions (Expansion Joint)(Under Construction)]]
+
<hr>
:[[TPO Details:D3.7.5-1 Roof-Wall Transitions (Expansion Joint)|D3.7.5-1 Roof-Wall Transitions (Expansion Joint)(Under Construction)]]
+
===Part 1 - General===
:[[TPO Details:D3.7.17 Roof-Wall Transitions (Divider/Joint)|D3.7.17 Roof-Wall Transitions (Divider/Joint)(Under Construction)]]
+
====='''Permitted Roof Systems''' ([[TPO_Roof_Systems_Standard#1.1.3.1._Permitted_Roof_Systems | Article 1.1.3.1.]])=====
:[[TPO Details:D3.7.5-2 Roof-Wall Transitions (Divider/Joint)|D3.7.5-2 Roof-Wall Transitions (Divider/Joint)(Under Construction)]]
+
<ol>
:[[TPO Details:D3.7.18 Roof-Wall Transitions (Fire Separation Joint)|D3.7.18 Roof-Wall Transitions (Fire Separation Joint)(Under Construction)]]
+
<li>[[TPO Conventionally Insulated System (Typical)| Conventionally Insulated System (Typical)]]
:[[TPO Details:D3.7.5-3 Roof-Wall Transitions (Fire Separation Joint)|D3.7.5-3 Roof-Wall Transitions (Fire Separation Joint)(Under Construction)]]
+
<li>[[TPO Conventionally Insulated System (Alternate) | Conventionally Insulated System (Alternate)]]
:[[TPO Details:D3.7.19 Roof-Wall Transitions (Fire Separation Wall)|D3.7.19 Roof-Wall Transitions (Fire Separation Wall)(Under Construction)]]
+
<li>[[TPO Protected Roof Assembly (Typical) | Protected Roof Assembly (Typical)]]
:[[TPO Details:D3.7.5-4 Roof-Wall Transitions (Fire Separation Wall)|D3.7.5-4 Roof-Wall Transitions (Fire Separation Wall)(Under Construction)]]
+
</li></ol>
  
:[[TPO Details:D3.7.20 Curbs & Sleepers (Equipment Sleeper)|D3.7.20 Curbs & Sleepers (Equipment Sleeper)(Under Construction)]]
+
===Part 6 - Air and Vapour Controls===
:[[TPO Details:D3.7.6-1 Curbs & Sleepers (Equipment Sleeper)|D3.7.6-1 Curbs & Sleepers (Equipment Sleeper)(Under Construction)]]
+
====='''Continuity and Support''' ([[TPO_Roof_Systems_Standard#6.3.2.1._Continuity_and_Support | Article 6.3.2.1.]])=====
:[[TPO Details:D3.7.21 Curbs & Sleepers (Multiple Roof Penetrations)|D3.7.21 Curbs & Sleepers (Multiple Roof Penetrations)(Under Construction)]]
+
<ol>
:[[TPO Details:D3.7.6-2 Curbs & Sleepers (Multiple Roof Penetrations)|D3.7.6-2 Curbs & Sleepers (Multiple Roof Penetrations)(Under Construction)]]
+
<li>[[TPO Air and Vapour Controls (Field) | {{hilite | Air and Vapour Controls (Field)|| 2021-February-7 }}]]
:[[TPO Details:D3.7.22 Curbs & Sleepers (Basic Curb)|D3.7.22 Curbs & Sleepers (Basic Curb)]]
+
</li></ol>
:[[TPO Details:D3.7.6-3 Curbs & Sleepers (Basic Curb)|D3.7.6-3 Curbs & Sleepers (Basic Curb)]]
 
:[[TPO Details:D3.7.23 Curbs & Sleepers (Mechanical Opening)|D3.7.23 Curbs & Sleepers (Mechanical Opening)]]
 
:[[TPO Details:D3.7.6-4 Curbs & Sleepers (Mechanical Opening)|D3.7.6-4 Curbs & Sleepers (Mechanical Opening)]]
 
:[[TPO Details:D3.7.24 Curbs & Sleepers (Pre-curb for Planters)|D3.7.24 Curbs & Sleepers (Pre-curb for Planters)(Under Construction)]]
 
