Difference between revisions of "CSA Tested Assemblies Draft 1"
Difference between revisions of "CSA Tested Assemblies Draft 1"
(→PARS) |
(→AARS) |
||
Line 116: | Line 116: | ||
</tab> | </tab> | ||
<tab name="PVC Membrane Assemblies"> | <tab name="PVC Membrane Assemblies"> | ||
− | + | No Tested Assemblies submitted | |
</tab> | </tab> | ||
<tab name="BUR Assemblies"> | <tab name="BUR Assemblies"> |
Revision as of 21:30, 9 June 2020
1 MARS
Using the Tables
The tables on the adjacent tabs display data and links to Tested Assembly Reports listed by the membrane type shown on the tab. Dynamic Wind Uplift (DUR) values are shown in sortable columns; to sort a column, click the column heading. You may also sort the data by manufacturer (click the column heading). Deck types tested with the Assembly are shown in the far right column. |
Structure and Organization of Tables Before you use these tables, know the wind load requirements for the roof under design or construction by reading Part 3 SECURING the ROOF ASSEMBLY of the membrane standard applicable to the roof you are designing or constructing. The tables on this page display a collection of test data and downloadable reports offered for the purpose of designing and constructing a roof capable of resisting negative wind pressures, commonly referred to as "wind uplift". The data and reports are offered without endorsement by the RCABC; they are provided as a courtesy by the RoofStar Guarantee Program to assist the Design Authority with the task of designing a roof that satisfies Code requirements, that meets the designer's specific and numerous design preferences, and that will qualify for a RoofStar Guarantee. The British Columbia Building Code (or the Code having jurisdiction) requires a roof to be capable of resisting Specified Wind Loads (see the British Columbia Building Code, Part 4 (4.1.7 Wind Loads) and Part 5 (5.2.2.2 Determination of Wind Load), inclusive of the notes in the appendices). The reader will note that there are optional pathways by which a roof design can comply with the Code. One pathway is the use of a "Tested Assembly" - a roof assembly tested in controlled laboratory conditions to resist simulated wind pressures and gusts. The test must be conducted in strict conformity to CSA-A123.21 Standard test method for the dynamic wind uplift resistance of membrane roofing systems (CSA-A123.21). The results of the test are published in a report signed off by the accredited testing agency. Each report details the materials and securement methods of the assembly. Every detail in a Tested Assembly report is critical for the performance of a roof designed on the basis of the tested assembly. CSA-A123.21 requires that the published test limits for a roof system be adjusted with a safety factor of 1.5; this factor reduces the actual test results in order to account for variabilities that a laboratory cannot test for, such as strong wind gusts. The Dynamic Uplift Resistance (DUR) values in the following tables conform to this requirement, and can be validated by reviewing the downloadable test reports. It is imperative that the user of these reports become familiar with the structure and content typical in a Tested Assembly report. While you will see that each accredited testing agency publishes test results in their own preferred format, there is general consistency among the report styles in the type of data each report provides:
Drop-down lists (see the example below) provide a quick summary of the tested and optional materials available for the
Occasionally, some of these were not included in the test. When that is the case, the drop-down menu will indicate their absence with "N/A". The reader will also find a quick summary of the roof assembly, to show in very basic terms how the assembly is secured. This feature of the tables will be especially helpful when searching for a suitable PARS assembly. Note, however, that the summaries do not list specific adhesives or fasteners sizes and types; these details must be garnered from a detailed reading of the Tested Assembly report. Tested Assemblies and RoofStar Guarantee Standards Tested Assembly reports must always be read in conjunction with the