AARS Tested Roof Assemblies
AARS Tested Roof Assemblies
USING TESTED ASSEMBLY REPORTS
The tables and products shown below provide basic material data related to roof assemblies tested for their performance in modulating and high winds, using the test method found in CSA A123.21. They also provide links to more information about the materials, including manufacturers' published Technical Data sheets. The reader is advised to use this information in conjunction with other RoofStar-accepted Materials, and with reference to roof system requirements derived from from appropriate wind uplift calculations (see the Wind-RCI calculator and reference notes and requirements outlined in Securing the Roof Assembly; also refer to the BC Building Code, Part 4 and Part 5). The information on this page is not intended for use as a comparison of material performance or quality. Nor should this information be construed as an endorsement of the suitability of any given material for a particular application. It is the sole responsibility of the Design Authority to assess the performance capability and material suitability for specific design requirements. Roof Assemblies are classified according to three different approaches to securement: MARS (Mechanically Attached Roof Systems), PARS (Partially Adhered Roof Systems), and AARS (Adhesive Applied Roof Systems). For a full explanation of these and other key details pertinent to an understanding of the test reports, visit Securing the Roof Assembly. In the tables below, the following definitions apply:
How to Use the Tables
|
USING TESTED ASSEMBLY REPORTS
The tables and products shown below provide basic material data related to roof assemblies tested for their performance in modulating and high winds, using the test method found in CSA A123.21. They also provide links to more information about the materials, including manufacturers' published Technical Data sheets. The reader is advised to use this information in conjunction with other RoofStar-accepted Materials, and with reference to roof system requirements derived from from appropriate wind uplift calculations (see the Wind-RCI calculator and reference notes and requirements outlined in Securing the Roof Assembly; also refer to the BC Building Code, Part 4 and Part 5). The information on this page is not intended for use as a comparison of material performance or quality. Nor should this information be construed as an endorsement of the suitability of any given material for a particular application. It is the sole responsibility of the Design Authority to assess the performance capability and material suitability for specific design requirements. Roof Assemblies are classified according to three different approaches to securement: MARS (Mechanically Attached Roof Systems), PARS (Partially Adhered Roof Systems), and AARS (Adhesive Applied Roof Systems). For a full explanation of these and other key details pertinent to an understanding of the test reports, visit Securing the Roof Assembly. In the tables below, the following definitions apply:
How to Use the Tables
|
1 SBS Membrane Systems
- The tables on the adjacent tabs display data and links to Tested Assembly Reports listed by the membrane type shown on the tab. These are reports that detail the makeup and performance of roof systems tested using the CSA-A123.21 Standard test method for the dynamic wind uplift resistance of membrane-roofing systems (latest edition). Use the maximum wind uplift values that equal or exceed the highest Specified Wind Loads; these are calculated using either the online Wind-RCI calculator or through manual engineering calculations (see the British Columbia Building Code, Division B, Part 4 (4.1.7 Specified Wind Loads));
(NOTE: while the reports show two different values for tested maximum assembly strength, the RPM tables display only the values adjusted for the required safety factor of 1.5) - Open the report for the tested assembly that fits with the design parameters you have chosen and calculated, and examine the report. It will break down the assembly by its components. Ensure all the key components (Secondary materials, such as deck overlay, insulation and insulation overlay) are accepted by the RoofStar Guarantee Program (note that fasteners and adhesives currently are not listed in this Manual - use the materials specified in the wind test report, or consult the membrane manufacturer);
- In cases where a tested Secondary material is not accepted by the RoofStar Guarantee Program, look for alternates which often are published in the each report. In the absence of published alternates, consult the manufacturer of the Tested Assembly for alternates that are accepted by the RoofStar Guarantee Program, and obtain the manufacturer's written approval.
