Difference between revisions of "Materials:DensDeck Prime with EONIC Roof Board"

Jump to: navigation, search

Difference between revisions of "Materials:DensDeck Prime with EONIC Roof Board"

Line 11: Line 11:
 
;Accepted for '''''RoofStar Guarantee Program''''': Date TBA
 
;Accepted for '''''RoofStar Guarantee Program''''': Date TBA
 
;:
 
;:
;'''Product Summary''':  
+
;'''Product Summary''': '''DensDeck Roof Guard''' is a water-resistant treated gypsum board manufactured with an embedded non structural fibreglass mat facer and a water-resistant treated core. '''DensDeck Prime Roof Guard''' is identical except that it has a treated surface to improve bonding.
DensDeck is a water-resistant treated gypsum board manufactured with an embedded non structural fibreglass mat facer and a water-resistant treated core. DensDeck Prime Roof Guard is identical except that it has a treated surface to improve bonding.
 
  
DensDeck is an accepted insulation overlay board in the RoofStar Guarantee Program. DensDeck Prime Roof Guard is an accepted insulation overlay board for adhered roof assemblies in the RGC Program.
+
:'''DensDeck Roof Guard''' is an accepted insulation overlay board in the '''''RoofStar Guarantee Program'''''. DensDeck Prime Roof Guard is an accepted insulation overlay board for adhered roof assemblies in the '''''RoofStar Guarantee Program'''''.
  
DensDeck and DensDeck Prime Roof Guard have achieved a very comprehensive Class A (UL 790) fire rating at Underwriters Laboratories due to their outstanding fire resistance.
+
:'''DensDeck Roof Guard''' and '''DensDeck Prime Roof Guard''' have achieved a very comprehensive Class A (UL 790) fire rating at Underwriters Laboratories due to their outstanding fire resistance.
 +
:* ASTM E 84 with '''DensDeck Roof Guard''' and '''DensDeck Prime Roof Guard''': Flame Spread 0, Smoke Developed 0
 +
:* ASTM E 119 with 5/8" DensDeck Fireguard Type X Roof Guard: UL Classified Type DGG
 +
 
 +
:'''DensDeck Roof Guard''' ® and '''DensDeck Prime Roof Guard'''™ Properties, Standards and Classifications
 +
 