:[[TPO Details:D3.7.6-5 Curbs & Sleepers (Pre-curb for Planters)|D3.7.6-5 Curbs & Sleepers (Pre-curb for Planters)(Under Construction)]]
 
  
:[[TPO Details:D3.7.25 Strip-in Flashings (Metal Plumbing)|D3.7.25 Strip-in Flashings (Metal Plumbing)(Under Construction)]]
+
===Part 10 - Perimeters and Walls===
:[[TPO Details:D3.7.7-1 Strip-in Flashings (Metal Plumbing)|D3.7.7-1 Strip-in Flashings (Metal Plumbing)(Under Construction)]]
+
====='''General Application''' ([[TPO_Roof_Systems_Standard#10.3.2.3._General_Application_Requirements_for_Perimeters_and_Walls | Article 10.3.2.3.]])=====
:[[TPO Details:D3.7.26 Strip-in Flashings (Two-part Cable)|D3.7.26 Strip-in Flashings (Two-part Cable)]]
+
<ol>
:[[TPO Details:D3.7.7-2 Strip-in Flashings (Two-part Cable)|D3.7.7-2 Strip-in Flashings (Two-part Cable)]]
+
<li>[[TPO Membrane Termination A | Membrane Termination A]]
:[[TPO Details:D3.7.27 Strip-in Flashings (Pourable Sealer Pocket)|D3.7.27 Strip-in Flashings (Pourable Sealer  Pocket)(Under Construction)]]
+
<li>[[TPO Membrane Termination B | Membrane Termination B]]
:[[TPO Details:D3.7.7-3 Strip-in Flashings (Pourable Sealer Pocket)|D3.7.7-3 Strip-in Flashings (Pourable Sealer  Pocket)(Under Construction)]]
+
<li>[[TPO Membrane Termination C | Membrane Termination C]]
 +
<li>[[TPO Membrane Termination D | Membrane Termination D]]
 +
<li>[[TPO Membrane Termination E | Membrane Termination E]]
 +
<li>[[TPO Membrane Termination F | Membrane Termination F]]
 +
</li></ol>
  
:[[TPO Details:D3.7.28 Water & Drainage (Cast Iron Drain)|D3.7.28 Water & Drainage (Cast Iron Drain)(Under Construction)]]
+
====='''Parapets''' ([[TPO_Roof_Systems_Standard#10.3.4.1._Parapets | Article 10.3.4.1.]])=====
:[[TPO Details:D3.7.8-1 Water & Drainage (Cast Iron Drain)|D3.7.8-1 Water & Drainage (Cast Iron Drain)(Under Construction)]]
+
<ol>
:[[TPO Details:D3.7.29 Water & Drainage (Spun Copper Drain)|D3.7.29 Water & Drainage (Spun Copper Drain)(Under Construction)]]
+
<li>[[TPO Parapet (Typical)| Parapet (Typical)]] - Under construction
:[[TPO Details:D3.7.8-2 Water & Drainage (Spun Copper Drain)|D3.7.8-2 Water & Drainage (Spun Copper Drain)(Under Construction)]]
+
<li>[[TPO Parapet (Independent of Roof Structure) | Parapet (Independent of Roof Structure)]] - Under construction
:[[TPO Details:D3.7.30 Water & Drainage (Clamping Spun Copper Drain)|D3.7.30 Water & Drainage (Clamping Spun Copper Drain)]]
+
<li>[[TPO Tall Parapet | Tall Parapet]] - Under construction
:[[TPO Details:D3.7.8-3 Water & Drainage (Clamping Spun Copper Drain)|D3.7.8-3 Water & Drainage (Clamping Spun Copper Drain)]]
+
<li>[[TPO Parapet-Wall Connection | Parapet-Wall Connection]] - Under construction
:[[TPO Details:D3.7.31 Water & Drainage (Open Wall Scupper)|D3.7.31 Water & Drainage (Open Wall Scupper)(Under Construction)]]
+
</li></ol>
:[[TPO Details:D3.7.8-4 Water & Drainage (Open Wall Scupper)|D3.7.8-4 Water & Drainage (Open Wall Scupper)(Under Construction)]]
+
 
