− | <big><big><big><big><big>ASM | + | <big><big><big><big><big>ASM | Ridge (Unvented, Insulated) ([[ASM_Roof_Systems_Standard#10.3.2.3. General Application Requirements for Perimeters and Walls | Article 10.3.2.3.]] and [[ASM_Roof_Systems_Standard#10.3.4.1. Ridges | Article 10.3.4.1.]])</big></big></big></big></big> |
− | { | + | {{Template:Construction Details Header}} |
− | |||
− | |||
− | |||
− | |||
<div class="panel panel-success"> | <div class="panel panel-success"> | ||
<div class="panel-heading"><big>'''SBS Details'''</big></div> | <div class="panel-heading"><big>'''SBS Details'''</big></div> |
Revision as of 16:21, 28 June 2022
Division D - Construction Details
ASM | Ridge (Unvented, Insulated) ( Article 10.3.2.3. and Article 10.3.4.1.)
Notice to Reader | |
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).
The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text. |
SBS Details
1 WORK INCLUDED
- (1) Underlayment
- The type of underlay required is determined by roof slope.
- (2) Ridge girts
- May be required by engineer for panel drag load fasteners. Secured using compatible non-corrosive fasteners.
- (3) Insulation
- Offset and stagger layers 300 mm (12").
- (4) Vapour-permeable separation membrane
- Installed over insulation and required on all insulated Architectural Sheet Metal Roof Systems. The material must be located between the insulation and metal panels/ventilation material (see 8.1.2 Design).
- (5) Ventilation layer
- A ventilation space is required on slopes less than 1:3; entangled mesh (shown) may be used as void fill. The ventilation space facilitates drying as condensation forms on the underside of the metal panels.
- (6) Architectural metal roof panel
- Top end of panels must be "bread-panned". Clips are not illustrated.
- (7) Drag-load fasteners
- Compatible non-corrosive fasteners.
- (8) Foam closures
- may be used to close ridge when cap flashing is mechanically attached to the panels ribs (see 10.3.5.3 (1)(2)).
- (9) Ridge cap flashing
- (10) Fasteners
- See 10.3.5.3 (1)(2).
2 RELATED WORK BY OTHERS
- (A) Acceptable Deck
NOTE: See the Standard for additional requirements.
Back to ASM Roof System Details