 +
:<table border="1" cellspacing="0" cellpadding="5">
 +
  <tr>
 +
    <td valign="bottom" align="center"></td>
 +
    <td valign="bottom" align="center">&frac14;&quot; DensDeck Roof Guard</td>
 +
    <td valign="bottom" align="center">&frac14;&quot; DensDeck Prime Roof Guard</td>
 +
    <td valign="bottom" align="center">&frac12;&quot; DensDeck Roof Guard</td>
 +
    <td valign="bottom" align="center">&frac12;&quot; DensDeck Prime Roof Guard</td>
 +
    <td valign="bottom" align="center"><sup>5</sup>&frasl;<sub>8</sub>&quot; DensDeck Roof Guard</td>
 +
    <td valign="bottom" align="center"><sup>5</sup>&frasl;<sub>8</sub>&quot; DensDeck Prime Roof Guard</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Thickness, inches, nominal</td>
 +
    <td align="center">&frac14;&quot; &plusmn; 1/16&quot;</td>
 +
    <td align="center">&frac14;&quot; &plusmn; 1/16&quot;</td>
 +
    <td align="center">&frac12;&quot; &plusmn; 1/32&quot;</td>
 +
    <td align="center">&frac12;&quot; &plusmn; 1/32&quot;</td>
 +
    <td valign="top" align="center"><sup>5</sup>&frasl;<sub>8</sub>&quot; &plusmn; 1/32&quot;</td>
 +
    <td valign="top" align="center"><sup>5</sup>&frasl;<sub>8</sub>&quot; &plusmn; 1/32&quot;</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Width, standard</td>
 +
    <td align="center">4' &plusmn; <sup>1</sup>&frasl;<sub>8</sub>&quot;</td>
 +
    <td align="center">4' &plusmn; <sup>1</sup>&frasl;<sub>8</sub>&quot;</td>
 +
    <td align="center">4' &plusmn; <sup>1</sup>&frasl;<sub>8</sub>&quot;</td>
 +
    <td align="center">4' &plusmn; <sup>1</sup>&frasl;<sub>8</sub>&quot;</td>
 +
    <td valign="top" align="center">4' &plusmn; <sup>1</sup>&frasl;<sub>8</sub>&quot;</td>
 +
    <td valign="top" align="center">4' &plusmn; <sup>1</sup>&frasl;<sub>8</sub>&quot;</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Length, standard</td>
 +
    <td align="center">8' &plusmn; &frac14;&quot;</td>
 +
    <td align="center">8' &plusmn; &frac14;&quot;</td>
 +
    <td align="center">8' &plusmn; &frac14;&quot;</td>
 +
    <td align="center">8' &plusmn; &frac14;&quot;</td>
 +
    <td valign="top" align="center">8' &plusmn; &frac14;&quot;</td>
 +
    <td valign="top" align="center">8' &plusmn; &frac14;&quot;</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Weight, lb / sq. ft., nominal</td>
 +
    <td align="center">1.1</td>
 +
    <td align="center">1.15</td>
 +
    <td align="center">1.95</td>
 +
    <td align="center">1.975</td>
 +
    <td valign="top" align="center">2.5</td>
 +
    <td valign="top" align="center">2.55</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Surfacing</td>
 +
    <td align="center">Glass mat</td>
 +
    <td align="center">Glass mat with non-asphaltic coating</td>
 +
    <td align="center">Glass mat </td>
 +
    <td align="center">Glass mat with non-asphaltic coating </td>
 +
    <td valign="top">Glass mat </td>
 +
    <td valign="top" align="center">Glass mat with non-asphaltic coating </td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Flexural Strength 4, parallel, <br>
 +
      lb. min</td>
 +
    <td align="center">405</td>
 +
    <td align="center">405</td>
 +
    <td align="center">805</td>
 +
    <td align="center">805</td>
 +
    <td align="center">1005</td>
 +
    <td align="center">1005</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Flute Spanability1</td>
 +
    <td align="center">2<sup>5</sup>&frasl;<sub>8</sub>&quot;</td>
 +
    <td align="center">2<sup>5</sup>&frasl;<sub>8</sub>&quot;</td>
 +
    <td align="center">5&quot;</td>
 +
    <td align="center">5&quot;</td>
 +
    <td align="center">8&quot;</td>
 +
    <td align="center">8&quot;</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Permeance2 , Perms</td>
 +
    <td align="center">50</td>
 +
    <td align="center">50</td>
 +
    <td align="center">35</td>
 +
    <td align="center">35</td>
 +
    <td align="center">32</td>
 +
    <td align="center">32</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">&ldquo;R&rdquo; Value3</td>
 +
    <td align="center">.28</td>
 +
    <td align="center">.28</td>
