9.1.3.3. Panel Seams
- Panel seam heights, which must accommodate the increased potential for water ingress as roof slope diminishes, shall conform to Table 9.1.3.3.-A.
Table 9.1.3.3.-A
Minimum Requirements for Seam Types and Heights
Forming Part of Article 9.1.3.3.
Conditions
(see also Part 2 and Article 9.1.3.1.)Seam Height Minimums Permissible Seam Types > 1:3 (4" in 12") 25.4 mm (1") All ≥ 1:4 (3" in 12") 38.1 mm ( 1-1/2”) Mechanical Lock, Snap Lock, Snap Cap 1:6 (2" in 12") to ≤ 1:3 (4" in 12") 38.1 mm ( 1-1/2”) Mechanical Lock only (single or double) Less than 1:6 (2” in 12”)
(reviewed by RGC prior to tender)50.8 mm (2”) + butyl sealant in seam Mechanical Lock only (single or double) 50.8 mm (2”) Mechanical Lock only (double) Power-curved panels
(reviewed by RGC prior to tender)38.1 mm (1-1/2”) + butyl sealant in seam Mechanical Lock only (single or double) Locations with High Snow Loads
(defined in Article 1.1.3.3.)50.8 mm (2”) + butyl sealant in seam Mechanical Lock only (double)