Difference between revisions of "ASM Membrane Gutter (Design Elements)"

Jump to: navigation, search

Difference between revisions of "ASM Membrane Gutter (Design Elements)"

(WORK INCLUDED)
 
(16 intermediate revisions by the same user not shown)
Line 1: Line 1:
{| class="wikitable" | style="color: black; background-color: orange; width: 100%;text-align:center"
+
{{Template:RPM Info}}
| colspan="2"  | <big>'''''RoofStar Guarantee Standards''''' are <span style="color:#6495ed">'''blue-linked'''</span></big>
+
 
|}
+
{{DISPLAYTITLE:<span style="position: absolute; clip: rect(1px 1px 1px 1px); clip: rect(1px, 1px, 1px, 1px);">{{FULLPAGENAME}}</span>}}
 +
__NOTOC__
 +
 
 +
<big><big>Division D - Construction Details</big></big>
 +
<hr>
 +
<big><big><big><big><big>ASM | Membrane Gutter (Design Elements) ([[ASM_Roof_Systems_Standard#11.1.4.3.._Membrane_Gutters | Article 11.1.4.3.]])</big></big></big></big></big>
 +
{{Template:Construction Details Header}}
 
<div class="panel panel-success">
 
<div class="panel panel-success">
 
<div class="panel-heading"><big>'''ASM Details'''</big></div>
 
<div class="panel-heading"><big>'''ASM Details'''</big></div>
Line 7: Line 13:
 
<div class="col-md-6">
 
<div class="col-md-6">
 
<div style="text-align:center; vertical-align:center">
 
<div style="text-align:center; vertical-align:center">
[[File:8.3.1.jpg|class=img-responsive]]
+
[[File:ASM 12.1.1 Built-in Gutter (Design).jpg|class=img-responsive | link=http://rpm.rcabc.org/images/3/3b/ASM_12.1.1_Built-in_Gutter_%28Design%29.jpg]]
 +
</div>
 +
 
 +
::Click below for a printable version of this page (N/A)
 +
 
 +
<div style="width:150px; text-align: left;">
 +
:[[File:Pdf.png|100 px|link=http://rpm.rcabc.org/images/5/52/D1.7.6-3_Print_Sheet.pdf|'''Print Sheet''']]
 
</div>
 
</div>
 +
 +
 
</div><!-- COL-MD-6 -->
 
</div><!-- COL-MD-6 -->
  
 
<div class="col-md-6">
 
<div class="col-md-6">
 
=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
;(1) '''Membranes''': Membranes must be installed to ''RoofStar Guarantee Standards'' and the manufacturer's printed instructions
+
;(1) '''Membranes''': Membranes must be installed to '''''RoofStar Guarantee Standards''''' and the manufacturer's printed instructions ({{hilite | NOTE: Fasteners shall be installed 152.4 mm (6”) or more above the maximum water line, and gutters must include a scupper overflow drain. || 2017-April-22 }}).
 
;(2) '''Adhesion''': Membranes must be fully adhered, where exposed, and mechanically fastened at terminations 300 mm (12") o/c
 
;(2) '''Adhesion''': Membranes must be fully adhered, where exposed, and mechanically fastened at terminations 300 mm (12") o/c
;(3) '''Height''': The minimum vertical sealed height above the maximum water level is 150 mm (6"). The membrane run up the slope will vary with roof pitch. Increase height in heavy snow regions.
+
;(3) '''Height''': The minimum vertical sealed height above the maximum water level is 152.4 mm (6"). The membrane run up the slope will vary with roof pitch. Increase height in heavy snow regions. Built-in gutter membranes can be extended to act as eave protection for the adjoining roof system. Underlay or eave protection membrane must overlap built-in gutter membrane by a minimum of 203.2 mm (8") and be installed in shingle fashion (not shown for clarity).
;(4) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMICE|'''Ice and Water Protection''']]: Built-in gutter membranes can be extended to act as an eave protection membrane. Underlay or eave protection membrane must overlap built-in gutter membrane by a minimum of 200 mm (8") and be installed in shingle fashion (not shown for clarity).
+
;(4) Metal cap flashing
  
 
<hr>
 
<hr>
  
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
;(A) '''Dimension''': Dimensions of parapets, cants and water loading of gutters are variable and should be determined by design authority  
+
;(A) [[ASM Roof Systems Standard#ASMDECK|'''Acceptable Deck''']]
;(B) [[RoofStar Guarantee Standards for ASM Roof Systems#ASMDECK|'''Acceptable Deck''']]
+
;(B) '''Dimension''': Dimensions of parapets, cants and water loading of gutters are variable and should be determined by design authority  
 
</div><!-- COL-6-MD -->
 
</div><!-- COL-6-MD -->
 
</div><!-- PANEL BODY -->
 
</div><!-- PANEL BODY -->
 
</div><!-- PANEL -->
 
</div><!-- PANEL -->
  
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements.
+
'''NOTE''': See the [[ASM Roof Systems Standard | '''Standard''']] for additional requirements.
  
 
<hr>
 
<hr>
  
 +
[[ASM Roof System Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''ASM Roof System Details'']]
  
 +
[[Main Page | <i class="fa fa-home fa"></i> Home]]
  
[[Section:E. Application: Steep Slope Roofs|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''ASM Application'']]
+
{{Tempate:RPM Page Footer with Copyright and Current Date}}
 
 
[[Architectural Sheet Metal Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''ASM Construction Details'']]
 
 
 
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']]
 

Latest revision as of 16:01, 18 March 2024



Division D - Construction Details


ASM | Membrane Gutter (Design Elements) ( Article 11.1.4.3.)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).

The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text.

ASM Details

ASM 12.1.1 Built-in Gutter (Design).jpg

Click below for a printable version of this page (N/A)
Print Sheet


1 WORK INCLUDED

(1) Membranes
Membranes must be installed to RoofStar Guarantee Standards and the manufacturer's printed instructions (NOTE: Fasteners shall be installed 152.4 mm (6”) or more above the maximum water line, and gutters must include a scupper overflow drain.).
(2) Adhesion
Membranes must be fully adhered, where exposed, and mechanically fastened at terminations 300 mm (12") o/c
(3) Height
The minimum vertical sealed height above the maximum water level is 152.4 mm (6"). The membrane run up the slope will vary with roof pitch. Increase height in heavy snow regions. Built-in gutter membranes can be extended to act as eave protection for the adjoining roof system. Underlay or eave protection membrane must overlap built-in gutter membrane by a minimum of 203.2 mm (8") and be installed in shingle fashion (not shown for clarity).
(4) Metal cap flashing

2 RELATED WORK BY OTHERS

(A) Acceptable Deck
(B) Dimension
Dimensions of parapets, cants and water loading of gutters are variable and should be determined by design authority

NOTE: See the Standard for additional requirements.


Back to ASM Roof System Details

Home

© RCABC 2024
No reproduction of this material, in whole or in part, is lawful without the expressed permission of the RCABC Guarantee Corp.