 +
    <td align="center">.56</td>
 +
    <td align="center">.56</td>
 +
    <td align="center">.67</td>
 +
    <td align="center">.67</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Linear Variation with change in temp., in / in  &nbsp;&deg;F</td>
 +
    <td align="center">8.5 x 10-6</td>
 +
    <td align="center">8.5 x 10-6</td>
 +
    <td align="center">8.5 x 10-6</td>
 +
    <td align="center">8.5 x 10-6</td>
 +
    <td align="center">8.5 x 10-6</td>
 +
    <td align="center">8.5 x 10-6</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Linear Variation with change in Moisture, in / in %RH</td>
 +
    <td align="center">6.25 x 10-6 </td>
 +
    <td align="center">6.25 x 10-6</td>
 +
    <td align="center">6.25 x 10-6</td>
 +
    <td align="center">6.25 x 10-6</td>
 +
    <td align="center">6.25 x 10-6</td>
 +
    <td align="center">6.25 x 10-6</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Water Absorption 4, % max</td>
 +
    <td align="center">10.0</td>
 +
    <td align="center">10.0</td>
 +
    <td align="center">10.0</td>
 +
    <td align="center">10.0</td>
 +
    <td align="center">10.0</td>
 +
    <td align="center">10.0</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Compression Strength, <br> psi nominal</td>
 +
    <td align="center">500 - 900</td>
 +
    <td align="center">500 - 900</td>
 +
    <td align="center">500 - 900</td>
 +
    <td align="center">500 - 900</td>
 +
    <td align="center">500 - 900</td>
 +
    <td align="center">500 - 900</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Surface water Absorption4,<br> Grams, nominal</td>
 +
    <td align="center">2.5</td>
 +
    <td align="center">&lt;2.0</td>
 +
    <td align="center">2.5</td>
 +
    <td align="center">&lt;2.0</td>
 +
    <td align="center">2.5</td>
 +
    <td align="center">&lt;2.0</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Flame Spread,<br> Smoke Developed<br> (ASTM E 84)</td>
 +
    <td align="center">0</td>
 +
    <td align="center">0</td>
 +
    <td align="center">0</td>
 +
    <td align="center">0</td>
 +
    <td align="center">0</td>
 +
    <td align="center">0</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Fire Classification</td>
 +
    <td colspan="2" align="center">FMRC Class 1<br>(as overlayment)<br>UL Class A (UL 790)<br>ULC S-102</td>
 +
    <td colspan="2" align="center">FMRC Class 1 (FM 4450)<br> UL 1256, ULC S-126<br> UL Class A (UL 790)<br> ULC S-102</td>
 +
    <td colspan="2" valign="top" align="center">FMRC Class 1 (FM 4450)<br> UL 1256, ULC S-126<br> UL Classified &ldquo;P&rdquo; assemblies<br> ULC Classified &ldquo;R&rdquo; assemblies<br> ULC S-1-1<br> Class A (UL 790),<br> ULC S-107</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Mold and Mildew Resistance</td>
 +
    <td colspan="2" align="center">No growth7</td>
 +
    <td colspan="2" align="center">No growth7</td>
 +
    <td colspan="2" align="center">No growth7</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">FM Approvals6</td>
 +
    <td colspan="2" align="center">60 and 90 psf uplift / FM Class 1-90 as an overlayment</td>
 +
    <td colspan="2" align="center">FMRC 1-60, 1-90, 1-135</td>
 +
    <td colspan="2" align="center">FMRC 1-60, 1-90, 1-180</td>
 +
  </tr>
 +
  <tr>
 +
    <td valign="top">Bending Radius</td>
 +
    <td colspan="2" align="center">5&rsquo;</td>
 +
    <td colspan="2" align="center">8&rsquo;</td>
 +
    <td colspan="2" valign="top" align="center">12&rsquo;</td>
 +
  </tr>
 +
  <tr>
 +
    <td colspan="7" valign="top">
 +
Tested in accordance with ASTM E-661 (400 lb. conc. load only for <sup>1</sup>&frasl;<sub>2</sub>&quot; and <sup>5</sup>&frasl;<sub>8</sub>&quot;).
 +
#Tested in accordance with ASTM E-96 (dry cup method).
 +
#Tested in accordance with ASTM C 518 (heat flow meter).
 +
#Tested in accordance with ASTM C 473.
 +
#ASTM C 1177 minimums.
 +
#Higher wind uplift ratings have been achieved by numerous membrane manufacturers using DensDeck Roof Guard in their FMRC-approved construction designs.
 +
#Tested in accordance with ASTM D 3273. </td>
 +
  </tr>
 +
</table>
  
