##Two part assembly consisting of a No. 16 MSG min thick coated steel base approximately 47.6 mm (1-7/8") wide and 40.9 mm (1-5/8") long and a No. 22 MSG min thick coated steel upper tab section. Fastened 600 mm (24") on centre. Height 61 mm (2-7/16") min, 75 mm (3") max, width 108 mm (4-5/16"); ''Knudson Manufacturing Inc.'' '''KR-24 Low-Floating Clip''', '''KR-24 High-Floating Clip''', or
 
##Two part assembly consisting of a No. 16 MSG min thick coated steel base approximately 47.6 mm (1-7/8") wide and 40.9 mm (1-5/8") long and a No. 22 MSG min thick coated steel upper tab section. Fastened 600 mm (24") on centre. Height 61 mm (2-7/16") min, 75 mm (3") max, width 108 mm (4-5/16"); ''Knudson Manufacturing Inc.'' '''KR-24 Low-Floating Clip''', '''KR-24 High-Floating Clip''', or
 
##One part assembly, No. 22 MSG min coated steel. Height, 59 mm (2-3/8") min, 75 mm (3") max, width 75 mm (3"); ''Knudson Manufacturing Inc.'' '''KR-24 Low-Fixed Clip''', '''KR-24 High-Fixed Clip''', fastened 600 mm (24") on centre.
 
##One part assembly, No. 22 MSG min coated steel. Height, 59 mm (2-3/8") min, 75 mm (3") max, width 75 mm (3"); ''Knudson Manufacturing Inc.'' '''KR-24 Low-Fixed Clip''', '''KR-24 High-Fixed Clip''', fastened 600 mm (24") on centre.
#'''Deck Requirements''': in keeping with the [http://rpm.rcabc.org/index.php/RoofStar_Guarantee_Standards_for_ASM_Systems RoofStar Guarantee Standards for ASM Systems].
+
#'''Deck Requirements''': in keeping with the [http://rpm.rcabc.org/index.php?title=Standard_for_Architectural_Sheet_Metal_(ASM)_Systems Standard for Architectural Sheet Metal (ASM) Systems].
  
 
====PROFILE====
 
====PROFILE====
Line 43: Line 43:
 
====PERFORMANCE REQUIREMENTS====
 
====PERFORMANCE REQUIREMENTS====
 
#'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
 
#'''Wind Uplift Standards''': Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also [http://{{SERVERNAME}}/index.php?title=ASM_Application_Guides_and_Notes Guides and Notes (Wind Resistance)] for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
#'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http://rpm.rcabc.org/index.php/RoofStar_Guarantee_Standards_for_ASM_Systems RoofStar Guarantee Standards for ASM Systems].
+
#'''Materials''':RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the [http://rpm.rcabc.org/index.php?title=Standard_for_Architectural_Sheet_Metal_(ASM)_Systems Standard for Architectural Sheet Metal (ASM) Systems].
  
 
<hr>
 
<hr>

Revision as of 18:12, 15 June 2021


The metal panel listed and described below is accepted for use in the RoofStar Guarantee Program.
Manufacturer
Tomtar Roofing & Sheet Metal Ltd.
Contact Address
See the current Membership list and contact information at www.rcabc.org
Product Group - Standing Seam Metal Roof System
Panel Machine
Knudson P2401
Panel Name
Tomtar P-2401 Standing Seam panel
Seam Type
Standing Seam (50 mm (2"))

The roofing assembly / material information published below and in the RCABC Roofing Practices Manual DOES NOT represent a complete set of the manufacturer's published data, nor does it represent a detailed specification. The preparation of a detailed specification is the responsibility of the design authority. For more information about this product or system, consult the manufacturer.

OVERVIEW

The Knudson P-2401 is an on-site continuous panel metal roofing machine. Panel profiles vary from 300 mm (12") to 500 mm (20") wide with a seam height of 50 mm (2").

On-site roll forming provides for the elimination of end laps with continuous panel forming capabilities in lengths up to nominal 46 m (150').

SYSTEM DESCRIPTION

  1. General: Standing seam panels employ a hidden fastening system for securement to a solid substrate. Panels are seamed together with a mechanical seamer.
  2. Range of application: on wood or metal sloped roofs; in commercial, institutional, industrial and residential construction; for re-roofing or new construction.
  3. Fasteners (Screws):
    1. For panel clip to steel attachment to be No. 12-16 by 22 mm (1") long self- drilling, self-tapping, hex-washer head plated steel screws used without sealing washers. Two fasteners per panel clip used, inserted into panel clip guide holes.
  4. Clips:
    1. Two part assembly consisting of a No. 16 MSG min thick coated steel base approximately 47.6 mm (1-7/8") wide and 40.9 mm (1-5/8") long and a No. 22 MSG min thick coated steel upper tab section. Fastened 600 mm (24") on centre. Height 61 mm (2-7/16") min, 75 mm (3") max, width 108 mm (4-5/16"); Knudson Manufacturing Inc. KR-24 Low-Floating Clip, KR-24 High-Floating Clip, or
    2. One part assembly, No. 22 MSG min coated steel. Height, 59 mm (2-3/8") min, 75 mm (3") max, width 75 mm (3"); Knudson Manufacturing Inc. KR-24 Low-Fixed Clip, KR-24 High-Fixed Clip, fastened 600 mm (24") on centre.
  5. Deck Requirements: in keeping with the Standard for Architectural Sheet Metal (ASM) Systems.

PROFILE

N/A

TECHNICAL DATA SHEET

N/A

SITE CONDITIONS

  1. Minimum roof slope is 1:6 (2" in 12"). Severe conditions (heavy snow or ice) minimum slope is 1:1.5 (8" in 12").

PERFORMANCE REQUIREMENTS

  1. Wind Uplift Standards: Engineered designs to resist wind uplift may refer to the British Columbia Building Code, Div. B, Appendix C, Table C-2 which lists various types of loads, including wind loads, for specific reference locations throughout the province. See also Guides and Notes (Wind Resistance) for a simplified calculation procedure. Regardless of the resources indicated here, the Design Authority is responsible to perform accurate wind load calculations and specify securement requirements.
  2. Materials:RoofStar (RGC) accepted metal panel systems shall be formed of steel conforming to the standards published in the Standard for Architectural Sheet Metal (ASM) Systems.