:[[TPO Details:D3.7.32 Water & Drainage (Through-wall Scupper)|D3.7.32 Water & Drainage (Through-wall Scupper)(Under Construction)]]
+
====='''Low-profile Edges''' ([[TPO_Roof_Systems_Standard#10.3.4.2._Low_Profile_Edges | Article 10.3.4.2.]])=====
:[[TPO Details:D3.7.8-5 Water & Drainage (Through-wall Scupper)|D3.7.8-5 Water & Drainage (Through-wall Scupper)(Under Construction)]]
+
<ol>
 +
<li>[[TPO Metal Edge Termination| {{hilite | {{hilite | Metal Edge Termination|| 2021-February-7 }} || 2026-October-31 }}]]
 +
</li></ol>
  
:[[TPO Details:D3.7.33 Miscellaneous Penetrations (Roof Anchor)|D3.7.33 Miscellaneous Penetrations (Roof Anchor)(Under Construction)]]
 
:[[TPO Details:D3.7.9-1 Miscellaneous Penetrations (Roof Anchor)|D3.7.9-1 Miscellaneous Penetrations (Roof Anchor)(Under Construction)]]
 
:[[TPO Details:D3.7.34 Miscellaneous Penetrations (Wall Anchor - Conventional Roof Assy)|D3.7.34 Miscellaneous Penetrations (Wall Anchor - Conventional Roof Assy)(Under Construction)]]
 
:[[TPO Details:D3.7.9-2 Miscellaneous Penetrations (Wall Anchor - Conventional Roof Assy)|D3.7.9-2 Miscellaneous Penetrations (Wall Anchor - Conventional Roof Assy)(Under Construction)]]
 
:[[TPO Details:D2.7.35 Miscellaneous Penetrations (Wall Anchor - Protected Roof Assy)|D3.7.35 Miscellaneous Penetrations (Wall Anchor - Protected Roof Assy)(Under Construction)]]
 
:[[TPO Details:D2.7.9-3 Miscellaneous Penetrations (Wall Anchor - Protected Roof Assy)|D3.7.9-3 Miscellaneous Penetrations (Wall Anchor - Protected Roof Assy)(Under Construction)]]
 
 
</div>
 
</div>
 +
<div class="col-md-4">
 +
<hr>
 +
 +
===Part 10 (continued)===
 +
====='''Fire Separations''' ([[TPO_Roof_Systems_Standard#10.3.4.4._Fire_Separation_Walls | Article 10.3.4.4.]])=====
 +
<ol>
 +
<li>[[TPO Fire Separation Joint |Fire Separation Joint]] - Under construction
 +
<li>[[TPO Fire Separation Wall | Fire Separation Wall]] - Under construction
 +
</li></ol>
 +
 +
====='''Doors, Windows, and Wall Openings''' ([[TPO_Roof_Systems_Standard#10.3.4.5._Doors.2C_Windows.2C_and_Wall_Openings | Article 10.3.4.5.]])=====
 +
<ol>
 +
<li>[[TPO Low Door Opening | {{hilite | Low Door Opening || 2026-October-31 }}]]
 +
<li>[[TPO Window Opening | Window Opening]] - Under construction
 +
</li></ol>
 +
 +
====='''Expansion Joints''' ([[TPO_Roof_Systems_Standard#10.3.6.1._Expansion_Joints | Article 10.3.6.1.]])=====
 +
<ol>
 +
<li>[[TPO Expansion Joint (Wall) | Expansion Joint (Wall)]] - Under construction
 +
<li>[[TPO Expansion Joint (Field)| Expansion Joint (Field)]] - Under construction
 +
</li></ol>
 +
 +
====='''Control Joints (Roof Dividers)''' ([[TPO_Roof_Systems_Standard#10.3.6.2._Control_Joints_.28Roof_Dividers.29 | Article 10.3.6.2.]])=====
 +
<ol>
 +
<li>[[TPO Control Joint (Roof Divider)| {{hilite | Control Joint (Roof Divider) || 2026-October-31 }}]]
 +
</li></ol>
 +
 +
===Part 11 - Drainage===
 +
 +
====='''Cast-iron Roof Drains''' ([[TPO_Roof_Systems_Standard#11.3.3.2._General_Requirements_for_Cast-iron_Roof_Drains | Article 11.3.3.2.]])=====
 +
<ol>
 +
<li>[[TPO Cast Iron Drains| Cast Iron Drains]] - Under construction
 +
</li></ol>
 +
 +
====='''Flanged Insert-type Roof Drains''' ([[TPO_Roof_Systems_Standard#11.3.3.6._Flanged_Insert-type_Roof_Drains | Article 11.3.3.6.]])=====
 +
<ol>
 +
<li>[[TPO Flanged Insert Drain| Flanged Insert Drain]] - Under construction
 +
<li>[[TPO Flanged Insert Drain (Clamping Ring)| Flanged Insert Drain (Clamping Ring)]] - Under construction
 +
</li></ol>
  