* ASTM E 84 with DensDeck and DensDeck Prime Roof Guard: Flame Spread 0, Smoke Developed 0
 
* ASTM E 119 with 5/8" DensDeck Fireguard Type X Roof Guard: UL Classified Type DGG
 
  
 
Due to the outstanding fire performance of 5/8" DensDeck Fireguard Type X Roof Guard, this product can replace any generic Type X gypsum board in an assembly in the UL Fire Resistance Directory under the prefix &#8220;P&#8221;.
 
Due to the outstanding fire performance of 5/8" DensDeck Fireguard Type X Roof Guard, this product can replace any generic Type X gypsum board in an assembly in the UL Fire Resistance Directory under the prefix &#8220;P&#8221;.

Revision as of 15:19, 4 November 2016

Notice to the Reader:

The roofing assembly / material information published in the RCABC Roofing Practices Manual and offered below does NOT represent a complete set of the manufacturer’s data or specifications. The preparation of a detailed specification is the responsibility of the design authority.

Manufacturer: Georgia-Pacific Canada Ltd.
Accepted for RoofStar Guarantee Program
Date TBA
Product Summary
DensDeck Roof Guard is a water-resistant treated gypsum board manufactured with an embedded non structural fibreglass mat facer and a water-resistant treated core. DensDeck Prime Roof Guard is identical except that it has a treated surface to improve bonding.
DensDeck Roof Guard is an accepted insulation overlay board in the RoofStar Guarantee Program. DensDeck Prime Roof Guard is an accepted insulation overlay board for adhered roof assemblies in the RoofStar Guarantee Program.
DensDeck Roof Guard and DensDeck Prime Roof Guard have achieved a very comprehensive Class A (UL 790) fire rating at Underwriters Laboratories due to their outstanding fire resistance.
  • ASTM E 84 with DensDeck Roof Guard and DensDeck Prime Roof Guard: Flame Spread 0, Smoke Developed 0
  • ASTM E 119 with 5/8" DensDeck Fireguard Type X Roof Guard: UL Classified Type DGG
DensDeck Roof Guard ® and DensDeck Prime Roof Guard™ Properties, Standards and Classifications
¼" DensDeck Roof Guard ¼" DensDeck Prime Roof Guard ½" DensDeck Roof Guard ½" DensDeck Prime Roof Guard 58" DensDeck Roof Guard 58" DensDeck Prime Roof Guard
Thickness, inches, nominal ¼" ± 1/16" ¼" ± 1/16" ½" ± 1/32" ½" ± 1/32" 58" ± 1/32" 58" ± 1/32"
Width, standard 4' ± 18" 4' ± 18" 4' ± 18" 4' ± 18" 4' ± 18" 4' ± 18"
Length, standard 8' ± ¼" 8' ± ¼" 8' ± ¼" 8' ± ¼" 8' ± ¼" 8' ± ¼"
Weight, lb / sq. ft., nominal 1.1 1.15 1.95 1.975 2.5 2.55
Surfacing Glass mat Glass mat with non-asphaltic coating Glass mat Glass mat with non-asphaltic coating Glass mat Glass mat with non-asphaltic coating
Flexural Strength 4, parallel,
lb. min
405 405 805 805 1005 1005
Flute Spanability1 258" 258" 5" 5" 8" 8"
Permeance2 , Perms 50 50 35 35 32 32
“R” Value3 .28 .28 .56 .56 .67 .67
Linear Variation with change in temp., in / in  °F 8.5 x 10-6 8.5 x 10-6 8.5 x 10-6 8.5 x 10-6 8.5 x 10-6 8.5 x 10-6
Linear Variation with change in Moisture, in / in %RH 6.25 x 10-6 6.25 x 10-6 6.25 x 10-6 6.25 x 10-6 6.25 x 10-6 6.25 x 10-6
Water Absorption 4, % max 10.0 10.0 10.0 10.0 10.0 10.0
Compression Strength,
psi nominal
500 - 900 500 - 900 500 - 900 500 - 900 500 - 900 500 - 900
Surface water Absorption4,
Grams, nominal
2.5 <2.0 2.5 <2.0 2.5 <2.0
Flame Spread,
Smoke Developed
(ASTM E 84)
0 0 0 0 0 0
Fire Classification FMRC Class 1
(as overlayment)
UL Class A (UL 790)
ULC S-102
FMRC Class 1 (FM 4450)
UL 1256, ULC S-126
UL Class A (UL 790)
ULC S-102
FMRC Class 1 (FM 4450)
UL 1256, ULC S-126
UL Classified “P” assemblies
ULC Classified “R” assemblies
ULC S-1-1
Class A (UL 790),
ULC S-107
Mold and Mildew Resistance No growth7 No growth7 No growth7
FM Approvals6 60 and 90 psf uplift / FM Class 1-90 as an overlayment FMRC 1-60, 1-90, 1-135 FMRC 1-60, 1-90, 1-180
Bending Radius 5’ 8’ 12’

Tested in accordance with ASTM E-661 (400 lb. conc. load only for 12" and 58").

  1. Tested in accordance with ASTM E-96 (dry cup method).
  2. Tested in accordance with ASTM C 518 (heat flow meter).
  3. Tested in accordance with ASTM C 473.
  4. ASTM C 1177 minimums.
  5. Higher wind uplift ratings have been achieved by numerous membrane manufacturers using DensDeck Roof Guard in their FMRC-approved construction designs.
  6. Tested in accordance with ASTM D 3273.


Due to the outstanding fire performance of 5/8" DensDeck Fireguard Type X Roof Guard, this product can replace any generic Type X gypsum board in an assembly in the UL Fire Resistance Directory under the prefix “P”.

  • 5/8" DensDeck Fireguard Type X Roof Guard is classified by Underwriters Laboratories and can be used in the following UL “P” assemblies: P225, P227, P230, P232, P235, P254, P257, P259, P266, P508, P510, P512, P514, P518, P701, P713, P714, P717, P718, P719, P720, P722, P724, P725, P726, P727, P728, P729, P730, P731, P732, P733, P734, P735, P736, P738, P739, P740, P801, P803, P805, P811, P813, P814, P815, P818, P819, P824, P825, P826, P828, P921
  • UL of Canada R210, R217, R222, R223, R224, R702, R703, R705, R804, R806, R808
  • ANSI / UL 1256 Steiner Tunnel “Fire Classified Construction”. This listing allows direct application on steel decking with ¼", ½" or 5/8" DensDeck or DensDeck Prime Roof Guard under foamed plastic insulations.
Click below for the Technical Data Sheet (TBA)
Technical Data Sheet



Back to Accepted Materials