Primary Material | Secondary Materials & Deck | Tested Assembly Report Data | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Membrane | Insulation Overlay |
Insulation | Deck Overlay |
Deck | Tested Systems |
kPa | Psf | Downloadable Test Report |
Test Facility | Test Facility Report No. | ||||
Low | High | Low | High | ||||||||||||
Henry Company Canada | Modified Plus G100 p / s | ---- | ---- | ---- | Steel | 1 Tested System | ---- | -3.80 | ---- | -80.00 | AARS Test Report 2 | Exova | 14-06-M0115-3, Revision 1 (S) | ||
Henry Company Canada | Modified Plus NP180 Tack | ---- | ---- | ---- | Steel | 1 Tested System | ---- | -4.79 | ---- | -100.00 | AARS Test Report 1 | Exova | 14-06-M0115-1B, Revision 1 (S) | ||
IKO Industries Ltd. | Modiflex HD-FS-Base | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Modiflex HD-SS-Base | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Modiflex MF-95 F/S | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Modiflex MF-95 S/S | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Modiflex MP-180 F/S | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Modiflex MP-180 SS | ---- | ---- | ---- | Steel Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- ---- |
-4.80 -2.40 -4.20 -1.40 |
---- ---- ---- ---- |
-100.00 -50.00 -87.00 -29.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 AARS Test Report 2 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 PUB-DRU 292025 | ||
IKO Industries Ltd. | Torchflex TP-180 FF | ---- | ---- | ---- | Steel Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- ---- |
-4.80 -2.40 -4.20 -2.50 |
---- ---- ---- ---- |
-100.00 -50.00 -87.00 -53.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 AARS Test Report 1 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 PUB-DRU278985 REV | ||
Soprema Inc. | Elastophene 180 S | ---- | ---- | ---- | Steel Steel |
1 Tested System 1 Tested System |
---- ---- |
-3.00 -2.40 |
---- ---- |
-63.00 -50.00 |
AARS Test Report 4 AARS Test Report 5 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 | ||
Soprema Inc. | Sopralene 180 S | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-3.00 -2.40 -3.00 |
---- ---- ---- |
-63.00 -50.00 -62.00 |
AARS Test Report 4 AARS Test Report 5 AARS Test Report 9 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 PUB-DRU229544 | ||
Soprema Inc. | Colply Base 410 | ---- | ---- | ---- | Steel | 1 Tested System | ---- | -2.40 | ---- | -50.00 | AARS Test Report 5 | exp. Service Inc. | PUB-DRU210983 | ||
Soprema Inc. | Elastophene 180 PS | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-3.00 -2.40 -3.00 |
---- ---- ---- |
-63.00 -50.00 -62.00 |
AARS Test Report 4 AARS Test Report 5 AARS Test Report 9 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 PUB-DRU229544 | ||
Soprema Inc. | Elastophene PS | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-3.00 -2.40 -3.00 |
---- ---- ---- |
-63.00 -50.00 -62.00 |
AARS Test Report 4 AARS Test Report 5 AARS Test Report 9 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 PUB-DRU229544 | ||
Soprema Inc. | Elastophene Flam | ---- | ---- | ---- | Steel Steel Steel Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System 2 Tested Systems 3 Tested Systems 2 Tested Systems |
---- ---- ---- -3.40 -2.40 -1.90 |
-4.30 -4.00 -4.30 -4.80 -4.60 -3.90 |
---- ---- ---- -72.00 -50.00 -40.00 |
-87.30 -83.30 -90.00 -100.00 -96.00 -83.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 7 AARS Test Report 8 AARS Test Report 10 AARS Test Report 11 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 PUB-DRC303964 PUB-DRU240661 PUB-DRU229544 PUB-DRU220544 | ||
Soprema Inc. | Sopraflash Flam Stick | ---- | ---- | ---- | Steel | 1 Tested System | ---- | -3.00 | ---- | -63.00 | AARS Test Report 6 | exp. Service Inc. | PUB-DRU209338 | ||