RoofStar Guarantee Standards for the membrane system that is specified. For example, a roof assembly might be tested with a particular material or in a particular way that does not conform to the Standards. To conform to our Standards, some modifications to the Tested Assembly may be required, which may then preclude its use - for example, adding an insulation overlay panel where none was tested, because the assembly design requires one in order to conform to the RoofStar Guarantee Standards. When a conflict is apparent or obvious the Design Authority may find a way to 'yes' by examining the alternative materials listed in many Tested Assembly reports. Alternatives include membranes, insulation overlays, insulation panels and roof deck overlays (commonly listed as "thermal layers"). Some materials are listed as "optional" which means that while the assembly was tested without the constituent material (a deck overlay, for example), the Design Authority may opt to use one of the materials listed in the report. Drop-down menus of the tables below (see the "View options" buttons) display Accepted Materials that can be used in each Tested Assembly. If in doubt about how to use the Tested Assembly reports together with the RoofStar Guarantee Standards, contact the RoofStar Guarantee Program via email, or by calling (604) 882-9734. Accepted Materials and Material Substitutions We have selected Tested Assembly reports based on the membranes that will qualify for a RoofStar Guarantee Program, but there are tested assemblies that include one or more Secondary Materials, as for example insulation, that are not Accepted by the RoofStar Guarantee Program. Drop-down lists clearly show this by indicating when a materials is "not accepted". To ensure that the entire roof system complies with the Accepted Material requirements of the 'RoofStar Guarantee Program, follow the requirements in 3.2.1 Material Substitutions in Tested Assemblies: "When a manufacturer's Tested Assembly incorporates materials (and listed alternates) that are not part of the RoofStar Guarantee Program, the Design Authority must identify appropriate substitutions for those materials from the list of RoofStar-accepted Materials and consult the manufacturer concerning compatibility with the Tested Assembly. and direct the user to consult the membrane manufacturer in order to determine which Accepted materials will qualify as alternates." to be continued... |
Tested Assembly Report Data | Primary Materials | Other System Materials & Deck | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Dynamic Uplift Resistance | Roof Assembly Summary |
Test Report | Cap Membrane |
Base Membrane |
Plies | Insulation Overlay |
Insulation | Deck Overlay |
Deck Type | |
kPa | Psf |
Tested Assembly Report Data | Primary Materials | Other System Materials & Deck | ||||||||
---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Dynamic Uplift Resistance | Roof Assembly Summary |
Test Report | Membrane | Plies | Insulation Overlay |
Insulation | Deck Overlay |
Deck Type | |
kPa | Psf | |||||||||
Elevate (formerly Firestone) | -2.9 | -60 | FIR MARS 1-A | 1 | Steel | |||||
Elevate (formerly Firestone) | -3.2 | -67 | FIR MARS 2-A | 1 | Steel |
Tested Assembly Report Data | Primary Materials | Other System Materials & Deck | ||||||||
---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Dynamic Uplift Resistance | Roof Assembly Summary |
Test Report | Membrane | Plies | Insulation Overlay |
Insulation | Deck Overlay |
Deck Type | |
kPa | Psf | |||||||||
Carlisle Syntec Systems Canada | -3.4 | -70 | CAR MARS 1-A | 1 | Steel | |||||
Carlisle Syntec Systems Canada | -2.3 | -47 | CAR MARS 2-A | 1 | Steel | |||||
Johns Manville Corp. | -3.6 | -75 | JM AARS 1-A | 1 | Steel | |||||
Johns Manville Corp. | -3.6 | -75 | JM AARS 2-A | 1 | Steel |
2 PARS
The tables on the adjacent tabs display data and links to Tested Assembly Reports listed by the membrane type shown on the tab. Dynamic Wind Uplift (DUR) values are shown in sortable columns; to sort a column, click the column heading. You may also sort the data by manufacturer (click the column heading). Deck types that were tested with the Assembly are shown in the far right column.
