Difference between revisions of "SBS Mechanical Equipment Curb"

Jump to: navigation, search

Difference between revisions of "SBS Mechanical Equipment Curb"

 
(37 intermediate revisions by the same user not shown)
Line 1: Line 1:
{| class="wikitable" | style="color: black; background-color: orange; width: 100%;text-align:center"
+
{{Template:RPM Info}}
| colspan="2"  | <big>To read '''''RoofStar Guarantee Standards''''' for any element in this illustration, click on the <span style="color:#6495ed">'''blue-linked'''</span> terms</big>
 
|}
 
[[File:D1.7.7.jpg]]
 
  
 +
{{DISPLAYTITLE:<span style="position: absolute; clip: rect(1px 1px 1px 1px); clip: rect(1px, 1px, 1px, 1px);">{{FULLPAGENAME}}</span>}}
 +
__NOTOC__
  
=== WORK INCLUDED ===
+
<big><big>Division D - Construction Details</big></big>
;(1) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSSUBSTRATES|'''Gypsum Deck Overlay''']]: Required when insulation is too thin to span flutes of steel decking or when required as thermal barrier by design authority.
+
<hr>
;(2) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSVAPOUR|'''Vapour Retarder''']]: If required by design authority.
+
<big><big><big><big><big>SBS | Mechanical Equipment Curb ([[SBS_Roof_Systems_Standard#12.3.2.4._Curbs.2C_Sleepers.2C_and_Equipment_Pads | Article 12.3.2.4.]])</big></big></big></big></big>
;(3) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSINSULATION|'''Insulation''']]: Mechanically fastened. See available insulation products in the [[Roof Deck Insulation|'''Accepted Materials''']] section of this Manual.
+
{{Template:Construction Details Header}}
;(4) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSINSULATIONOVERLAY|'''Insulation Overlay Board''']]: As required.
 
;(5) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSBASE|'''Base Sheet''']]: Adhered to overlay board using asphalt, cold adhesive, self-adhered, mechanical attachment or torch applied according to manufacturer's specification. Torching directly to wood surfaces is not permitted.
 
;(6) [[RoofStar Guarantee Standards for SBS Roof Systems#SBS-STRIPPING|'''Base Sheet Flashing''']]: Adhered according to manufacturer's specifications, using cold adhesive, hot asphalt, self-adhered or torch applied to cover boards, or mechanically attached membrane. Must be tucked under metal flange and mechanically attached to nailing strip.
 
;(7) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSBASE|'''Cap Sheet''']]: Applied according to manufacturer's printed instructions and to <i>RoofStar Guarantee Standards</i>.
 
;(8) [[RoofStar Guarantee Standards for SBS Roof Systems#SBS-STRIPPING|'''Cap Sheet Flashing''']]: Applied according to manufacturer's printed instructions and to <i>RoofStar Guarantee Standards</i>. Must be tucked under metal flange and mechanically attached to the nailing strip.
 
;(9) [[RoofStar Guarantee Standards for SBS Roof Systems#METALCAP-SBS|'''Metal Base Flashing''']]: Mechanically fasten, standing seam at corners. Full width base flashing optional on flexible membranes. Partial skirt flashing minimum 75 mm (3") required on mechanical curbs that require flashing under metal flange.
 
  
<hr>
+
<div class="panel panel-success">
 +
<div class="panel-heading"><big>'''SBS Details'''</big></div>
 +
<div class="panel-body">
 +
<div class="col-md-6">
 +
<div style="text-align:center; vertical-align:center">
 +
[[File:SBS 11.3.3.2.-3B.jpg| link=http://rpm.rcabc.org/images/6/6c/D1.7.6-4%281%29.jpg | class=img-responsive]]
  
=== RELATED WORK BY OTHERS ===
+
[[File:SBS 11.3.3.2.-3C.jpg| link=http://rpm.rcabc.org/images/d/d3/D1.7.6-4_%282%29.jpg | class=img-responsive]]
;(A) [[RoofStar Guarantee Standards for SBS Roof Systems#SBSDECKS|'''Acceptable Deck''']]
+
</div>
;(B) '''Air / Vapour Seal'''
 
;(C) '''Mechanical Curb''': Minimum 200 mm (8") and maximum 300 mm (12") above finished roof surface.
 
