=== WORK INCLUDED ===
+
{{DISPLAYTITLE:<span style="position: absolute; clip: rect(1px 1px 1px 1px); clip: rect(1px, 1px, 1px, 1px);">{{FULLPAGENAME}}</span>}}
(1) <b>Gypsum Overlay Board: </b>If required by design authority.
+
__NOTOC__
  
(2) <b>Vapour Retarder</b>: If required by design authority.
+
<big><big>Division D - Construction Details</big></big>
 +
<hr>
 +
<big><big><big><big><big>SBS | Equipment Sleeper ([[SBS_Roof_Systems_Standard#12.3.2.4._Curbs.2C_Sleepers.2C_and_Equipment_Pads | Article 12.3.2.4.]])</big></big></big></big></big>
 +
{{Template:Construction Details Header}}
 +
<div class="panel panel-success">
 +
<div class="panel-heading"><big>'''SBS Details'''</big></div>
 +
<div class="panel-body">
 +
<div class="col-md-6">
 +
<div style="text-align:center; vertical-align:center">
 +
[[File:10.3.5.2.jpg| link=http://rpm.rcabc.org/images/3/30/10.3.5.2.jpg | class=img-responsive]]
 +
</div>
 +
</div><!-- COL-MD-6 -->
  
(3) <b>Insulation</b>
+
<div class="col-md-6">
 +
=== WORK INCLUDED ===
 +
;(1) [[SBS Roof Systems Standard#PART_5|'''Supporting Deck Overlay''']]: If required by design authority.
 +
;(2) [[SBS Roof Systems Standard#PART_6|'''Air or Vapour Control Layers''']]: If required by design authority.
 +
;(3) [[SBS Roof Systems Standard#PART_7|'''Insulation''']]: See available insulation products in the [[Division C| Accepted Materials]] Division of this ''Manual''.
 +
;(4) [[SBS Roof Systems Standard#PART_8|'''Insulation Overlay''']]:  As required.
 +
;(5) [[SBS Roof Systems Standard#PART_9|'''Primary Membrane''']]: Also see membrane protection in [[SBS Roof Systems Standard#9.3.2.7. Protection of Membranes| Article 9.3.2.7.]]
 +
;(6) [[SBS Roof Systems Standard#PART_10|'''Membrane Flashing''']]:  Lap one ply from each side over top of sleeper (C) and mechanically fasten.
 +
;(7) '''Alternate Cap Flashing''': May be used instead of lapping membrane flashing over sleeper.
 +
;(8) [[SBS Roof Systems Standard#PART_13|'''Metal Base Flashing''']]: Mechanically fasten to top of wood blocking, standing seam at corners, optional on flexible membrane systems.<b> </b>Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
 +
;(9) [[SBS Roof Systems Standard#PART_13|'''Metal Cap Flashing''']]
 +
:NOTE: (8) and (9) may be one piece.
  
(4) <b>Insulation Overlay</b>:  As required. See <i>RGC Guarantee Standard B4.1, B4.2 </i>and<i> C4.1</i>
+
<hr>
 
 
(5) <b>Primary Membrane and Membrane Protection</b>
 
 
 
(6) <b>Membrane Flashing:</b>  Lap one ply from each side over top of sleeper (C) and mechanically fasten.
 
 
 
(7)<b> Alternate Cap Flashing:</b> May be used instead of lapping membrane flashing over sleeper.
 
 
 
(8)<b> Metal Base Flashing:</b>  Mechanically fasten to top of wood blocking, standing seam at corners, optional on flexible membrane systems.<b> </b>Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats. See <i>RGC Guarantee Standard A6.9</i>
 
 
 
(9)<b> Metal Cap Flashing:</b><i> </i>Flashings
 
 
 
(8) and (9) may be one piece.
 
  
 
=== RELATED WORK BY OTHERS ===
 
=== RELATED WORK BY OTHERS ===
(A) <b>Acceptable Deck</b>
+
;(A) [[SBS Roof Systems Standard#PART_2|'''Acceptable Supporting Deck Structure''']]
 
+
;(B) [[SBS Roof Systems Standard#PART_6|'''Air and Vapour Control Layer Seal''']]
(B) <b>Air / Vapour Seal</b>
+
;(C) [[SBS Roof Systems Standard#PART_11|'''Wood Blocking/Sleeper''']]: Minimum 150 mm (6") thick, minimum 100 mm (4") above finished roof surface.
 
+
</div><!-- COL-6-MD -->
(C) <b>Wood Blocking / Sleeper:</b> Minimum 150 mm (6") thick, minimum 100 mm (4") above finished roof surface.
+
</div><!-- PANEL BODY -->
 
+
</div><!-- PANEL -->
'''NOTE''': Refer to <i>RGC Guarantee Standards</i> for additional requirements.
 
  
 +
'''NOTE''': See the [[SBS Roof Systems Standard | '''Standard''']] for additional requirements.
  
 
<hr>
 
<hr>
  
 +
[[SBS Roof System Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''"SBS" Roof System Details'']]
  
 +
[[Main Page | <i class="fa fa-home fa"></i> Home]]
  
 
+
{{Tempate:RPM Page Footer with Copyright and Current Date}}
[[Section:D. Application: Low Slope Roofs|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''SBS Application'']]
 
 
 
[[SBS Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''SBS Construction Details'']]
 
 
 
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Construction Details'']]
 

Latest revision as of 18:21, 27 October 2023



Division D - Construction Details


SBS | Equipment Sleeper ( Article 12.3.2.4.)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).

The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text.

SBS Details

10.3.5.2.jpg

1 WORK INCLUDED

(1) Supporting Deck Overlay
If required by design authority.
(2) Air or Vapour Control Layers
If required by design authority.
(3) Insulation
See available insulation products in the Accepted Materials Division of this Manual.
(4) Insulation Overlay
As required.
(5) Primary Membrane
Also see membrane protection in Article 9.3.2.7.
(6) Membrane Flashing
Lap one ply from each side over top of sleeper (C) and mechanically fasten.
(7) Alternate Cap Flashing
May be used instead of lapping membrane flashing over sleeper.
(8) Metal Base Flashing
Mechanically fasten to top of wood blocking, standing seam at corners, optional on flexible membrane systems. Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
(9) Metal Cap Flashing
NOTE: (8) and (9) may be one piece.

2 RELATED WORK BY OTHERS

(A) Acceptable Supporting Deck Structure
(B) Air and Vapour Control Layer Seal
(C) Wood Blocking/Sleeper
Minimum 150 mm (6") thick, minimum 100 mm (4") above finished roof surface.

NOTE: See the Standard for additional requirements.