Tested Assembly Report Data | Primary Materials | Other System Materials & Deck | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Dynamic Uplift Resistance | Roof Assembly Summary |
Test Report | Cap Membrane |
Base Membrane |
Plies | Insulation Overlay |
Insulation | Deck Overlay |
Deck Type | |
kPa | Psf |
Tested Assembly Report Data | Primary Materials | Other System Materials & Deck | ||||||||
---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Dynamic Uplift Resistance | Roof Assembly Summary |
Test Report | Membrane | Plies | Insulation Overlay |
Insulation | Deck Overlay |
Deck Type | |
kPa | Psf | |||||||||
Carlisle Syntec Systems Canada | -1.8 | -37.5 | CAR PARS 1-A | 1 | Steel | |||||
Elevate (formerly Firestone) | -2.1 | -45 | FIR PARS 2-A | 1 | Steel | |||||
Elevate (formerly Firestone) | -3.2 | -67 | FIR PARS 3-A | 1 | Steel |
Tested Assembly Report Data | Primary Materials | Other System Materials & Deck | ||||||||
---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Dynamic Uplift Resistance | Roof Assembly Summary |
Test Report | Membrane | Plies | Insulation Overlay |
Insulation | Deck Overlay |
Deck Type | |
kPa | Psf | |||||||||
Carlisle Syntec Systems Canada | -1.7 | -35 | CAR PARS 3-A | 1 | Steel | |||||
Elevate (formerly Firestone) | -2.9 | -60 | FIR PARS 4-A | 1 | Steel | |||||
Elevate (formerly Firestone) | -3.2 | -67 | FIR PARS 5-A | 1 | Steel | |||||
IKO Industries Ltd. | -4.9 | -100 | IKO-PARS 21-A | 1 | Steel | |||||
IKO Industries Ltd. | -3.4 | -70 | IKO-PARS 22-A | 1 | Steel | |||||
IKO Industries Ltd. | -4.9 | -100 | IKO-PARS 23-A | 1 | Steel |
Tested Assembly Report Data | Primary Materials | Other System Materials & Deck | ||||||||
---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Dynamic Uplift Resistance | Roof Assembly Summary |
Test Report | Membrane | Plies | Insulation Overlay |
Insulation | Deck Overlay |
Deck Type | |
kPa | Psf | |||||||||
Carlisle Syntec Systems Canada | -1.8 | -37.5 | CAR PARS 2-A | 1 | Steel |
Tested Assembly Report Data | Primary Materials | Other System Materials & Deck | ||||||||
---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Dynamic Uplift Resistance | Roof Assembly Summary |
Test Report | Membrane | Plies | Insulation Overlay |
Insulation | Deck Overlay |
Deck Type | |
kPa | Psf | |||||||||
IKO Industries Ltd. | -3.6 | -75 | IKO PARS 10-A | 4 | Steel | |||||
IKO Industries Ltd. | -2.9 | -60 | IKO PARS 11-A | 4 | Steel |
3 AARS
The tables on the adjacent tabs display data and links to Tested Assembly Reports listed by the membrane type shown on the tab. Dynamic Wind Uplift (DUR) values are shown in sortable columns; to sort a column, click the column heading. You may also sort the data by manufacturer (click the column heading). Deck types that were tested with the Assembly are shown in the far right column.
Tested Assembly Report Data | Primary Materials | Other System Materials & Deck | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Dynamic Uplift Resistance | Roof Assembly Summary |
Test Report | Cap Membrane |
Base Membrane |
Plies | Insulation Overlay |
Insulation | Deck Overlay |
Deck Type | |
kPa | Psf |
Tested Assembly Report Data | Primary Materials | Other System Materials & Deck | ||||||||
---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Dynamic Uplift Resistance | Roof Assembly Summary |
Test Report | Membrane | Plies | Insulation Overlay |
Insulation | Deck Overlay |
Deck Type | |
kPa | Psf | |||||||||
Elevate (formerly Firestone) | -2 | -41 | FIR AARS 1-A | 1 | Steel |
Tested Assembly Report Data | Primary Materials | Other System Materials & Deck | ||||||||
---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Dynamic Uplift Resistance | Roof Assembly Summary |
Test Report | Membrane | Plies | Insulation Overlay |
Insulation | Deck Overlay |
Deck Type | |
kPa | Psf | |||||||||
Elevate (formerly Firestone) | -2.4 | -50 | FIR AARS 2-A | 1 | Steel | |||||
IKO Industries Ltd. | -4.19 | -87.5 | IKO-AARS 25-A | 1 | Steel | |||||
IKO Industries Ltd. | -2.39 | -50 | IKO-AARS 26-A | 1 | Steel |
No Tested Assemblies submitted
Tested Assembly Report Data | Primary Materials | Other System Materials & Deck | ||||||||
---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Dynamic Uplift Resistance | Roof Assembly Summary |
Test Report | Membrane | Plies | Insulation Overlay |
Insulation | Deck Overlay |
Deck Type | |
kPa | Psf | |||||||||
IKO Industries Ltd. | -4.9 | -100 | IKO AARS 11-A | 4 | Steel |
© RCABC 2020
No reproduction of these Standards, in whole or in part, is lawful without the expressed permission of the RGC Guarantee Program.