;(D) '''Rigid Insulation'''
 
  
  
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements.
+
</div><!-- COL-MD-6 -->
* Some mechanical curbs are designed to allow membrane flashing to be carried up onto metal flange. Install according to manufacturers&#8217; instructions.
 
  
 +
<div class="col-md-6">
 +
=== WORK INCLUDED ===
 +
;(1) [[SBS Roof Systems Standard#PART_5|'''Supporting Deck Overlay''']]: Required when insulation is too thin to span flutes of steel decking or when required as thermal barrier by design authority.
 +
;(2) [[SBS Roof Systems Standard#PART_6|'''Air or Vapour Control Layers''']]: If required by design authority.
 +
;(3) [[SBS Roof Systems Standard#PART_7|'''Insulation''']]: Mechanically fastened.  See available insulation products in the[[Division C| Accepted Materials]] Division of this ''Manual''.
 +
;(4) [[SBS Roof Systems Standard#PART_8|'''Insulation Overlay''']]: As required.
 +
;(5) Flame protection (membrane strip): Also refer to the Standard for alternative methods for handling flame-sensitive details and roof perimeters.
 +
;(6) [[SBS Roof Systems Standard#PART_9|'''Base Field Membrane''']]: Adhered to overlay board using asphalt, cold adhesive, self-adhered, mechanical attachment or torch applied according to manufacturer's specification. Torching directly to wood surfaces is not permitted.
 +
;(7) [[SBS Roof Systems Standard#PART_10|'''Base Membrane Flashing''']]: Adhered according to manufacturer's specifications, using cold adhesive, hot asphalt, self-adhered or torch applied to cover boards, or mechanically attached membrane. Must be tucked under metal flange and mechanically attached to nailing strip.
 +
;(8) [[SBS Roof Systems Standard#PART_9|'''Cap Field Membrane''']]: Applied according to manufacturer's printed instructions and to <i>RoofStar Guarantee Standards</i>.
 +
;(9) [[SBS Roof Systems Standard#PART_10|'''Cap Membrane Flashing''']]: Applied according to manufacturer's printed instructions and to <i>RoofStar Guarantee Standards</i>. Must be tucked under metal flange and mechanically attached to the nailing strip.
 +
;(10) [[SBS Roof Systems Standard#PART_13|'''Metal Flashing''']]: Mechanically fasten, standing seam at corners. Full width base flashing optional on flexible membranes. Partial skirt flashing minimum 75 mm (3") required on mechanical curbs that require flashing under metal flange.
 +
;(11) [[SBS Roof Systems Standard#PART_13|'''Alternate Corner Cap (Shop-manufactured)''']]: Weld seams.  Bed in two parallel courses of butyl tape or acceptable sealant.  Mechanically fasten to outside face of curb flange.
 +
;(12) '''Butyl Tape (sealant)'''
 +
;(13) [[SBS Roof Systems Standard#PART_13|'''Fasteners''']]: Flanged fasteners with neoprene washers.
  
 
<hr>
 
<hr>
  
 +
=== RELATED WORK BY OTHERS ===
 +
;(A) [[SBS Roof Systems Standard#PART_2|'''Supporting Deck Structure''']]
 +
;(B) [[SBS Roof Systems Standard#PART_6|'''Air or Vapour Control Layer Seal''']]: Air and vapour controls installed by others should be made accessible to the ''Contractor'' for connection, to maintain continuity across assemblies and throughout the building enclosure.
 +
;(C) '''Mechanical Curb''': Minimum 200 mm (8") above finished roof surface.
 +
:* Some mechanical curbs are designed to allow membrane flashing to be carried up onto metal flange. Install according to manufacturers&#8217; instructions.
 +
;(D) '''Wood Nailing Board'''
 +
;(E) '''Neoprene Gasket for RTU'''
 +
 +
[[File:SBS 11.3.3.2.-3A.jpg| link=http://rpm.rcabc.org/images/d/d3/D1.7.6-4_%282%29.jpg | 450px]]
 +
</div><!-- COL-6-MD -->
 +
</div><!-- PANEL BODY -->
 +
</div><!-- PANEL -->
  
