TPO Low Door Opening

Jump to: navigation, search

TPO Low Door Opening

Revision as of 16:23, 7 November 2025 by James Klassen (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)



Division D - Construction Details


TPO | Low Door Opening ( Article 10.3.4.5.)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).

The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text.

TPO Details


Part 10 - Construction Detail - Low Door Opening - TPO.png

1 WORK INCLUDED

(1) Roof system
Conventionally insulated system shown (refer to the membrane Standard for requirements).
(2) Field membrane
TPO shown (see Part 9 for requirements)
(3) Self-adhered membrane (pre-flashing)
Adhered. Apply over rough sill or sill woodwork. Prime as required.
(4) Metal water-stop flashing
Dimensions as specified in design. Mechanically attach to inside face of door sill. Cut flashing to fit opening width.
(5) Membrane flashing (not shown)
Optional, if field membrane stops at edge securement. Install to overlap and seal in metal water-stop flashing.
(6) Membrane corner reinforcement
Install as required by the Standard and the manufacturer.
(7) Metal base flashing (under door)
Optional; protection for membrane when pavers are installed (shown), or when exposed membrane is vulnerable to damage. Mechanical fasteners must be at least 87.5 mm (3-1/2”) above the drainage plane.
(8) Membrane flashing (not shown)
Optional, if field membrane stops at edge securement. Applicable for exterior-insulated walls. Seals roof membrane flashing to air/vapour barrier on wall and provides sufficient exposure for positive union with WRB (by others). Mechanically secure membrane (metal base flashing used for securement in this detail).
(9) Metal base flashing (walls)
Optional; protects membrane flashing from damage, and functions as removable panel to permit access to membrane flashing for future replacement.
(10) Pavers and pedestals
May be installed by others, if specified. See Part 14 for material and application requirements. Must be at least 12 mm (1/2”) away from other pavers, and from membrane flashing or metal base flashing, to permit adequate drainage.

2 RELATED WORK BY OTHERS

(A) Wall and cladding
Generic and representative only.
(B) WRB (Water Resistive Barrier)
Generic and representative only.
(C) Door and jamb assembly
Generic and representative only.

NOTE: See the Standard for additional requirements.


Back to TPO Roof System Details