Difference between revisions of "SBS Low Door Opening"

Jump to: navigation, search

Difference between revisions of "SBS Low Door Opening"

(WORK INCLUDED)
 
(35 intermediate revisions by the same user not shown)
Line 1: Line 1:
[[File:10.3.3.5.jpg]]
+
{{Template:RPM Info}}
  
=== WORK INCLUDED ===
+
{{DISPLAYTITLE:<span style="position: absolute; clip: rect(1px 1px 1px 1px); clip: rect(1px, 1px, 1px, 1px);">{{FULLPAGENAME}}</span>}}
;(1) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSBASE|'''Primary Roof Membrane''']]
+
__NOTOC__
;(2) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSDOOR|'''Membrane Flashing''']]: Carried up wall minimum 200 mm (8") above roof surface. At doorsill openings membrane flashing may be less than 200mm (8") in height but must not be less than 100mm (4") in height above the primary roof membrane. When doorsills are less than 200mm (8") a metal waterstop flashing must be mechanically attached to backside of doorsill framing or opening and be sealed with membrane flashing. Membrane gussets must be installed at doorsill opening corners.
 
;(3) '''Protection/Drainage Layer''': Optional
 
;(4) [[RoofStar Guarantee Standards for SBS Roof Systems#METALCAP-SBS|'''Metal Base Flashing''']]: Optional on flexible membrane systems. Required on assemblies using gravel ballast filter mats.
 
;(5) [[RoofStar Guarantee Standards for SBS Roof Systems#METALCAP-SBS|'''Metal Counter-flashing''']]
 
;(6) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSDOOR|'''Metal Water-stop Flashing''']]: Mechanically attached to inside of door sill framing or opening. Cut flashing to fit opening and install membrane gussets at corners.
 
;(7) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSDOOR|'''Metal Pan Sill Flashing''']]: Optional - Metal pan with water stop formed with pan folded, welded or soldered corners mechanically attached to inside of door sill frame or opening and sealed with membrane flashing.
 
  
=== RELATED WORK BY OTHERS ===
+
<big><big>Division D - Construction Details</big></big>
(A) <b>Acceptable Deck</b>: Concrete slab shown
+
<hr>
 +
<big><big><big><big><big>SBS | Low Door Opening ([[SBS_Roof_Systems_Standard#10.3.4.5._Doors.2C_Windows.2C_and_Wall_Openings | Article 10.3.4.5.]])</big></big></big></big></big>
 +
{{Template:Construction Details Header}}
 +
<div class="panel panel-success">
 +
<div class="panel-heading"><big>'''SBS Details'''</big></div>
 +
<div class="panel-body">
 +
<div class="col-md-6">
 +
<div style="text-align:center; vertical-align:center">
 +
[[File:SBS Low Door Opening.jpg|link=https://rpm.rcabc.org/images/2/26/SBS_Low_Door_Opening.jpg |class=img-responsive]]
 +
</div>
 +
</div><!-- COL-MD-6 -->
  
(B) <b>Wall Cladding and Flashing</b>
+
<div class="col-md-6">
 +
=== WORK INCLUDED ===
 +
;(1) [[SBS Roof Systems Standard#PART_1|'''Roof system''']]: Conventionally insulated system shown (refer to the membrane Standard for requirements).
 +
;(2) [[SBS Roof Systems Standard#PART_9|'''Field Membrane''']]: SBS-modified bituminous system shown (see Part 9 for standards)
 +
;(3) [[SBS Roof Systems Standard#PART_10|'''Self-adhered membrane (pre-flashing)''']]: Apply over rough sill or sill woodwork.  Prime as required.
 +
;(4) [[SBS Roof Systems Standard#PART_10|'''Metal water-stop flashing''']]: Dimensions as specified in design.  Mechanically attach to inside face of door sill.  Cut flashing to fit opening width.
 +
;(5) [[SBS Roof Systems Standard#PART_10|'''Membrane flashing''']]: Base membrane shown.  Install to overlap and seal in metal water-stop flashing.
 +
;(6) [[SBS Roof Systems Standard#PART_10|'''Membrane gussets''']]: Install in corners to seal joints.
 +
;(7) [[SBS Roof Systems Standard#PART_13|'''Metal base flashing (under door)''']]: Optional; protection for membrane when pavers are installed (shown), or when exposed membrane is vulnerable to damage.  Mechanical fasteners must be at least 87.5 mm (3-1/2”) above the drainage plane.
 +
;(8) [[SBS Roof Systems Standard#PART_10|'''Membrane flashing''']]: Applicable for exterior-insulated walls.  Seals roof membrane flashing to air/vapour barrier on wall and provides sufficient exposure for positive union with WRB (by others).  Mechanically secure membrane (metal base flashing used for securement in this detail).
 +
;(9) [[SBS Roof Systems Standard#PART_10|'''Metal base flashing (walls)''']]: Optional; protects membrane flashing from damage, and functions as removable panel to permit access to membrane flashing for future replacement.
 +
;(10) [[SBS Roof Systems Standard#PLATFORM|'''Pavers and pedestals''']]: May be installed by others, if specified.  See '''Part 14''' for material and application requirements.  Must be at least 12 mm (1/2”) away from other pavers, and from membrane flashing or metal base flashing, to permit adequate drainage.
  
