Template:AARS Membrane - SBS 2-Ply Base
Template:AARS Membrane - SBS 2-Ply Base
Revision as of 18:06, 29 June 2018 by James Klassen (talk | contribs)
- How to use the table
- In the table below look for maximum wind uplift values that exceed the requirements determined through the RCI calculator;
(NOTE: while the reports show two different values for tested maximum assembly strength, the RPM tables display only the values adjusted for the required safety factor of 1.5) - Open the report for the tested assembly that fits with the design parameters you have chosen and calculated, and examine the report. It will break down the assembly by its components. Ensure all the key components (Secondary materials, such as deck overlay, insulation and insulation overlay) are accepted by the RoofStar Guarantee Program (note that fasteners and adhesives currently are not listed in this Manual - use the materials specified in the wind test report, or consult the membrane manufacturer);
- In cases where a tested Secondary material is not accepted by the RoofStar Guarantee Program, look for alternates which often are published in the each report. In the absence of published alternates, consult the listed manufacturer for alternates that are accepted by the RoofStar Guarantee Program, and obtain the manufacturer's written approval.
Primary Material | Secondary Materials & Deck | Tested Assembly Report Data | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Membrane | Insulation Overlay |
Insulation | Deck Overlay |
Deck | Tested Systems |
kPa | Psf | Downloadable Test Report |
Test Facility | Test Facility Report No. | ||||
Low | High | Low | High | ||||||||||||
Henry Company Canada | Modified Plus G100 p / s | ---- | ---- | ---- | Steel | 1 Tested System | ---- | -3.80 | ---- | -80.00 | AARS Test Report 2 | Exova | 14-06-M0115-3, Revision 1 (S) | ||
Henry Company Canada | Modified Plus NP180 Tack | ---- | ---- | ---- | Steel | 1 Tested System | ---- | -4.79 | ---- | -100.00 | AARS Test Report 1 | Exova | 14-06-M0115-1B, Revision 1 (S) | ||
IKO Industries Ltd. | Modiflex HD-FS-Base | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Modiflex HD-SS-Base | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Modiflex MF-95 F/S | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Modiflex MF-95 S/S | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Modiflex MP-180 F/S | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Modiflex MP-180 SS | ---- | ---- | ---- | Steel Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- ---- |
-4.80 -2.40 -4.20 -1.40 |
---- ---- ---- ---- |
-100.00 -50.00 -87.00 -29.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 AARS Test Report 2 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 PUB-DRU 292025 | ||
IKO Industries Ltd. | Torchflex TP-180 FF | ---- | ---- | ---- | Steel Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- ---- |
-4.80 -2.40 -4.20 -2.50 |
---- ---- ---- ---- |
-100.00 -50.00 -87.00 -53.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 AARS Test Report 1 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 PUB-DRU278985 REV | ||
Soprema Inc. | Elastophene 180 S | ---- | ---- | ---- | Steel Steel |
1 Tested System 1 Tested System |
---- ---- |
-3.00 -2.40 |
---- ---- |
-63.00 -50.00 |
AARS Test Report 4 AARS Test Report 5 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 | ||
Soprema Inc. | Sopralene 180 S | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-3.00 -2.40 -3.00 |
---- ---- ---- |
-63.00 -50.00 -62.00 |
AARS Test Report 4 AARS Test Report 5 AARS Test Report 9 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 PUB-DRU229544 | ||
Soprema Inc. | Colply Base 410 | ---- | ---- | ---- | Steel | 1 Tested System | ---- | -2.40 | ---- | -50.00 | AARS Test Report 5 | exp. Service Inc. | PUB-DRU210983 | ||
