Difference between revisions of "SBS Air and Vapour Controls (field)"

Jump to: navigation, search

Difference between revisions of "SBS Air and Vapour Controls (field)"

(Tag: New redirect)
 
(Tag: Removed redirect)
Line 1: Line 1:
#REDIRECT [[ASM Air and Vapour Controls (Field)]]
+
{{Template:RPM Info}}
 +
 
 +
{{DISPLAYTITLE:<span style="position: absolute; clip: rect(1px 1px 1px 1px); clip: rect(1px, 1px, 1px, 1px);">{{FULLPAGENAME}}</span>}}
 +
__NOTOC__
 +
 
 +
<big><big>Division D - Construction Details</big></big>
 +
<hr>
 +
<big><big><big><big><big>SBS | Air and Vapour Controls (Field) ([[SBS_Roof_Systems_Standard#6.3.2.1._Continuity_and_Support | Article 6.3.2.1.]])</big></big></big></big></big>
 +
{{Template:Construction Details Header}}
 +
<div class="panel panel-success">
 +
<div class="panel-heading"><big>'''"All Systems" Details'''</big></div>
 +
<div class="panel-body">
 +
<div class="col-md-6">
 +
<div style="text-align:center; vertical-align:center">
 +
[[File:Figure 6.3.1-1.jpg|class=img-responsive | link=https://rpm.rcabc.org/images/5/54/Figure_6.3.1-1.jpg]]
 +
<br>
 +
<div class="col-md-8">
 +
[[File:Figure 6.3.1-2.jpg|class=img-responsive | link=https://rpm.rcabc.org/images/d/d0/Figure_6.3.1-2.jpg]]
 +
</div>
 +
</div>
 +
 
 +
<div class="col-md-6">
 +
::Click below for a printable version of this page (under development)
 +
 
 +
<div style="width:150px; text-align: left;">
 +
:[[File:Pdf.png|100 px|link=|'''Print Sheet''']]
 +
</div>
 +
</div>
 +
 
 +
</div><!-- COL-MD-6 -->
 +
<div class="col-md-6">
 +
=== WORK INCLUDED ===
 +
;(1) [[ASM Roof Systems Standard#PART_5|'''Supporting Deck Overlay''']]: Recommended over steel decks, to provide continuous support for membrane control layers (this fulfills the requirement for continuity, ''British Columbia Building Code'', Div. B, '''5.4.1.2''' ('''3''')).
 +
;(2) [[SBS Roof Systems Standard#PART_6|'''Air or Vapour Controls''']]: Self-adhering membrane (typical).
 +
;(3) [[SBS Roof Systems Standard#PART_6|'''Metal Support''']]: For fully or intermittently unsupported side or end laps.  Use pre-finished galvanized steel (min. 24 Ga.), fabricated at least 100 mm (4”) wider than membrane overlaps, and secured with compatible flat-head fasteners (two fasteners per flute, or as otherwise specified).
 +
;(4) [[SBS Roof Systems Standard#PART_6|'''Long edges (side laps)''']]:Centre membrane runs along top flutes of steel deck (applicable when no deck overlay is specified and installed). Overlap membrane side laps at least 50 mm (2”), or as specified by the membrane manufacturer (whichever is greater).  Side laps must be fully supported by the roof deck or a metal support.
 +
;(5) [[SBS Roof Systems Standard#PART_6|'''End laps''']]:Overlap the roll ends at least 100 mm (4”), or as specified by the membrane manufacturer (whichever is greater).  End laps must be fully supported by the roof deck or a metal support.
 +
 
 +
<hr>
 +
 
 +
=== RELATED WORK BY OTHERS ===
 +
;(A) [[SBS Roof Systems Standard#PART_2|'''Acceptable Deck''']]
 +
</div><!-- COL-6-MD -->
 +
</div><!-- PANEL BODY -->
 +
</div><!-- PANEL -->
 +
 
 +
'''NOTE''': See the [[SBS Roof Systems Standard | '''Standard''']] for additional requirements.
 +
 
 +
<hr>
 +
 
 +
[[SBS Roof System Details|<i class="fa fa-chevron-circle-left fa" ></i> Back to ''"SBS" Roof System Details'']]
 +
 
 +
[[Main Page | <i class="fa fa-home fa"></i> Home]]
 +
 
 +
{{Tempate:RPM Page Footer with Copyright and Current Date}}

Revision as of 14:51, 28 October 2022



Division D - Construction Details


SBS | Air and Vapour Controls (Field) ( Article 6.3.2.1.)

Notice to Reader
Images used in a Construction Detail are representative and not prescriptive, and are not necessarily drawn to scale. They are intended to support the related Standard (Ref. Division A, Article 2.2.1.2.).

The reader may link to the related Article in the detail title, or link to the Standard as it relates to a specific element in the detail. All hyperlinks are displayed blue text.

"All Systems" Details

Figure 6.3.1-1.jpg

Figure 6.3.1-2.jpg

Click below for a printable version of this page (under development)
Print Sheet

1 WORK INCLUDED

(1) Supporting Deck Overlay
Recommended over steel decks, to provide continuous support for membrane control layers (this fulfills the requirement for continuity, British Columbia Building Code, Div. B, 5.4.1.2 (3)).
(2) Air or Vapour Controls
Self-adhering membrane (typical).
(3) Metal Support
For fully or intermittently unsupported side or end laps. Use pre-finished galvanized steel (min. 24 Ga.), fabricated at least 100 mm (4”) wider than membrane overlaps, and secured with compatible flat-head fasteners (two fasteners per flute, or as otherwise specified).
(4) Long edges (side laps)
Centre membrane runs along top flutes of steel deck (applicable when no deck overlay is specified and installed). Overlap membrane side laps at least 50 mm (2”), or as specified by the membrane manufacturer (whichever is greater). Side laps must be fully supported by the roof deck or a metal support.
(5) End laps
Overlap the roll ends at least 100 mm (4”), or as specified by the membrane manufacturer (whichever is greater). End laps must be fully supported by the roof deck or a metal support.

2 RELATED WORK BY OTHERS

(A) Acceptable Deck

NOTE: See the Standard for additional requirements.


Back to "SBS" Roof System Details

Home