 +
'''NOTE''': See the [[SBS Roof Systems Standard | '''Standard''']] for additional requirements.
  
 +
<hr>
  
[[Section:D. Application: Low Slope Roofs|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''SBS Application'']]
+
[[SBS Roof System Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''"SBS" Roof System Details'']]
  
[[SBS Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''SBS Construction Details'']]
+
[[Main Page | <i class="fa fa-home fa"></i> Home]]
  
[[Section:G. Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''Construction Details'']]
+
{{Tempate:RPM Page Footer with Copyright and Current Date}}

Latest revision as of 18:19, 27 October 2023



Division D - Construction Details


SBS | Mechanical Equipment Curb ( Article 12.3.2.4.)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).

The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text.

SBS Details

SBS 11.3.3.2.-3B.jpg

SBS 11.3.3.2.-3C.jpg


1 WORK INCLUDED

(1) Supporting Deck Overlay
Required when insulation is too thin to span flutes of steel decking or when required as thermal barrier by design authority.
(2) Air or Vapour Control Layers
If required by design authority.
(3) Insulation
Mechanically fastened. See available insulation products in the Accepted Materials Division of this Manual.
(4) Insulation Overlay
As required.
(5) Flame protection (membrane strip)
Also refer to the Standard for alternative methods for handling flame-sensitive details and roof perimeters.
(6) Base Field Membrane
Adhered to overlay board using asphalt, cold adhesive, self-adhered, mechanical attachment or torch applied according to manufacturer's specification. Torching directly to wood surfaces is not permitted.
(7) Base Membrane Flashing
Adhered according to manufacturer's specifications, using cold adhesive, hot asphalt, self-adhered or torch applied to cover boards, or mechanically attached membrane. Must be tucked under metal flange and mechanically attached to nailing strip.
(8) Cap Field Membrane
Applied according to manufacturer's printed instructions and to RoofStar Guarantee Standards.
(9) Cap Membrane Flashing
Applied according to manufacturer's printed instructions and to RoofStar Guarantee Standards. Must be tucked under metal flange and mechanically attached to the nailing strip.
(10) Metal Flashing
Mechanically fasten, standing seam at corners. Full width base flashing optional on flexible membranes. Partial skirt flashing minimum 75 mm (3") required on mechanical curbs that require flashing under metal flange.
(11) Alternate Corner Cap (Shop-manufactured)
Weld seams. Bed in two parallel courses of butyl tape or acceptable sealant. Mechanically fasten to outside face of curb flange.
(12) Butyl Tape (sealant)
(13) Fasteners
Flanged fasteners with neoprene washers.

2 RELATED WORK BY OTHERS

(A) Supporting Deck Structure
(B) Air or Vapour Control Layer Seal
Air and vapour controls installed by others should be made accessible to the Contractor for connection, to maintain continuity across assemblies and throughout the building enclosure.
(C) Mechanical Curb
Minimum 200 mm (8") above finished roof surface.
  • Some mechanical curbs are designed to allow membrane flashing to be carried up onto metal flange. Install according to manufacturers’ instructions.
(D) Wood Nailing Board
(E) Neoprene Gasket for RTU

SBS 11.3.3.2.-3A.jpg

NOTE: See the Standard for additional requirements.


Back to "SBS" Roof System Details

Home

© RCABC 2024
No reproduction of this material, in whole or in part, is lawful without the expressed permission of the RCABC Guarantee Corp.