=== WORK INCLUDED ===
 
=== WORK INCLUDED ===
;(1) [[SBS Roof Systems Standard#SBSSUBSTRATES|'''Supporting Deck Overlay''']]: If required by design authority.
+
;(1) [[SBS Roof Systems Standard#PART_5|'''Supporting Deck Overlay''']]: If required by design authority.
;(2) [[SBS Roof Systems Standard#SBSAIRVAPOUR|'''Air or Vapour Control Layers''']]: If required by design authority.
+
;(2) [[SBS Roof Systems Standard#PART_6|'''Air or Vapour Control Layers''']]: If required by design authority.
;(3) [[SBS Roof Systems Standard#SBSINSULATION|'''Insulation''']]: See available insulation products in the [[Roof Deck Insulation|'''Accepted Materials''']] section of this Manual.
+
;(3) [[SBS Roof Systems Standard#PART_7|'''Insulation''']]: See available insulation products in the [[Roof Deck Insulation|'''Accepted Materials''']] section of this Manual.
;(4) [[SBS Roof Systems Standard#SBSINSULATIONOVERLAY|'''Insulation Overlay''']]:  As required.  
+
;(4) [[SBS Roof Systems Standard#PART_8|'''Insulation Overlay''']]:  As required.  
;(5) [[SBS Roof Systems Standard#SBSBASE|'''Primary Membrane''']] and [[SBS Roof Systems Standard#SBSPROTECTION| '''Membrane Protection''']]
+
;(5) [[SBS Roof Systems Standard#PART_9|'''Primary Membrane''']] and [[SBS Roof Systems Standard#SBSPROTECTION| '''Membrane Protection''']]
;(6) [[SBS Roof Systems Standard#SBS-STRIPPING|'''Membrane Flashing''']]:  Lap one ply from each side over top of sleeper (C) and mechanically fasten.
+
;(6) [[SBS Roof Systems Standard#PART_10|'''Membrane Flashing''']]:  Lap one ply from each side over top of sleeper (C) and mechanically fasten.
 
;(7) '''Alternate Cap Flashing''': May be used instead of lapping membrane flashing over sleeper.
 
;(7) '''Alternate Cap Flashing''': May be used instead of lapping membrane flashing over sleeper.
;(8) [[SBS Roof Systems Standard#METALCAP-SBS|'''Metal Base Flashing''']]: Mechanically fasten to top of wood blocking, standing seam at corners, optional on flexible membrane systems.<b> </b>Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
+
;(8) [[SBS Roof Systems Standard#PART_13|'''Metal Base Flashing''']]: Mechanically fasten to top of wood blocking, standing seam at corners, optional on flexible membrane systems.<b> </b>Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
;(9) [[SBS Roof Systems Standard#METALCAP-SBS|'''Metal Cap Flashing''']]
+
;(9) [[SBS Roof Systems Standard#PART_13|'''Metal Cap Flashing''']]
 
:NOTE: (8) and (9) may be one piece.
 
:NOTE: (8) and (9) may be one piece.
  
Line 31: Line 31:
  
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
;(A) [[SBS Roof Systems Standard#SBSDECKS|'''Acceptable Supporting Deck Structure''']]
+
;(A) [[SBS Roof Systems Standard#PART_2|'''Acceptable Supporting Deck Structure''']]
;(B) [[SBS Roof Systems Standard#SBSAIRVAPOUR|'''Air and Vapour Control Layer Seal''']]
+
;(B) [[SBS Roof Systems Standard#PART_6|'''Air and Vapour Control Layer Seal''']]
;(C) [[SBS Roof Systems Standard#SBSCURB|'''Wood Blocking/Sleeper''']]: Minimum 150 mm (6") thick, minimum 100 mm (4") above finished roof surface.
+
;(C) [[SBS Roof Systems Standard#PART_11|'''Wood Blocking/Sleeper''']]: Minimum 150 mm (6") thick, minimum 100 mm (4") above finished roof surface.
 
</div><!-- COL-6-MD -->
 
</div><!-- COL-6-MD -->
 
</div><!-- PANEL BODY -->
 
</div><!-- PANEL BODY -->

Revision as of 18:57, 1 September 2021


Notice to Reader
Images used in a Construction Detail are representative and not prescriptive. Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the requirements of the Standard they represent. Unless otherwise required by the Standard, dimensions, the selection of materials and their application remains the responsibility of the Design Authority.

The full text of the referenced requirements in the Standard may be read by using the blue hyperlinks
SBS Details

10.3.5.2.jpg

1 WORK INCLUDED

(1) Supporting Deck Overlay
If required by design authority.
(2) Air or Vapour Control Layers
If required by design authority.
(3) Insulation
See available insulation products in the Accepted Materials section of this Manual.
(4) Insulation Overlay
As required.
(5) Primary Membrane and Membrane Protection
(6) Membrane Flashing
Lap one ply from each side over top of sleeper (C) and mechanically fasten.
(7) Alternate Cap Flashing
May be used instead of lapping membrane flashing over sleeper.
(8) Metal Base Flashing
Mechanically fasten to top of wood blocking, standing seam at corners, optional on flexible membrane systems. Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
(9) Metal Cap Flashing
NOTE: (8) and (9) may be one piece.

2 RELATED WORK BY OTHERS

(A) Acceptable Supporting Deck Structure
(B) Air and Vapour Control Layer Seal
(C) Wood Blocking/Sleeper
Minimum 150 mm (6") thick, minimum 100 mm (4") above finished roof surface.

NOTE: See the Standard for additional requirements.