Soprema Inc. | Sopralene 180 PS | ---- | ---- | ---- | Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System |
---- ---- ---- |
-3.00 -2.40 -3.00 |
---- ---- ---- |
-63.00 -50.00 -62.00 |
AARS Test Report 4 AARS Test Report 5 AARS Test Report 9 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 PUB-DRU229544 | ||
Soprema Inc. | Sopralene 250 S | ---- | ---- | ---- | Steel Steel |
1 Tested System 1 Tested System |
---- ---- |
-3.00 -2.40 |
---- ---- |
-63.00 -50.00 |
AARS Test Report 4 AARS Test Report 5 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 | ||
Soprema Inc. | Sopralene Flam 180 | ---- | ---- | ---- | Steel Steel Steel Steel Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System 2 Tested Systems 1 Tested System 3 Tested Systems 2 Tested Systems |
---- ---- ---- -3.40 ---- -2.40 -1.90 |
-4.30 -4.00 -4.30 -4.80 -3.00 -4.60 -3.90 |
---- ---- ---- -72.00 ---- -50.00 -40.00 |
-87.30 -83.30 -90.00 -100.00 -62.00 -96.00 -83.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 7 AARS Test Report 8 AARS Test Report 9 AARS Test Report 10 AARS Test Report 11 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 PUB-DRC303964 PUB-DRU240661 PUB-DRU228011 PUB-DRU229544 PUB-DRU220544 | ||
Soprema Inc. | Sopralene Flam 250 | ---- | ---- | ---- | Steel Steel Steel Steel Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System 2 Tested Systems 1 Tested System 3 Tested Systems 2 Tested Systems |
---- ---- ---- -3.40 --- -2.40 -1.90 |
-4.30 -4.00 -4.30 -4.80 -3.00 -4.60 -3.90 |
---- ---- ---- -72.00 ---- -50.00 -40.00 |
-87.30 -55.50 -90.00 -100.00 -62.00 -96.00 -83.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 7 AARS Test Report 8 AARS Test Report 9 AARS Test Report 10 AARS Test Report 11 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 PUB-DRC303964 PUB-DRU240661 PUB-DRU228011 PUB-DRU229544 PUB-DRU220544 | ||
Soprema Inc. | Sopraply Base 510 | ---- | ---- | ---- | Steel | 1 Tested System | ---- | -3.00 | ---- | -62.00 | AARS Test Report 9 | exp. Service Inc. | PUB-DRU228011 | ||
Soprema Inc. | Sopraply Base 520 | ---- | ---- | ---- | Steel Steel Steel Steel Steel Steel |
1 Tested System 1 Tested System 1 Tested System 2 Tested Systems 3Tested Systems 2 Tested Systems |
---- ---- ---- -3.40 -2.40 -1.90 |
-4.30 -4.00 -4.30 -4.80 -4.60 -3.90 |
---- ---- ---- -72.00 -50.00 -40.00 |
-87.30 -83.30 -90.00 -100.00 -96.00 -83.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 7 AARS Test Report 8 AARS Test Report 10 AARS Test Report 11 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 PUB-DRC303964 PUB-DRU240661 PUB-DRU229544 PUB-DRU220544 |
Primary Material | Secondary Materials & Deck | Tested Assembly Report Data | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Manufacturer | Membrane | Insulation Overlay |
Insulation | Deck Overlay |
Deck | Tested Systems |
kPa | Psf | Downloadable Test Report |
Test Facility | Test Facility Report No. | ||||
Low | High | Low | High | ||||||||||||
Henry Company Canada | ModifiedPLUS NP250g T4 | ---- | ---- | ---- | Steel Steel |
1 1 |
---- ---- |
-3.80 -4.79 |
---- ---- |
-80.00 -100.00 |
AARS Test Report 1 AARS Test Report 2 |
Exova | 14-06-M0115-1B, Revision 1 (S) 14-06-M0115-3, Revision 1 (S) | ||
IKO Industries Ltd. | Armourcool Granular TP-HD Cap | ---- | ---- | ---- | Steel Steel Steel |
1 1 1 |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Modiflex MP-180 Cap | ---- | ---- | ---- | Steel Steel Steel |
1 1 1 |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Modiflex MP-250 Cap | ---- | ---- | ---- | Steel Steel Steel |
1 1 1 |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Modiflex MP-HD-Cap | ---- | ---- | ---- | Steel Steel Steel |
1 1 1 |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Torchflex TP-180 Cap | ---- | ---- | ---- | Steel Steel Steel |
