WORK INCLUDED
(1) Trim: and the kick-out must be approximately 20-degree angle to the vertical slope.
(2) Fold Layout: Formed from a minimum 26 guage galvanized steel diverters shall extend a minimum 125 mm (5") up vertical surfaces 100 mm (4") to the roof.
(3) Breadpanned Corner Fold: Fold up must be equal in height to to the upstand of the flashing.
(4) Hidden Seam: Breadpan fold to be turned behind the upstand.
(5) Angle Trim: Kick-out can be angle trimmed and a drip edge formed at the outlet. Outlet is to extend a minimum of 25mm (1") lower than the edge of the roof material and lead water into the gutter where existing.
- NOTE
- Refer to RGC Guarantee Standards for additional requirements
- Proprietary soldered or welded diverter flashing may be used provided they conform to RGC Guarantee Standards.
Back to Asphalt Shingle Application