Difference between revisions of "Draft CD 11"

Jump to: navigation, search

Difference between revisions of "Draft CD 11"

Line 1: Line 1:
=Main heading=
+
{| class="wikitable" | style="color: black; background-color: orange; width: 100%;text-align:center"
=Main heading=
+
| colspan="2"  | <big>'''''Notice to Reader'''''</big>
=Main heading=
+
|-
=Main heading=
+
| style="color: black; background-color: #ffffcc; width: 100%;text-align:center" | Images used in a Construction Detail are representative and <u>not intended in their representation of an assembly to be prescriptive</u>.  Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the Standards, Guiding Principles and Recommendations of the '''RoofStar Guarantee Standards''' for a Waterproofing or Water-shedding System. Actual design with respect to dimensions, the selection of materials and their application remains the responsibility of the ''Design Authority''.<br><br>The full text of applicable '''''RoofStar Guarantee Standards''''' may be read by using the <span style="color:#6495ed">'''blue hyperlinks'''</span>
 +
|}
 +
<div class="panel panel-success">
 +
<div class="panel-heading"><big>'''SBS Details'''</big></div>
 +
<div class="panel-body">
 +
<div class="col-md-6">
 +
<div style="text-align:center; vertical-align:center">
 +
[[File:ASM 10.4.3 Ridge (Vented).jpg|class=img-responsive | link=http://rpm.rcabc.org/images/3/3d/ASM_10.4.3_Ridge_%28Vented%29.jpg]]
 +
</div>
 +
 
 +
::Click below for a printable version of this page (N/A)
 +
 
 +
<div style="width:150px; text-align: left;">
 +
:[[File:Pdf.png|100 px|link=http://rpm.rcabc.org/images/5/52/D1.7.6-3_Print_Sheet.pdf|'''Print Sheet''']]
 +
</div>
 +
 
 +
 
 +
</div><!-- COL-MD-6 -->
 +
 
 +
<div class="col-md-6">
 +
=== WORK INCLUDED ===
 +
;(1) [[RoofStar Guarantee Standards for ASM Roof Assemblies#ASMUNDERLAYMENT|'''Underlayment''']]: The type of underlay required is determined by roof slope.
 +
;(2) [[RoofStar Guarantee Standards for ASM Roof Assemblies#ASMSEP-VENT|'''Separation layer''']]: Vapour-permeable layer over insulation, required on all insulated Architectural Sheet Metal Roof Systems.  The material must be located between the insulation and metal panels (see [http://rpm.rcabc.org/index.php?title=RoofStar_Guarantee_Standards_for_Architectural_Sheet_Metal_(ASM)_Systems#Design_5 '''8.1.2 Design''']).
 +
;(3) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMCLIP |'''Architectural metal panel clip''']]: When a ventilation material is specified or required (Item 2), clips must be supported on an EPDM pad or supported according to the standards in [http://rpm.rcabc.org/index.php?title=RoofStar_Guarantee_Standards_for_Architectural_Sheet_Metal_(ASM)_Systems#Separation_and_Ventilation_Layers '''8.3.3 Separation and Ventilation Layers'''].
 +
;(4) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMCLOSURE |'''Architectural metal roof panel''']]
 +
;(5) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMCLOSURE |'''Bread-panned panel termination''']]: Must be bent and folded, not cut.
 +
;(6) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMDRAG |'''Drag-load fasteners''']]: Compatible non-corrosive fasteners.
 +
;(7) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMSEALANT |'''Sealant''']]
 +
;(8) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMZ |''''Z' Closure''']]: Set in accepted sealant or butyl tape and secured with compatible non-corrosive flathead fasteners.
 +
;(9) Ventilation screen
 +
;(10) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMZ | '''Ridge cap flashing''']]: Hooked onto ventilation screen.
 +
 
 +
<hr>
 +
 
 +
=== RELATED WORK BY OTHERS ===
 +
;(A) [[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems#ASMDECK|'''Acceptable Deck''']]: Installed with ventilation gap at peak.
 +
</div><!-- COL-6-MD -->
 +
</div><!-- PANEL BODY -->
 +
</div><!-- PANEL -->
 +
 
 +
'''NOTE''': Refer to '''''RoofStar Guarantee Standards''''' for additional requirements.
 +
 
 +
<hr>
 +
 
 +
[[RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems|<i class="fa fa-chevron-circle-right fa" ></i> RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems]]
 +
 
 +
[[Architectural Sheet Metal Construction Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''ASM Construction Details'']]

Revision as of 15:35, 5 October 2020

Notice to Reader
Images used in a Construction Detail are representative and not intended in their representation of an assembly to be prescriptive. Nor are they necessarily drawn to scale. Rather, they are provided to visually convey the Standards, Guiding Principles and Recommendations of the RoofStar Guarantee Standards for a Waterproofing or Water-shedding System. Actual design with respect to dimensions, the selection of materials and their application remains the responsibility of the Design Authority.

The full text of applicable RoofStar Guarantee Standards may be read by using the blue hyperlinks
SBS Details

ASM 10.4.3 Ridge (Vented).jpg

Click below for a printable version of this page (N/A)
Print Sheet


1 WORK INCLUDED

(1) Underlayment
The type of underlay required is determined by roof slope.
(2) Separation layer
Vapour-permeable layer over insulation, required on all insulated Architectural Sheet Metal Roof Systems. The material must be located between the insulation and metal panels (see 8.1.2 Design).
(3) Architectural metal panel clip
When a ventilation material is specified or required (Item 2), clips must be supported on an EPDM pad or supported according to the standards in 8.3.3 Separation and Ventilation Layers.
(4) Architectural metal roof panel
(5) Bread-panned panel termination
Must be bent and folded, not cut.
(6) Drag-load fasteners
Compatible non-corrosive fasteners.
(7) Sealant
(8) 'Z' Closure
Set in accepted sealant or butyl tape and secured with compatible non-corrosive flathead fasteners.
(9) Ventilation screen
(10) Ridge cap flashing
Hooked onto ventilation screen.

2 RELATED WORK BY OTHERS

(A) Acceptable Deck
Installed with ventilation gap at peak.

NOTE: Refer to RoofStar Guarantee Standards for additional requirements.


RoofStar Guarantee Standards for Architectural Sheet Metal (ASM) Systems

Back to ASM Construction Details