AS Details:E2.7.11 (Counter-flashing - Diverter Flashing)

Jump to: navigation, search

AS Details:E2.7.11 (Counter-flashing - Diverter Flashing)

Revision as of 22:21, 21 December 2015 by James Klassen (talk | contribs)

7.1.5.9.jpg


WORK INCLUDED

(1) Trim: and the kick-out must be approximately 20-degree angle to the vertical slope.

(2) Fold Layout: Formed from a minimum 26 guage galvanized steel diverters shall extend a minimum 125 mm (5") up vertical surfaces 100 mm (4") to the roof.

(3) Breadpanned Corner Fold: Fold up must be equal in height to to the upstand of the flashing.

(4) Hidden Seam: Breadpan fold to be turned behind the upstand.

(5) Angle Trim: Kick-out can be angle trimmed and a drip edge formed at the outlet. Outlet is to extend a minimum of 25mm (1") lower than the edge of the roof material and lead water into the gutter where existing.

NOTE
  • Refer to RGC Guarantee Standards for additional requirements
  • Proprietary soldered or welded diverter flashing may be used provided they conform to RGC Guarantee Standards.


Back to Asphalt Shingle Application

Back to Asphalt Shingles Construction Details

Back to Construction Details