1 1 1 |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Torchflex TP-250 Cap 5mm | ---- | ---- | ---- | Steel Steel Steel |
1 1 1 |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Torchflex TP-250 Cap | ---- | ---- | ---- | Steel Steel Steel Steel |
1 1 1 1 |
---- ---- ---- ---- |
-4.80 -2.40 -4.20 -2.50 |
---- ---- ---- ---- |
-100.00 -50.00 -87.00 -53 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 AARS Test Report 1 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 PUB-DRU278985 REV | ||
IKO Industries Ltd. | Torchflex TP-HD-Cap | ---- | ---- | ---- | Steel Steel Steel |
1 1 1 |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Prevent TP 250 Cap 4 mm | ---- | ---- | ---- | Steel Steel Steel |
1 1 1 |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Prevent TP-HD-Cap | ---- | ---- | ---- | Steel Steel Steel |
1 1 1 |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
IKO Industries Ltd. | Prevent Premium TP 250 Cap 4 mm | ---- | ---- | ---- | Steel Steel Steel |
1 1 1 |
---- ---- ---- |
-4.80 -2.40 -4.20 |
---- ---- ---- |
-100.00 -50.00 -87.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 |
exp. Service Inc. | PUB-DRU292547 PUB-DRU285762 PUB-DRU285764 | ||
Soprema Inc. | Colply Traffic Cap 460 | ---- | ---- | ---- | Steel Steel |
1 1 |
---- ---- |
-3.00 -2.40 |
---- ---- |
-63.00 -50.00 |
AARS Test Report 4 AARS Test Report 5 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 | ||
Soprema Inc. | Colply Traffic Cap FR 461 | ---- | ---- | ---- | Steel Steel |
1 1 |
---- ---- |
-3.00 -2.40 |
---- ---- |
-63.00 -50.00 |
AARS Test Report 4 AARS Test Report 5 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 | ||
Soprema Inc. | Soprafix Traffic Cap 660 | ---- | ---- | ---- | Steel Steel |
1 1 |
---- ---- |
-2.90 -2.70 |
---- ---- |
-58.20 -55.50 |
AARS Test Report 1 AARS Test Report 2 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 | ||
Soprema Inc. | Soprafix Traffic Cap FR 661 | ---- | ---- | ---- | Steel Steel |
1 1 |
---- ---- |
-2.90 -2.70 |
---- ---- |
-58.20 -55.50 |
AARS Test Report 1 AARS Test Report 2 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 | ||
Soprema Inc. | Sopralene 180 GR | ---- | ---- | ---- | Steel Steel |
1 1 |
---- ---- |
-3.00 -2.40 |
---- ---- |
-63.00 -50.00 |
AARS Test Report 4 AARS Test Report 5 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 | ||
Soprema Inc. | Sopralene 250 GR | ---- | ---- | ---- | Steel Steel |
1 1 |
---- ---- |
-3.00 -2.40 |
---- ---- |
-63.00 -50.00 |
AARS Test Report 4 AARS Test Report 5 |
exp. Service Inc. | PUB-DRU212868 PUB-DRU210983 | ||
Soprema Inc. | Sopraply Traffic Cap 560 | ---- | ---- | ---- | Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel |
1 1 1 2 1 3 2 3 2 1 1 |
---- ---- ---- -3.40 ---- -2.40 -1.90 -3.60 -3.60 ---- ---- |
-2.90 -2.70 -4.30 -4.80 -3.00 -4.60 -3.90 -4.30 -3.80 -2.40 -2.40 |
---- ---- ---- -72.00 ---- -50.00 -40.00 -75.00 -75.00 ---- ---- |
-58.20 -55.50 -90.00 -100.00 -62.00 -96.00 -83.00 -90.00 -80.00 -50.00 -50.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 7 AARS Test Report 8 AARS Test Report 9 AARS Test Report 10 AARS Test Report 11 AARS Test Report 12 AARS Test Report 13 AARS Test Report 14 AARS Test Report 15 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 PUB-DRC303964 PUB-DRU240661 PUB-DRU228011 PUB-DRU229544 PUB-DRU220544 PUB-DRU241032 PUB-DRU293410 PUB-DRU210498 PUB-DRU210736 | ||
Soprema Inc. | Sopraply Traffic Cap FR 561 | ---- | ---- | ---- | Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel |
1 1 1 2 1 3 2 3 2 1 1 |
---- ---- ---- -3.40 ---- -2.40 -1.90 -3.60 -3.60 ---- ---- |
-2.90 -2.70 -4.30 -4.80 -3.00 -4.60 -3.90 -4.30 -3.80 -2.40 -2.40 |
---- ---- ---- -72.00 ---- -50.00 -40.00 -75.00 -75.00 ---- ---- |