 +
====='''Scuppers and Overflows''' ([[TPO_Roof_Systems_Standard#11.3.3.7._Scuppers_and_Overflows | Article 11.3.3.7.]])=====
 +
<ol>
 +
<li>[[TPO Open-wall Scupper Drain | Open-wall Scupper Drain ]] - Under construction
 +
<li>[[TPO Through-wall Scupper Drain | Through-wall Scupper Drain ]] - Under construction
 +
</li></ol>
  
 +
</div>
 +
<div class="col-md-4">
 
<hr>
 
<hr>
  
 +
===Part 12 - Penetrations and Curbs===
 +
 +
====='''Flashing Penetrations''' ([[TPO_Roof_Systems_Standard#12.3.2.1._General_Requirements_for_Flashing_Penetrations | Article 12.3.2.1.]])=====
 +
<ol>
 +
<li>[[TPO Plumbing Vent (Conventional Roof System)| {{hilite | Plumbing Vent (Conventional Roof System) || 2026-October-31 }}]]
 +
<li>[[TPO 2-Part Retrofit Flashing (Cable Penetration) | 2-Part Retrofit Flashing (Cable Penetration)]] - Under construction
 +
<li>[[TPO Fall Protection Anchor in Roof | Fall Protection Anchor in Roof]] - Under construction
 +
<li>[[TPO Fall Protection Anchor in Wall  | Fall Protection Anchor in Wall]] - Under construction
 +
<li>[[TPO Fall Protection Anchor in Wall (Protected) | Fall Protection Anchor in Wall (Protected Roof System)]] - Under construction
 +
</li></ol>
 +
 +
====='''Curbs, Sleepers, and Equipment Pads''' ([[TPO_Roof_Systems_Standard#12.3.2.4._Curbs.2C_Sleepers.2C_and_Equipment_Pads | Article 12.3.2.4.]])=====
 +
<ol>
 +
<li>[[TPO Basic Curb| {{hilite | Basic Curb || 2021-February-7 }}]] - Under construction
 +
<li>[[TPO Curb for Multiple Penetrations| Curb for Multiple Penetrations]] - Under construction
 +
<li>[[TPO Mechanical Equipment Curb| Mechanical Equipment Curb]] - Under construction
 +
<li>[[TPO Equipment Sleeper | Equipment Sleeper]] - Under construction
 +
</li></ol>
  
 +
====='''Railings, Ladders, and Other Attached Structures''' ([[TPO_Roof_Systems_Standard#12.3.2.7._Railings.2C_Ladders.2C_and_Other_Attached_Structures | Article 12.3.2.7.]])=====
 +
<ol>
 +
<li>[[TPO Railing | Railing]] - Under construction
 +
</li></ol>
  
 +
====='''Sealant Pockets''' ([[TPO_Roof_Systems_Standard#12.3.2.8._Sealant_Pockets | Article 12.3.2.8.]])=====
 +
<ol>
 +
<li>[[TPO Sealant Pocket| Sealant Pocket]] - Under construction
 +
</li></ol>
  
[[TPO/PVC (Thermoplastic Membranes) Roof Systems|<i class="fa fa-chevron-circle-left" ></i> Back to ''TPO/PVC Roof Systems'']]
+
===Part 13 - Linear Metal Flashing===
 +
:[[LMF Metal Cap Flashing (joints) | Metal Cap Flashing (joints)]]
 +
:[[LMF Metal Cap Flashing (inside corner) | Metal Cap Flashing (inside corner)]]
 +
:[[LMF Metal Cap Flashing (Parapet-to-Wall Transition - Site Formed) | Metal Cap Flashing (Parapet-to-Wall Transition - Site Formed)]]
  