Soprema Inc. | Elastophene 180 PS | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-3.00 -2.40 -3.00 |
---- ---- ---- |
-63.00 -50.00 -62.00 |
AARS Test Report 4 AARS Test Report 5 AARS Test Report 9 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 PUB-DRU229544 | ||
Soprema Inc. | Elastophene PS | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-3.00 -2.40 -3.00 |
---- ---- ---- |
-63.00 -50.00 -62.00 |
AARS Test Report 4 AARS Test Report 5 AARS Test Report 9 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 PUB-DRU229544 | ||
Soprema Inc. | Elastophene Flam | ---- | ---- | ---- | Steel Steel Steel Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System 2 Tested Systems 3 Tested Systems 2 Tested Systems |
---- ---- ---- -3.40 -2.40 -1.90 |
-4.30 -4.00 -4.30 -4.80 -4.60 -3.90 |
---- ---- ---- -72.00 -50.00 -40.00 |
-87.30 -83.30 -90.00 -100.00 -96.00 -83.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 7 AARS Test Report 8 AARS Test Report 10 AARS Test Report 11 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 PUB-DRC303964 PUB-DRU240661 PUB-DRU229544 PUB-DRU220544 | ||
Soprema Inc. | Sopraflash Flam Stick | ---- | ---- | ---- | Steel | 1 Tested System | ---- | -3.00 | ---- | -63.00 | AARS Test Report 6 | exp. Service Inc. | PUB-DRU209338 | ||
Soprema Inc. | Sopralene 180 PS | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-3.00 -2.40 -3.00 |
---- ---- ---- |
-63.00 -50.00 -62.00 |
AARS Test Report 4 AARS Test Report 5 AARS Test Report 9 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 PUB-DRU229544 | ||
Soprema Inc. | Sopralene 250 S | ---- | ---- | ---- | Steel Steel |
1 Tested System 1 Tested System |
---- ---- |
-3.00 -2.40 |
---- ---- |
-63.00 -50.00 |
AARS Test Report 4 AARS Test Report 5 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 | ||
Soprema Inc. | Sopralene Flam 180 | ---- | ---- | ---- | Steel Steel Steel Steel Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System 2 Tested Systems 1 Tested System 3 Tested Systems 2 Tested Systems |
---- ---- ---- -3.40 ---- -2.40 -1.90 |
-4.30 -4.00 -4.30 -4.80 -3.00 -4.60 -3.90 |
---- ---- ---- -72.00 ---- -50.00 -40.00 |
-87.30 -83.30 -90.00 -100.00 -62.00 -96.00 -83.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 7 AARS Test Report 8 AARS Test Report 9 AARS Test Report 10 AARS Test Report 11 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 PUB-DRC303964 PUB-DRU240661 PUB-DRU228011 PUB-DRU229544 PUB-DRU220544 | ||
Soprema Inc. | Sopralene Flam 250 | ---- | ---- | ---- | Steel Steel Steel Steel Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System 2 Tested Systems 1 Tested System 3 Tested Systems 2 Tested Systems |
---- ---- ---- -3.40 --- -2.40 -1.90 |
-4.30 -4.00 -4.30 -4.80 -3.00 -4.60 -3.90 |
---- ---- ---- -72.00 ---- -50.00 -40.00 |
-87.30 -55.50 -90.00 -100.00 -62.00 -96.00 -83.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 7 AARS Test Report 8 AARS Test Report 9 AARS Test Report 10 AARS Test Report 11 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 PUB-DRC303964 PUB-DRU240661 PUB-DRU228011 PUB-DRU229544 PUB-DRU220544 | ||
Soprema Inc. | Sopraply Base 510 | ---- | ---- | ---- | Steel | 1 Tested System | ---- | -3.00 | ---- | -62.00 | AARS Test Report 9 | exp. Service Inc. | PUB-DRU228011 | ||
Soprema Inc. | Sopraply Base 520 | ---- | ---- | ---- | Steel Steel Steel Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System 2 Tested Systems 3Tested Systems 2 Tested Systems |
---- ---- ---- -3.40 -2.40 -1.90 |
-4.30 -4.00 -4.30 -4.80 -4.60 -3.90 |
---- ---- ---- -72.00 -50.00 -40.00 |
-87.30 -83.30 -90.00 -100.00 -96.00 -83.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 7 AARS Test Report 8 AARS Test Report 10 AARS Test Report 11 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 PUB-DRC303964 PUB-DRU240661 PUB-DRU229544 PUB-DRU220544 |