-58.20 -55.50 -90.00 -100.00 -62.00 -96.00 -83.00 -90.00 -80.00 -50.00 -50.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 7 AARS Test Report 8 AARS Test Report 9 AARS Test Report 10 AARS Test Report 11 AARS Test Report 12 AARS Test Report 13 AARS Test Report 14 AARS Test Report 15 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 PUB-DRC303964 PUB-DRU240661 PUB-DRU228011 PUB-DRU229544 PUB-DRU220544 PUB-DRU241032 PUB-DRU293410 PUB-DRU210498 PUB-DRU210736 | ||
Soprema Inc. | Sopralene Flam 250 GR | ---- | ---- | ---- | Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel |
1 1 1 1 1 2 1 3 2 3 2 1 1 |
---- ---- ---- ---- ---- -3.40 ---- -2.40 -1.90 -3.60 -3.60 ---- ---- |
-2.90 -2.70 -2.90 -3.00 -4.30 -4.80 -3.00 -4.60 -3.90 -4.30 -3.80 -2.40 -2.40 |
---- ---- ---- ---- ---- -72.00 ---- -50.00 -40.00 -75.00 -75.00 ---- ---- |
-58.20 -55.50 -60.00 -63.00 -90.00 -100.00 -62.00 -96.00 -83.00 -90.00 -80.00 -50.00 -50.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 3 AARS Test Report 6 AARS Test Report 7 AARS Test Report 8 AARS Test Report 9 AARS Test Report 10 AARS Test Report 11 AARS Test Report 12 AARS Test Report 13 AARS Test Report 14 AARS Test Report 15 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 SOPI-DRS-00231265-13-5100 PUB-DRU209338 PUB-DRC303964 PUB-DRU240661 PUB-DRU228011 PUB-DRU229544 PUB-DRU220544 PUB-DRU241032 PUB-DRU293410 PUB-DRU210498 PUB-DRU210736 | ||
Soprema Inc. | Sopralene Mammouth GR | ---- | ---- | ---- | Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel |
1 1 1 1 2 1 3 2 3 2 1 1 |
---- ---- ---- ---- -3.40 ---- -2.40 -1.90 -3.60 -3.60 ---- ---- |
-2.90 -2.70 -3.00 -4.30 -4.80 -3.00 -4.60 -3.90 -4.30 -3.80 -2.40 -2.40 |
---- ---- ---- ---- -72.00 ---- -50.00 -40.00 -75.00 -75.00 ---- ---- |
-58.20 -55.50 -63.00 -90.00 -100.00 -62.00 -96.00 -83.00 -90.00 -80.00 -50.00 -50.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 6 AARS Test Report 7 AARS Test Report 8 AARS Test Report 9 AARS Test Report 10 AARS Test Report 11 AARS Test Report 12 AARS Test Report 13 AARS Test Report 14 AARS Test Report 15 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 PUB-DRU209338 PUB-DRC303964 PUB-DRU240661 PUB-DRU228011 PUB-DRU229544 PUB-DRU220544 PUB-DRU241032 PUB-DRU293410 PUB-DRU210498 PUB-DRU210736 | ||
Soprema Inc. | SopraStar Flam HD GR | ---- | ---- | ---- | Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel |
1 1 1 1 2 1 3 2 3 2 1 1 |
---- ---- ---- ---- -3.40 ---- -2.40 -1.90 -3.60 -3.60 ---- ---- |
-2.90 -2.70 -3.00 -4.30 -4.80 -3.00 -4.60 -3.90 -4.30 -3.80 -2.40 -2.40 |
---- ---- ---- ---- -72.00 ---- -50.00 -40.00 -75.00 -75.00 ---- ---- |
-58.20 -55.50 -63.00 -90.00 -100.00 -62.00 -96.00 -83.00 -90.00 -80.00 -50.00 -50.00 |
AARS Test Report 1 AARS Test Report 2 AARS Test Report 6 AARS Test Report 7 AARS Test Report 8 AARS Test Report 9 AARS Test Report 10 AARS Test Report 11 AARS Test Report 12 AARS Test Report 13 AARS Test Report 14 AARS Test Report 15 |
exp. Service Inc. | RP-DRU210754 RAP-DRU240663 PUB-DRU209338 PUB-DRC303964 PUB-DRU240661 PUB-DRU228011 PUB-DRU229544 PUB-DRU220544 PUB-DRU241032 PUB-DRU293410 PUB-DRU210498 PUB-DRU210736 |
2 EPDM Membrane Systems
- The tables on the adjacent tabs display data and links to Tested Assembly Reports listed by the membrane type shown on the tab. These are reports that detail the makeup and performance of roof systems tested using the CSA-A123.21 Standard test method for the dynamic wind uplift resistance of membrane-roofing systems (latest edition). Use the maximum wind uplift values that equal or exceed the highest Specified Wind Loads; these are calculated using either the online Wind-RCI calculator or through manual engineering calculations (see the British Columbia Building Code, Division B, Part 4 (4.1.7 Specified Wind Loads));