[[Construction Details|<i class="fa fa-chevron-circle-left" ></i> Back to ''Construction Details Section'']]
+
:[[TPO Metal Butt Joint | {{hilite | Metal Butt Joint || 2026-October-31 }}]]
 +
 
 +
:'''NOTE''': The following pages are currently under construction
 +
 
 +
:[[LMF 13.3.1-4 Metal Cap Flashing (Parapet-to-Wall Transition - Shop-Formed) | Metal Cap Flashing (Parapet-to-Wall Transition - Shop-Formed)]]
 +
 
 +
===Part 14 - The Roof as a Platform===
 +
 
 +
</div>
 +
 
 +
<div class="col-md-12">
 +
<hr>
 +
 
 +
[[TPO Roof Systems Standard|<i class="fa fa-chevron-circle-left" ></i> ''Standard for TPO Membrane Roof Systems'']]
 +
 
 +
[[RCABC Roofing Practices Manual| <i class="fa fa-home fa"></i> Home]]
 +
{{Template:RPM Page Footer with Copyright and Current Date}}
 +
</div>

Latest revision as of 22:14, 12 November 2025



Division D - Construction Details

Construction Details for TPO Membrane Roof Systems
TPO project (courtesy Carlisle Syntec).jpg
The drawings linked on this page are intended to represent a variety of TPO Membrane roof system applications while remaining generic with regards to manufacturers’ specific application specifications. They do not represent all possible manufacturer application roof system designs. Consult each manufacturer's specifications and the RoofStar Guarantee Standards to develop a system acceptable to both the manufacturer and the RoofStar Guarantee Program.
For further information about TPO Membrane System designs and requirements, see the Standard for TPO Membrane Roof Systems.

Part 10 (continued)

Fire Separations ( Article 10.3.4.4.)
  1. Fire Separation Joint - Under construction
  2. Fire Separation Wall - Under construction
Doors, Windows, and Wall Openings ( Article 10.3.4.5.)
  1. Low Door Opening
  2. Window Opening - Under construction
Expansion Joints ( Article 10.3.6.1.)
  1. Expansion Joint (Wall) - Under construction
  2. Expansion Joint (Field) - Under construction
Control Joints (Roof Dividers) ( Article 10.3.6.2.)
  1. Control Joint (Roof Divider)

Part 11 - Drainage

Cast-iron Roof Drains ( Article 11.3.3.2.)
  1. Cast Iron Drains - Under construction
Flanged Insert-type Roof Drains ( Article 11.3.3.6.)
  1. Flanged Insert Drain - Under construction
  2. Flanged Insert Drain (Clamping Ring) - Under construction
Scuppers and Overflows ( Article 11.3.3.7.)
  1. Open-wall Scupper Drain - Under construction
  2. Through-wall Scupper Drain - Under construction

Part 12 - Penetrations and Curbs

Flashing Penetrations ( Article 12.3.2.1.)
  1. Plumbing Vent (Conventional Roof System)
  2. 2-Part Retrofit Flashing (Cable Penetration) - Under construction
  3. Fall Protection Anchor in Roof - Under construction
  4. Fall Protection Anchor in Wall - Under construction
  5. Fall Protection Anchor in Wall (Protected Roof System) - Under construction
Curbs, Sleepers, and Equipment Pads ( Article 12.3.2.4.)
  1. Basic Curb - Under construction
  2. Curb for Multiple Penetrations - Under construction
  3. Mechanical Equipment Curb - Under construction
  4. Equipment Sleeper - Under construction
Railings, Ladders, and Other Attached Structures ( Article 12.3.2.7.)
  1. Railing - Under construction
Sealant Pockets ( Article 12.3.2.8.)
  1. Sealant Pocket - Under construction

Part 13 - Linear Metal Flashing

Metal Cap Flashing (joints)
Metal Cap Flashing (inside corner)
Metal Cap Flashing (Parapet-to-Wall Transition - Site Formed)
Metal Butt Joint
NOTE: The following pages are currently under construction
Metal Cap Flashing (Parapet-to-Wall Transition - Shop-Formed)

Part 14 - The Roof as a Platform


Standard for TPO Membrane Roof Systems