 +
<hr>
  
'''NOTE''': Refer to <i>RGC Guarantee Standards</i> for additional requirements.
+
=== RELATED WORK BY OTHERS ===
 +
;(A) '''Wall and cladding''': Generic and representative only.
 +
;(B) '''WRB (Water Resistant Barrier)''': Generic and representative only.
 +
;(C) '''Door and jamb assembly''': Generic and representative only.
 +
</div><!-- COL-6-MD -->
 +
</div><!-- PANEL BODY -->
 +
</div><!-- PANEL -->
  
 +
'''NOTE''': See the [[SBS Roof Systems Standard | '''Standard''']] for additional requirements.
  
 
<hr>
 
<hr>
  
 +
[[SBS Roof System Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''"SBS" Roof System Details'']]
  
 +
[[Main Page | <i class="fa fa-home fa"></i> Home]]
  
 
+
{{Tempate:RPM Page Footer with Copyright and Current Date}}
[[Section:D. Application: Low Slope Roofs|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''SBS Application'']]
 
 
 
[[SBS Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''SBS Construction Details'']]
 
 
 
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa-2x" ></i> Back to ''Construction Details'']]
 

Latest revision as of 22:42, 9 December 2022



Division D - Construction Details


SBS | Low Door Opening ( Article 10.3.4.5.)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).

The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text.

SBS Details

SBS Low Door Opening.jpg

1 WORK INCLUDED

(1) Roof system
Conventionally insulated system shown (refer to the membrane Standard for requirements).
(2) Field Membrane
SBS-modified bituminous system shown (see Part 9 for standards)
(3) Self-adhered membrane (pre-flashing)
Apply over rough sill or sill woodwork. Prime as required.
(4) Metal water-stop flashing
Dimensions as specified in design. Mechanically attach to inside face of door sill. Cut flashing to fit opening width.
(5) Membrane flashing
Base membrane shown. Install to overlap and seal in metal water-stop flashing.
(6) Membrane gussets
Install in corners to seal joints.
(7) Metal base flashing (under door)
Optional; protection for membrane when pavers are installed (shown), or when exposed membrane is vulnerable to damage. Mechanical fasteners must be at least 87.5 mm (3-1/2”) above the drainage plane.
(8) Membrane flashing
Applicable for exterior-insulated walls. Seals roof membrane flashing to air/vapour barrier on wall and provides sufficient exposure for positive union with WRB (by others). Mechanically secure membrane (metal base flashing used for securement in this detail).
(9) Metal base flashing (walls)
Optional; protects membrane flashing from damage, and functions as removable panel to permit access to membrane flashing for future replacement.
(10) Pavers and pedestals
May be installed by others, if specified. See Part 14 for material and application requirements. Must be at least 12 mm (1/2”) away from other pavers, and from membrane flashing or metal base flashing, to permit adequate drainage.

2 RELATED WORK BY OTHERS

(A) Wall and cladding
Generic and representative only.
(B) WRB (Water Resistant Barrier)
Generic and representative only.
(C) Door and jamb assembly
Generic and representative only.

NOTE: See the Standard for additional requirements.


Back to "SBS" Roof System Details

Home

© RCABC 2024
No reproduction of this material, in whole or in part, is lawful without the expressed permission of the RCABC Guarantee Corp.