(NOTE: while the reports show two different values for tested maximum assembly strength, the RPM tables display only the values adjusted for the required safety factor of 1.5) - Open the report for the tested assembly that fits with the design parameters you have chosen and calculated, and examine the report. It will break down the assembly by its components. Ensure all the key components (Secondary materials, such as deck overlay, insulation and insulation overlay) are accepted by the RoofStar Guarantee Program (note that fasteners and adhesives currently are not listed in this Manual - use the materials specified in the wind test report, or consult the membrane manufacturer);
- In cases where a tested Secondary material is not accepted by the RoofStar Guarantee Program, look for alternates which often are published in the each report. In the absence of published alternates, consult the manufacturer of the Tested Assembly for alternates that are accepted by the RoofStar Guarantee Program, and obtain the manufacturer's written approval.
Manufacturer | Product Name | Number of Tested Systems (per report) |
kPa (Low) | kPa (High) | Psf (Low) | Psf (High) | Deck Type | Downloadable Test Report | Test Facility | Test Facility Report No. |
---|---|---|---|---|---|---|---|---|---|---|
Firestone Building Products | Rubbergard EPDM Membrane | 1 Tested System | ---- | -2.00 | ---- | -41.00 | Steel | AARS Test Report 1 | exp. Service Inc. | PUB-DRU303357 |
Firestone Building Products | Rubbergard ECO White EPDM Membrane | 1 Tested System | ---- | -2.00 | ---- | -41.00 | Steel | AARS Test Report 1 | exp. Service Inc. | PUB-DRU303357 |
3 TPO Membrane Systems
- The tables on the adjacent tabs display data and links to Tested Assembly Reports listed by the membrane type shown on the tab. These are reports that detail the makeup and performance of roof systems tested using the CSA-A123.21 Standard test method for the dynamic wind uplift resistance of membrane-roofing systems (latest edition). Use the maximum wind uplift values that equal or exceed the highest Specified Wind Loads; these are calculated using either the online Wind-RCI calculator or through manual engineering calculations (see the British Columbia Building Code, Division B, Part 4 (4.1.7 Specified Wind Loads));
(NOTE: while the reports show two different values for tested maximum assembly strength, the RPM tables display only the values adjusted for the required safety factor of 1.5) - Open the report for the tested assembly that fits with the design parameters you have chosen and calculated, and examine the report. It will break down the assembly by its components. Ensure all the key components (Secondary materials, such as deck overlay, insulation and insulation overlay) are accepted by the RoofStar Guarantee Program (note that fasteners and adhesives currently are not listed in this Manual - use the materials specified in the wind test report, or consult the membrane manufacturer);
- In cases where a tested Secondary material is not accepted by the RoofStar Guarantee Program, look for alternates which often are published in the each report. In the absence of published alternates, consult the manufacturer of the Tested Assembly for alternates that are accepted by the RoofStar Guarantee Program, and obtain the manufacturer's written approval.
Product Name | Number of Tested Systems (per report) |
kPa (Low) | kPa (High) | Psf (Low) | Psf (High) | Deck Type | Downloadable Test Report | Test Facility | Test Facility Report No. | |
---|---|---|---|---|---|---|---|---|---|---|
Firestone Building Products | Ultraply 1.2 mm TPO Membrane | 1 Tested System | ---- | -2.04 | ---- | -50.00 | Steel | AARS Test Report 2 | exp. Service Inc. | PUB-DRU303358 |
Firestone Building Products | UltraPly 1.6 mm TPO Membrane | 1 Tested System | ---- | -2.04 | ---- | -50.00 | Steel | AARS Test Report 2 | exp. Service Inc. | PUB-DRU303358 |
4 PVC Membrane Systems
Under development